Tender For Installation Of Automatic Sprinkler System As Part Of Fire Fighting Arrangement At 100 Bedded Combined Hospital, District Hardoi (U.P.) (67/Uppcl/Gm-7/E-Tender/2026-27 Dated: 22.09.2026)

Issued by Government Departments · Hardoi, Uttar Pradesh
Tender Value
81.31 Lakhs
Estimated cost
Bid Submission
07 Oct 2026
14 days left
EMD
1.63 Lakhs
Bank guarantee accepted
Document Fee
11800
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Hardoi → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Installation Of Automatic Sprinkler System As Part Of Fire Fighting Arrangement At 100 Bedded Combined Hospital, District Hardoi (U.P.) (67/Uppcl/Gm-7/E-Tender/2026-27 Dated: 22.09.2026)

BOQ

Name of Work:- Installation of Automatic Sprinkler System as part of Fire Fighting Arrangement at 100 Bedded Combined Hospital, District Hardoi (U.P.) (67/UPPCL/GM-7/E-TENDER/2026-27 Dated: 22.09.2026)
Sl. No. Item Description
1Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
225 mm dia
332 mm dia
450mm dia
565mm dia
680 mm dia
7100 mm dia
8150 mm dia
9Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
10(A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.(D) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads.. 900 Lpm at 35 m Head
11Providing/Fixing of cubical type floor mounted Fire pump control panel fabricated from 16 G M.S. sheet duly powder coated finish of approved shade and comprising of : a) One 100 amp. TP+NL M.C.C.B with rotary handle of beacking capacity 35 KA. b)One Volt meter (0-500 V) with selector switch. c) One set including lamps.
12Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
13Providing & fixing of Flow switch in Following sizes in M.S. pipe line including connection etc. as required. 100 mm Dia.
14Providing and fixing in position the industrial type pressure gauges with gun metal/brass valves complete as required
15Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
16Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
1780 mm dia
18100 mm dia
19Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 25 mm nominal bore
20Supply, Installation, testing & commissioning of 50mm ball valve for sprinler drain line.
21Providing, fixing Testing &commissioning of 15mm dia quartzoid bulb type sprinkler of rating 68 degree centigrade with required accessories
22Pendent Type
23Upright Type
24Providing, installation, testing and commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed of FM approved complete as required.
25Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.
26700 mm
27Providing/Fixing Fire man axe. Make.
28FIRE EXTINGUISHERS
29Supply and fixingof C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.
30Supply and fixingof fire extinguisher,ABC Type 6.00 kg. capacity(ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.
31Fire Alarm SystemWork
32Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card,minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.
33Two Loop Panel.
34Supplying, installation, testing and commissioning of intelligent analog addressable photo thermal detector complete with mounting base complete as required.
35Supplying, installation, testing and commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
36Supplying, installation, testing & commissioning of addressable phone control module complete as required.
37Supplying, installation, testing & commissioning of addressable manual call point complete as required.
38Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
39Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
40Armoured Cables (Cable/Gland/Lug) :
41Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.
4210 Sqmm 4 Core
431.5 Sqmm 2 Core
44Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge.
4510 Sqmm 4 Core
4616 Sqmm 4 Core
4735 Sqmm 3.5 Core
48Supply and fixing of self glow type exit sinage. (LED Type)
49Maintanace & Overhuling of Fire Pump Main,Deisel,Jokey,hose ,landing valve complete with all respects
50All above Rate are including 1% Lebour Cess and will be deduct from Contractor BillGST will be pay extra as per prevailing Rates Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57646349
AUTHORITY Government Departments
TENDER VALUE 81.31 Lakhs
LAST DATE 07-10-2026
Authority
Authority Name Uttar Pradesh Projects Corporation Limited
Work Description Tender for Installation Of Automatic Sprinkler System As Part Of Fire Fighting Arrangement At 100 Bedded Combined Hospital, District Hardoi (U.P.) (67/Uppcl/Gm-7/E-Tender/2026-27 Dated: 22.09.2026)
Basic Detail
Tender No 67/UPPCL/GM-7/E-TENDER/2026-27 Dated-22.09.2026
Bidding Type Tender
Location
City Hardoi
State Uttar Pradesh
Key Dates
Publish Date 23 Sep 2026
Submission Date 07 Oct 2026
Open Date 07 Oct 2026
Finance
Tender Value 81.31 Lakhs
Tender Fee 11800
EMD 1.63 Lakhs
Exemption Not Available
Document List
5066c39b-27a2-466b-b002-2eb0df773f72.html
BID67.pdf
BOQ_2239985.xls
Tendernotice_1 (76).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 23, 2026
11:30 IST

Tender Published

Tender notice published.

Today
Oct 07, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 14 days
Oct 07, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 14 days

Tender Documents

Download All (ZIP) ↓
html

5066c39b-27a2-466b-b002-2eb0df773f72.html

pdf

BID67.pdf

xls

BOQ_2239985.xls

pdf

Tendernotice_1 (76).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender