Defence Statutory Bodies & Commissions/Committees Closing in 3 days TDR #57649865

Tender For Repair / Replacement Of External Water Supply System & Connected Allied Works In The Aor Army Unit & Connected Md Accn, Certain Maintenance Of Lt Panels Including Repair Of Oh Lines & Ug Cable & Allied Services At Prtc & 106 Inf Bn Area An

Issued by Statutory Bodies & Commissions/Committees · Bengaluru Urban, Karnataka
Tender Value
42.50 Lakhs
Estimated cost
Bid Submission
21 Oct 2026
3 days left
EMD
85000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Bengaluru Urban → Karnataka
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair / Replacement Of External Water Supply System & Connected Allied Works In The Aor Army Unit & Connected Md Accn, Certain Maintenance Of Lt Panels Including Repair Of Oh Lines & Ug Cable & Allied Services At Prtc & 106 Inf Bn Area And Repair / Maintenance Of Solar Street Lights, Led Street Lights, Post Top Lanterns, Pathway Lights, Solar Water Heater In The Aor Of Army Units Under Ge (North) Bangalore

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 30-Sep-2026 8381Corrigendum BOQ 14-Oct-2026
2 14-Oct-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 21-Oct-2026

BOQ

Name of Work:- REPAIR / REPLACEMENT OF EXTERNAL WATER SUPPLY SYSTEM & CONNECTED ALLIED WORKS IN THE AOR ARMY UNIT & CONNECTED MD ACCN, CERTAIN MAINTENANCE OF LT PANELS INCLUDING REPAIR OF OH LINES & UG CABLE & ALLIED SERVICES AT PRTC & 106 INF BN AREA AND REPAIR / MAINTENANCE OF SOLAR STREET LIGHTS, LED STREET LIGHTS, POST TOP LANTERNS, PATHWAY LIGHTS, SOLAR WATER HEATER IN THE AOR OF ARMY UNITS UNDER GE (NORTH) BANGALORE
Sl. No. Item Description
1Excavation in trenches not exceeding 1.5 m depth and not exceeding 1.5m width and getting out in Soft/loose soil for laying of pipe lines.
2M & L excavation in trenches in soft/loose soil not less than 1.5 mtr deep and not exc 3 mtr in deep for pole foundation etc complete all as specified and as directed.
3Returning, refilling incl spreading, levelling watering and well ramming in layers not exceeding 25 cm thick with any type of soil all as directed
4Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 mtr above the starting point all as specified as directed.
5Taking up CI/DI water mains (including all fittings), with spigot and socket ends and lead joints/Titan Joints for the following size :- 150 mm bore
6All as per item No. 5 above but for100 mm bore
7All as per item No. 5 above but for80 mm bore
8S&F DI pipe (flanged / spigot type) laid in trenches of the following sizes :-150 mm dia
9All as per item No. 8 above but for100 mm dia
10All as per item No. 8 above but for80 mm dia Note :- (i) Cost of CI specials shall be measured and paid separetely.
11Cutting of DI/CI pipe in position for insertion of CI/DI specials of following sizes;-150 mm bore
12All as per item No. 11 above but for100 mm bore
13All as per item No. 11 above but for80 mm bore
14M&L for CI/DI Specials like bends, tappers, tee pieces all sockets, all spitgot, collars, caps & plugs any size & shape as ordered by Engineer- in- charge incl testing complete as specified & directed for the following sizes:-Up to 150 mm bore
15M&L Run lead joint for water mains of the following size of CI pipes :-150mm
16All as per item No. 15 above but for100mm
17All as per item No. 15 above but for80mmNote:- Excavation and earth work shall be measured and paid separately
18Dismantaling the sluice valves in various location and reconditioning the sluice valve by replacing SS spindle, spindle nuts with brass ring, gland nuts, gland packing etc and refixing after properly repairs of the following sizes:-200 mm dia bore
19All as per item No. 18 above but for150 mm dia bore
20All as per item No. 18 above but for100 mm dia bore
21All as per item No. 18 above but for80 mm dia bore
22M&L for repacking stuffing box of sluice valve spindle including taking a part and reassembling of following sizes:-150 mm bore
23All as per item No. 22 above but for100 mm bore
24All as per item No. 22 above but for80 mm bore
25Taking up the old/rusted/unsv GI/CI/HDPE/PPR pipes with fittings and connected control gate valves/ Sluice valve/non return valve/foot valve etc. from sump/ trenches/ floors/roof for the following size:- 15 mm dia
26All as per item No. 25 above but for20mm dia
27All as per item No. 25 above but for25mm dia
28All as per item No. 25 above but for40mm dia
29All as per item No. 25 above but for50mm dia
30All as per item No. 25 above but for80mm dia
31All as per item No. 25 above but for100mm dia
32S&F GI water tubing medium grade with all fitting (flanged / socket / union / tee etc) laid in trenches / walls / floors / roof of following sizes :-15 mm dia
33All as per item No. 32 above but for20mm dia
34All as per item No. 32 above but for25mm dia
35All as per item No. 32 above but for40mm dia
36All as per item No. 32 above but for50mm dia
37All as per item No. 32 above but for80mm dia
38All as per item No. 32 above but for100mm dia
39S&F in repair brass non return valve of the following size dia internal threded type complete including taking down the existing all as specified and as directed.63/65/80 mm dia
40All as per item No. 39 above but for100 mm dia
41Supply & fixing in replacement of the following size gun metal Gate valve with iron wheel.15 mm dia
42All as per item No. 41 above but for20 mm dia
43All as per item No. 41 above but for25 mm dia
44All as per item No. 41 above but for40 mm dia
45All as per item No. 41 above but for50 mm dia
46All as per item No. 41 above but for80 mm dia
47Dismantling Old valve pit complete with deteriorated MS cover and Construction of brick massonry valve pit chamber of inner dimension 150x150x100 cms suitable for sluice valves upto 150mm size, with PCC 1:4:8 type D-2 for foundation, brick work in cm 1:6 rendering 1:4, 15mm plastering, coping in PCC 1:2:4 type B-1, incl necessary earth work, including MS sheet cover of thickness 3.15mm on 50x50x6 mm angle iron framework including two coats of synthetic enamelled paint over a coat of red oxide primer with making provision of locking arrangement .
48Dismantling Old valve pit complete with deteriorated MS cover and Construction of brick massonry valve pit chamber of inner dimension 200x225x115 cms suitable for sluice valves upto 150mm size, with PCC 1:4:8 type D-2 for foundation, brick work in cm 1:6 rendering 1:4, 15mm plastering, coping in PCC 1:2:4 type B-1, incl necessary earth work, including MS sheet cover of thickness 3.15mm on 50x50x6 mm angle iron framework including two coats of synthetic enamelled paint over a coat of red oxide primer with making provision of locking arrangement .
49Dismantling Old valve pit complete with deteriorated MS cover and Construction of brick massonry valve pit chamber of inner dimension 200x250x115 cms suitable for sluice valves upto 150mm size, with PCC 1:4:8 type D-2 for foundation, brick work in cm 1:6 rendering 1:4, 15mm plastering, coping in PCC 1:2:4 type B-1, incl necessary earth work, including MS sheet cover of thickness 3.15mm on 50x50x6 mm angle iron framework including two coats of synthetic enamelled paint over a coat of red oxide primer with making provision of locking arrangement .
50S&F in replacement of sluice valve both side flanged and ISI marked (IS-780) of sluice valve cast iron body with S/S spindle and brass fly nuts, class PN-1.6 and cast iron hand wheel and joining with nut, bolt, washers and rubber insortion packing 6mm thick etc of following sizes:-200 mm dia bore
51All as per item No. 50 above but for150 mm dia bore
52All as per item No. 50 above but for100 mm dia bore
53All as per item No. 50 above but for80 mm dia bore
54Removing of unserviceable foot valve from tank and replacement with new CI foot valve ball type of following sizes:-125/100 mm dia bore
55All as per item No. 54 above but for80 mm dia bore
56All as per item No. 54 above but for50/63 mm dia bore
57Removing old unserviceable float valve from service tank supply and fix float valve with PVC body aluminium float rod, nylon float high pressure type Make:- Prayag) for the following size:-20 mm bore
58All as per item No. 57 above but for25 mm bore
59Taking out old unserviceable foot valve from UG sump and removing unserviceable leather from suction line and replacement the same with high quality leather including nuts, bolts, washer etc and servicing for the following sizes. 150 mm bore
60All as per item No. 59 above but for100 mm bore
61All as per item No. 59 above but for80 mm bore
62Supply and installation with testing complete of digital water level indication device operating on single phase supply direct display in 19 mm size (letter display) digit system in meter/CM of water of overhead tank ensuring alarm while water fall or rise over predetermined limits with the following description complete all as specified and as directed by Engineer-in-charge including dismantling old unserviceable water level indicator.(a) The entire unit must operate through a compact electronic circuit which must ensure reliable operation at 230V +10% at 50 Hz +5%, with reliable in display and alarm at low and high level head tank.(b) One circuit must be housed in high impact polystyrne molded box nylon mlded connection strips. The level system must resistance transducer, while unattested by corrosion and other contents avilable in water the product must be controlled by Micro switch.(c) The whole unit must electronically contolled and the upper level and lower level indications must be in two parts. Each complete part must be fitted in MS CRS sheet box separetaly. One must be installed at over head tank and second at pump house with proper powder coating paint with locking arrangements.
63M&L for testing 03/04 core copper conductor PVC insulated heavy duty unsheathed cable 1100 volts grade 0.5 Sqmm from control box to display meter in ducts/on ground/through existing pipes etc including taking out unserviceable flexible cable all as specified and as directed.
64M&L in replacement of Mechnical joints with rubber washer, nuts and bolts as existing at site of the following sizes of CI/DI pipes :-150 mm bore
65All as per item No. 64 above but for100 mm bore
66All as per item No. 64 above but for80 mm bore
67S&F in replacment of Air release valve of existing size suitable for centrifugal pump set complete all as specified and as directed.
68Supply and installed avaiation lights of LED Based all as specified and directed by Engr-in-Charge.
69M & L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.5 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr connected to and incl galvanized strip 32x6mm as earth lead up to 7.5 mtr long by means of nuts, bolts, thimbles,check nuts and washers etc made of galvanized iron connected to earthing test point all as shown in electrical plate No 3 of SSR Part-I 2020 and as specified or indicated and testing on completion incl earth work and excavation in any type of soil PCC (1:3:6) type C1 chamber, pre cost slab 40mm thick in cement concrete (1:2:4) type B1 with 8 mm dia MS bars reinforced at 10 cm centre to centre both ways incl funnel with watering pipe wire mesh and lugs, incl test point complete all as specified and as directed.
70M&L for Air termination single pointed aluminium rod 12mm dia and 300mm long
71M& L for test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hex, head screw.
72M&L for Aluminium Strip 25x3.15mm with saddles and fixing screws etc, for roof conductors and down conductors above ground.
73Supply and filling Calcium hypochlorite granular (65-80% chorine contect)disinfectant in Sumps complete as specified and directed by Engineer-in-charge
74M & L for sand cushioning with a layer of dry sand 23 cm thick under and above the cable complete all as specified and as directed
75S & L sub class burnt bricks for cable protection complete as specified as directed
76Taking down old unsv/burnt XLPE cable from trench/wall/pole of following size :-2 C x 10 Sqmm
77All as per item No. 76 above but for4 C x 10 Sqmm
78All as per item No. 76 above but for4 C x 16 Sqmm
79All as per item No. 76 above but for3.5 C x 25 Sqmm
80All as per item No. 76 above but for3.5 C x 35 Sqmm
81All as per item No. 76 above but for3.5 C x 50 Sqmm
82All as per item No. 76 above but for3.5 C x 70 Sqmm
83All as per item No. 76 above but for3.5 C x 95 Sqmm
84All as per item No. 76 above but for3.5 C x 120 Sqmm
85Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor connected with suitable legs including neccessary roadcrossing if applicable for following size :-2 C x 10 Sqmm
86All as per item No. 85 above but for4 C x 10 Sqmm
87All as per item No. 85 above but for4 C x 16 Sqmm
88All as per item No. 85 above but for3.5 C x 25 Sqmm
89All as per item No. 85 above but for3.5 C x 35 Sqmm
90All as per item No. 85 above but for3.5 C x 50 Sqmm
91All as per item No. 85 above but for3.5 C x 70 Sqmm
92All as per item No. 85 above but for3.5 C x 95 Sqmm
93All as per item No. 85 above but for3.5 C x 120 Sqmm
94M&L for replacement of iron work of any type incl cross arms, supports, bracing MS clamps etc made out of MS channel/angle iron/flat iron/ round section of any size and bolt nuts and washer incl painting with two costs of aluminium paint over a coat of red oxide all as specified and as directed
95M&L in replacement of pin type porcelain, vitreous white or brown insulator incl one galvanized mild steel spindle two galvanized iron washer and galvanized iron nut 100 mm height and 65mm dia for 1100 volts grade complete all as specified and as directed
96M & L in replacement of shackle type porcelain, vitreous white or brown insulator incl one galvanized mild steel spindle two galvanized iron washer and galvanized iron nut 75 mm height and 90mm dia for 1100 volts grade complete all as specified and as directed
97M & L in repair for GI tubing light grade 40mm with all accessories for cable protection fixed on poles/bldgs/road and laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed. Note road cutting rate are included on the above items.
98M & L in repair for GI tubing light grade 50mm with all accessories for cable protection fixed on poles/bldgs/road and laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed. Note road cutting rate are included on the above items.
99M & L in repair for GI tubing light grade 80mm with all accessories for cable protection fixed on poles/bldgs/road and laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed. Note road cutting rate are included on the above items.
100M & L in repair for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr connected to galvanized earth lead wire 4 mm dia as earth lead up to 7.5 mtr long by means of nuts, bolts, thimbles,check nuts and washers etc made of galvanized iron connected to earthing test point all as shown in electrical plate No 3 of SSR Part-I 2010 and as specified or indicated and testing on completion incl earth work and excavation in any type of soil PCC (1:3:6) type C1 chamber, pre cost slab 40mm thick in cement concrete (1:2:4) type B1 with 8 mm dia MS bars reinforced at 10 cm centre to centre both ways incl funnel with watering pipe wire mesh and lugs, incl test point complete all as specified and as directed.incl dismantling and taking out old U/S.
101M & L for tightening of ACSR (Aluminium conductor steel reinforced) conductor of any size between two poles 04/06 runs of conductor incl binding wire of appropriate size complete incl clearing of path and branch cutting etc all as specified and as directed
102S & F in replacemet of UNSV existing /suitable size MCCBs 4 pole 415 Volts 50HZ incl complete connections with incoming cable and out going cable with suitable thimbles and crimping the thimbles with crimping tools insulating the naked portion with insulation tape as underMCCB 100 Amps ,16 KA with adjustable Thermal setting
103All as per item No. 102 above but forMCCB 200 Amps 36 KA with adjustable Thermal setting .
104All as per item No. 102 above but forMCCB 250 Amps 36 KA with adjustable Thermal setting .
105All as per item No. 102 above but forMCCB 315 Amps 36 KA with adjustable Thermal setting .
106All as per item No. 102 above but forMCCB 63 Amps , 25 KA with adjustable Thermal setting
107M & L for replacement of LT 2 line separator 230 volts 50 Hz all as specified as directed
108M & L for replacement of LT 4 line separator 415 volts 50 Hz all as specified as directed
109M&L in repair for cable jointing kit for 1.1KV grade cable for straight through joint complete with jointing material and accessories suitable for 3.5 core/4core XLPE armoured aluminium conductor cable for following sizes:-3.5 C x 25 to 35 Sqmm
110All as per item No. 109 above but for3.5 C x 50 to 120 Sqmm
111M&L for painting of steel tubular/PCC poles of any height and type ,incl security light mounting brackets with one coat of aluminium paint/two coat of cement base paint incluing painting black and yellow strip or as ordered by engineer-in-charge on poles up to 1.5 mtr high above coping level and numbering of pole complete all specified and as directed.
112Dismantling of ACSR (Aluminium conductor steel reinforced) conductors
113M&L of ACSR (Aluminium conductor steel reinforced) conductor of any size on poles incl binding wire of appropriate size complete incl clearing of path and branch cutting etc all as specified and as directed
114Refixing of ACSR conductor connected with new existing wire tightening to insulator incl line clearance by pruning of tree branch approx 1 m apart from conductor tightening side.
115Stay assembley complete with all accessories as shown in elect plate No 1 of SSR Part-I consisting of stay rod 20mm dia 1.8 mtr long,size of stay plate 230 x 230 x 6 mm with nuts,bolts,insulator stay clamps etc. complete all as shown on drawing and as directed.Note:- Excavation and stay wire shall be measured and paid separately
116M&L for galvanized stay wire stranded 7/4 mm complete all as specified and as directed
117Dismantling the damaged unservicable pole of any type.
118Supply and errect steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410SP-31, 9 mtr long .
119M&L for PCC 1:3:6 type C1 with 20mm graded stone aggregate for couping of pole,filling and mass concrete of pole, make good to road surface , hard standing etc incl necessary form work all as specified and as directed
120M&L for PCC 1:4:8 type D2 with 40mm graded stone aggregate in foundation of poles all as specified and as directed
121M&L for in repair outdoor type, double door sheet metal enclosure/Junction box of size 80x80x30 cm with aluminium bus bar 400 Amps for 3 phase & neutral including MCCB 4 pole 415 volts 250 Amps 36 KA .including removing old unserviceable junction box complete all as specified and as directed
122Supply and fix in replacement of Timeline distribution board 32 A 3 pole /230V analog time switch including complete accessories relay contactor, timer etc, all as specified and as directed. Make:- Indoasian Cat No. TL032AB0
123M&L for cable fault finding for LT cables any sizes complete all as specified and as directed
124S&F in repair on pole/ wall etc GI pipe bracket made of 40mm bore light grade GI pipe1.5 mtr long suitably bent to shape and fixed on wall/ pole for fixing street light fitting with 2 Nos suitable MS clamps of size 25 x 3 mm size incluiding bolts, nuts, washers all as specified and as directed.
125Supply and fixing,replacement of moulded (FRP) junction box with IP 65 protection of size 300x200x80mm with 32 Amp 4 way heavy duty terminal block with 6 Amp MCB SP and two number of cable entry gland of standard size with suitable MS bracket to fix with pole complete all as directed
126Supply and fixing 60 W LED street light fitting with pressure die cast housing along with prismatic polycarbonate modular secondary lens optics with IP 66 ingress protection and impact resistance of IK 08. 4kV inbuilt and 10 kV external surge protection with top opening driver cover for easy maintenance .including taking down old unserviceable street light fittings from pole.
127Supply and fixing 90 W LED street light fitting with pressure die cast housing and toughened glass and individual LEDs with secondary lens optics with IP 66 ingress protection and impact resistance of IK 07. 5kV inbuilt and 10 kV external surge protection with top opening driver cover for easy maintenance .including taking down old unserviceable street light fittings from pole.
128S&F in replacement of 2 runs of PVC insulated 2.5 sqmm single core multistranded copper conductor cable and one run of 2.5 sqmm copper wire as earth continuity conductor drawn through and incl rigid non metalic conduit 20 mm external dia fixed on poles & connecting up all as specified and as directed. Note: Two runs of cable and one run of earth wire and one run of conduit shall be measured as one length.
129Supply & fix in replacement of on load Change over switch 4 pole in sheet metal enclosure compact design rating 63 Amps suitable for isolation and prevent leakage current/ flush over between phases, handle lock feature in off position with three padlocks
130Supply & fix in replacement of on load Change over switch 4 pole in sheet metal enclosure compact design rating 100 Amps suitable for isolation and prevent leakage current/ flush over between phases, handle lock feature in off position with three padlocks INDOASIAN or Havells/L&T/Standard.
131Supply & fix in replacement of on load Change over switch 4 pole in sheet metal enclosure compact design rating 400 Amps suitable for isolation and prevent leakage current/ flush over between phases, handle lock feature in off position with three padlocks
132Dismanling and taking out the LED street light fittings any make from Pole and removing the burned out /unserviceable LED driver 25 W to 60W and replacement of new drive to make the fitting serviceable and refixing the existing/new location all as directed at site.
133Dismanling and taking out the LED street light fittings any make from Pole and removing the burned out /unserviceable LED driver 90 W and replacement of new drive to make the fitting serviceable and refixing the existing/new location all as directed at site.
134Dismanling and taking out the flood light from high mast pole and removing the burned out/unserviceable LED driver 200 W and replacement of new drive to make the fitting serviceable and refixing the existing/new location all as directed at site.
135S&F in repair 200W LED flood light luminaries with innovative die-cast aluminium flood light with highly efficient LEDs as light source, suitable for highmast lighting with complete accessories including taking down old unserviceable flood lights from high mast pole all as specified and as directed.
136S&F in replacement of new generation 25 Watt post top energy saving IP-65 enviornmental, friendly long life with symmetrically light distribution, spun aluminium with high power
137S&F in replacement of Stellar LED post-top offering combination of sturdy design, execllent illumination and aesthetics in one go. IP 66 and IK 10 rating ensures it stands tall amid varid environemtnal conditionsl , friendly long life with symmetrically light distribution , spun aluminium with high power LED. Make :-Mk -Havells NEBULAPT40WLED857PSYMTOPC or equvalent-Phillips/ Crompton
138S&F in replacement of TERRAIN post top lentern is a wether proof indirect lighting solution wich improves horizental uniformity , with reduced glare and improved lighting control saving IP-65 enviornmental, friendly long life with symmetrically light distribution , spun aluminium with high power LED. Make :-Mk -Crompton LPTC-40-CDL or equvalent-Phillips/ Havells
139M&L for painting of outdoor type Feeder piller panel upto the size of 1100 x 450 x 1200 mm (approx), incl replacement of door hinges with new one and apply one coat of smoke grey colour paint and base angle with black paint complete or as directed by Engineer-in-charge complete all specified and as directed.
140M&L for painting of outdoor type Lt panel upto the size of 2500 x 600 x 3000 mm (approx), incl replacement of door hinges with new one and apply one coat of smoke grey colour paint and base angle with black paint complete or as directed by Engineer-in-charge complete all specified and as directed.
141Boring of holes under road, pavement, hard standing by trenchless techless using ultra sounding technique and necessary machine including HDPE pipe of 63 mm dia bore suitable for 0.4 mpa working pressure.
142M&L in for repair of LT panel upto the size of 2500 x 3000 mm (approx), incl replacement of door hinges with new one and duly with powder coated, painted one coat of red oxide primer and two coats of synthetic enamel paint of smoke grey colour as directed by Engineer-in-charge complete all specified and as directed.
143Supply, testing and commissioning in replacement of weather and vermin proof LT feeder pillar box factory fabricated outdoor cubical/kiosk type CPRI approved and confirming to IS 5036 totally enclosed made out of 3 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel centre opening front and rear opening doors (covers) with handles, each control switch to be fixed in each compartment with hinged door, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly with powder coated, painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and bus bar for phase & neutral 500 Amps,36 KA capacity and IP 54 protection mounted on epoxy insulator-01 Set including mounting the panel board on ground with PCC 1 :3:6 bedding upto a height of 50 cm above ground level and the size of feeder should not less than 150x130x 45 cm. complete all as directed and comprising the following including taking out unseviceable LT Panel incl dismantling and taking out old U/S:- (i) Incoming MCCB 4 pole, 400 Amps 36 KA 415 Volts -01 No (ii) Outgoing MCCB 4 pole, 250 Amps 25 KA 415 Volts -01 No (iii) Outgoing MCCB 4 pole, 200 Amps 25 KA 415 Volts -02 Nos(iii) Outgoing MCCB 4 pole, 100 Amps 16 KA 415 Volts -02 Nos (iv) Digital Voltmeter 0-500 volts with selector switch - 01 No (v) Digital Amps meter CT operated 0-400 Amps with phase selector switch - 01 Nos (vi) LED Indicator lamp ( RYB ) - 01 Set (03 Nos)
144S & F in replacement of 03 core sheathed of 1.5 sqmm PVC insulated cable with mulitstanded copper PVC insulated cable with multistanded copper conductor 1100 volts grade cofirming to IS 694 including drawn throgh the steel tubular pole and connection to light fitting and MCBs all as specified and as directed.
145S&F in replacement of 45 Watt post top LED light fitting, die cast aluminum graphite grey powder coated spigot, Acrylic clear diffuser, spun aluminum power coated canopy, LED connected in series and paralled combination either better heat dissipation arrangement, LED colour 3000 K + 300K, open and short circuit protection, voltage surge protection 5KV, suitable for 60mm OD pipe entry with fixing bolts, IP-65.
146Supply & fix in replacement 9 Watt LED Bollard Light complete with PCC Foundation, RCC Foundation/Pedestal, excavation, reinforcement, formwork, anchor bolts, grouting, backfilling, all fixing accessories, wiring connections and making good the disturbed surface, complete in all respects as specified and as directed by Engineer-in-Charge.
147Supply & fix in repai / replacement of Driver suitable for LED bollard 9 watt Make :- Bajaj Havells / Phillips / Crompton.
148Maintenance / servicing, cleaning, descaling of solar water heating system complete of capacity 100/200 Ltr per day with 02 Nos of collector of any size 01 No of stainless steel tank and 01 No of plastic make up tank 500 Ltr by replacement of washers, gasket, adaptor and worn out nut bolt, GI fitting for water pipe line 20/25 mm dia for inlet and outlet of stainless steel tank / collector /water make up tank and making fully leak proof by brazing / welding of the inner container for arresting leakages complete and testing for satisfactory performance all as specified and directed.
149All as per Sl Item No 148 above but of capacity 201/300 Ltr per day.
150S&F in repair / replacement of broken glass of solar flat plate collector of size 206 cm x 105 cm x 4 mm thick (L x B x W) (or as per existing size) by new one including rubber packing complete all as specified and as directed.
151S&F in repair of ETC Tube 47mm dia/ 54mm dia, glass tube with copper coating fixed in repairs complete all as specified and directed.
152S&F in repair / replacement black hose pipe suitable for 20/25mm dia hot/cold water pipe for solar hot water system all as specified by Engr -in Charge
153S&F in repair Electric heating element 3KW, ISI Marked threaded/cup type to SS tank of solar water heating system 100/150/200 ltrs capacity with necessary fixtures including taking out unserviceable one complete all as specified and directed by Engr-in-Charge.
154S&F in repair Thermostat of any size and type as per existing type, ISI Marked for solar water heating system 100/150/200 ltrs capacity including taking out unserviceable one all as specified and directed by Engr-in-Charge.
155Supply installation, testing and commissioning of LED Solar Street light All IN ONE TYPE with inbuilt battery, SPV Module of capacity 12 Watt of light source and 12 watt SPV panel, IP 65 protection, Lumionous efficacy 120 Lm /watt, Colour temperature 6000 K, battery 12.8 V, 12 AH including charging system with overload protection, light sensor devices , etc all as specified and directed. Make: Bajaj & Model no:- Model No: 152404 SOLAR BSZSL 12 W LED
156Taking down old unserviceable LED Solar Street light any Type and replacment of unserviceble parts like inbuilt battery, SPV Module of capacity 12/20 Watt of light source and upto 20 watt SPV panel, IP 65 protection, Lumionous efficacy 120 Lm /watt, Colour temperature 6000 K, battery 12.8 V, 42 AH including charging system with overload protection, light sensor devices, wiring, nut / bolts / washer ets after testing and commissioning the same location , Note : 1. As per maintenance schedule prescribed in repair and maintenance manual (authorised servicing centre who is conversant with the Solar Street light and report should be submitted by the contractor)2. Rate quoted by the contractor includes the fixing charges for replacement of parts specified in relevant item here in after. 3. The tenderer shall produce qualification and experiance cerificate of the mechanic to the Engineer in charge and approved personal only will be allowed to carried out the work 4. All speir part shall be measured and paid seperatly
157All as per item No. 156 above but forbattery 12.8 V, 42 AH including charging system with overload protection,
158All as per item No. 156 above but forSPV Module of capacity upto 42 Watt of light source
159All as per item No. 156 above but for12 watt SPV panel
160All as per item No. 156 above but forlight sensor devices
161All as per item No. 156 above but forWiring / nut / bolt / washer / clamp etc . Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57649865
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 42.50 Lakhs
LAST DATE 21-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair / Replacement Of External Water Supply System & Connected Allied Works In The Aor Army Unit & Connected Md Accn, Certain Maintenance Of Lt Panels Including Repair Of Oh Lines & Ug Cable & Allied Services At Prtc & 106 Inf Bn Area And Repair / Maintenance Of Solar Street Lights, Led Street Lights, Post Top Lanterns, Pathway Lights, Solar Water Heater In The Aor Of Army Units Under Ge (North) Bangalore
Basic Detail
Tender No 8381
Bidding Type Tender
Location
City Bengaluru Urban
State Karnataka
Key Dates
Publish Date 14 Oct 2026
Submission Date 21 Oct 2026
Open Date 24 Oct 2026
Finance
Tender Value 42.50 Lakhs
Tender Fee 500
EMD 85000
Exemption Available
Document List
3b78ea3d-a633-482f-9e8e-e5739cda629f.html
8381Tender.pdf
BOQ_886384.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 14, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 14, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Oct 21, 2026
18:00 IST

Corrigendum-2 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 3 days
Oct 21, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 3 days
Oct 24, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 6 days

Tender Documents

Download All (ZIP) ↓
html

3b78ea3d-a633-482f-9e8e-e5739cda629f.html

pdf

8381Tender.pdf

xls

BOQ_886384.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender