Tender For Strengthening Of Fire Safety Arrangements And Installation Of Automatic Fire Alarm, Sprinkler, Smoke Extraction, And Smoke Management Systems At Bhaurao Deoras Joint Hospital, Mahanagar, Lucknow, Under The Department Of Medical Health And
Tender Overview
Project Description
Tender for Strengthening Of Fire Safety Arrangements And Installation Of Automatic Fire Alarm, Sprinkler, Smoke Extraction, And Smoke Management Systems At Bhaurao Deoras Joint Hospital, Mahanagar, Lucknow, Under The Department Of Medical Health And Family Welfare
BOQ
| Sl. No. | Item Description |
| 1 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : DSR 2025 SI No 27.7 |
| 2 | 25 mm dia (27.7.1) |
| 3 | 32 mm dia (27.7.2) |
| 4 | 40 mm dia (27.7.3) |
| 5 | 50mm dia (27.7.4) |
| 6 | 65 mm dia (27.7.5) |
| 7 | 80 mm dia (27.7.6) |
| 8 | 100 mm dia (27.7.7) |
| 9 | Supplying Installation testing & Commissioning of 25 mm Ball valve PN -1 gunmental as per IS:778 including necessary accessories and connections. (MR) |
| 10 | Supplying Installation testing & Commissioning of 50mm Ball valve PN -1 gunmental as per IS:778 including necessary accessories and connections. (MR) |
| 11 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required.. DSR 2025 SI No. 27.20 |
| 12 | (A) Supplying, installation, testing and commissioning of electric driven terrace pumpconforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required.(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class- 'F' insulation, conforming to IS-12615: 2018.(D) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads.. DSR 2025 SI No. 27.4.450 lpm 35 m Head ( DSR 2025 SI No. 27.4.2) |
| 13 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Civil DSR 2023 (18.48) |
| 14 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Civil DSR 2023 SI No 18.7 |
| 15 | 25 mm nominal dia Pipes ( 18.7.3) |
| 16 | 32 mm nominal dia Pipes (18.7.4) |
| 17 | 50 mm nominal dia Pipes (18.7.6) |
| 18 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand(zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) as per Civil DSR SI No 4.1.3) |
| 19 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 0C with required accessories : DSR 2025 SI No. 27.21 |
| 20 | Pendent Type (27.21.1) |
| 21 | Horizontal side wall Sprinkler (27.21.3) |
| 22 | Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. DSR 2025 SI No. 27.29 |
| 23 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mmNPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizescomplete as required. DSR 2025 Sl. No. 27.25 |
| 24 | 700 mm (27.25.1) |
| 25 | 1000 mm (27.25.2) |
| 26 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. DSR 2025 SI No 28.2.7 |
| 27 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. DSR-2025 SI.No.28.3.3 |
| 28 | Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required.. DSR-2025 SI.No.28.3.6 |
| 29 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. DSR-2025 SI.No.28.3.9 |
| 30 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loopmodules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communicationcard, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), powersupply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS systemwith open protocol BACnet/ Modbus over IP complete as per specifications. DSR 2025 SI No 28.2.1.2Two loop Panel |
| 31 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & RLS/HFFR outer sheath complete as required. DSR 2025 SI NO. 28.5.2 |
| 32 | Supply and Laying of Aluntiniuan Conductor PVC insulated armoured served sheathed cables 1100V grade at a depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with bumi bricks on sides and on top as directed by Engineer in Charge complete in all respect including, excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. PWD SOR 2024 SI No 20a.1 |
| 33 | 6 Sqmm 4 Core |
| 34 | 10 Sqmm 4 Core |
| 35 | 16 Sqmm 4 Core |
| 36 | 95 Sqmm 3.5 Core |
| 37 | 240 Sqmm 3.5 Core |
| 38 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. PWD SOR 2018 SI No 503 |
| 39 | 6 Sqmm 4 Core |
| 40 | Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making connection etc. complete in all respects as per direction of the Engineer incharge. PWD SOR 2018 SI No 504 |
| 41 | 6 sq mm |
| 42 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. DSR 2025 Sl. No.11.1 |
| 43 | 4 X 10 sq. mm (25mm) |
| 44 | 4 X 16 sq. mm (28mm) |
| 45 | 3½ X 95 sq. mm (45mm) |
| 46 | 3½ X 240 sq. mm (62mm) |
| 47 | Supply and burying of Safe Earthing Electrod T-19 Zn-Zinc Coated,Length 3000mm,outer pipe 48.4mmx3.2mm,inner pipe 26.9mm x 2.6 mm,terminal Dia 12mm,coating 80-100 micron filled with crystalline conductive mixture (CCm) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonary housing.(From electrode terminal to switch board,cost of 25x3 G.I. Strip will be extra) SOR 2018 Sl No 726 B |
| 48 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & springwasher spaced at 50mm) DSR 2025 Sl. No.5.9 |
| 49 | Supply and fixing of one number 8 SWG G.I. wire in 15mm dia. G.I. pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand, labour, T&P other material required for proper completion of the work as directed at site. PWD SOR 2018 SI No.721 |
| 50 | Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. SOR 2018 Sl No 1133 |
| 51 | Providing of MS fire sand bucket stand (MR) |
| 52 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. DSR 2025 Sl No. 4.6 |
| 53 | 100 mm width X 50 mm depth X 1.6 mm thickness (4.6.1) |
| 54 | 150 mm width X 50 mm depth X 1.6 mm thickness (4.6.2) |
| 55 | Wiring point for light with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit pipe on surface, complete with 1.5sq. mm FRLSH earth PVC insulated multistrand single core copper conductor cable as earth continuity wire drawn inside the conduit , GP Box, Modular type switch and ceiling rose/angle/ batten holder on 3 mm. thick phenolic laminated backelite-sheet etc. complete in all respect,as per SOR 2018 121(C)+187A |
| 56 | Fire Exit Lights (MR) |
| 57 | Dismantling of aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge. (Civil DSR 2023 15.57) |
| 58 | Dismantling and reinstalling of existing smoke detectors and respose indicator (MR) |
| 59 | Refixing of existing false ceiling as per Civil DAR 2023 Si no. 12.52.3 |
| 60 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. DSR 2025 SI No 28.2.4 |
| 61 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. DSR 2022 SI No 28.2.5 |
| 62 | Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main \\"T\\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross \\"T\\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \\"T\\" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross \\"T\\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \\"T\\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. |
| 63 | 12.5 mm thick square edge PVC Laminated Gypsum Tile of size 595x595 mm, made of Gypsum plasterboard, manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16mm thick fire retardant PVC film on the face side and 12micron metalized polyester on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyester film so as to make the tile a completely sealed unit. as per CIVIL DSR 2023 (12.52.3) |
| 64 | Providing/Fixing of cubical type floor mounted Fire pump control panel fabricated from 16 G M.S. sheet duly powder coated finish of approved shade and comprising of:a)One 63 amp. TP+NL M.C.C.B with rotary handle of beacking capacity 35 KA.b)One Volt meter (0-500 V) with selector switch.c) One set including lamps. (MR) |
| 65 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. DSR 2025 SI No.27.22 |
| 66 | Providing and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as required. DSR-2025 SI No. 30.8 |
| 67 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. DSR 2025 SI no. 27.13 |
| 68 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 100 mm dia DSR 2025 Sl No 27.15.2 |
| 69 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : DSR 2025 SI No 27.11 |
| 70 | 50 mm dia (27.11.2) |
| 71 | 65 mm dia (27.11.3) |
| 72 | 80 mm dia (27.11.4) |
| 73 | 100 mm dia (27.11.5) |
| 74 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : DSR 2025 SI No. 27.14 |
| 75 | 80 mm dia (27.14.4) |
| 76 | 100 mm dia (27.14.5) |
| 77 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. DSR 2025 SI No 28.2.4 |
| 78 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required. DSR 2025 SI No 28.2.9 |
| 79 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. Civil DSR SI No 10.2 |
| 80 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all onnections etc as required. DSR 2025 SI No 28.2.5 |
| 81 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. DSR 2025 SI No 28.2.14 |
| 82 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. DSR 2025 SI No 28.2.15 |
| 83 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.(a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585(b) 20 mm nominal internal dia gun metal globe valve & nozzle.(c) Drum and brackets for fixing the equipmets on wall.(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 M DSR 2025 No 27.17.1 |
| 84 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required as per DSR 2025 S.I. No. 27. 9.1 Single Handed Gunmetal |
| 85 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: Gun metal DSR 2025 SI No. 27.18.1 |
| 86 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : DSR 2025 SI.No.27.16.1 Gun metal |
| 87 | Providing/fixing of Weather proof standard fire hose cabinet (900 mm X 600 mm X 450 mm) Outdoor type made of not les thad 16/18 SWGMS sheet having glassed hinged door (5 mm thick glass ) including necessary locking arrangement with handle for housing hydrant valve, two nos. 15 meter long fire hose pipes , branch pipe as required as per drawings. including brackets for mounting accessories , painting ( one coat primer and two coat of fire red color). The cabined shall be mounted on self standing mounting type painted MS Angle iron frame as required . the words \\"FIRE HOSE\\" to be painted on the box (MR) |
| 88 | Providing/Fixing Fire man axe. (MR) |
| 89 | Supply, Installation testing & commissioning of high temperature rated direct smoke Axial flow fan suitable for demand controlled ventilation for 12ACPH operation for the site .Each fan shall be completed with casing made from mild steel dult enamel painted,adjustable pitch die cast aluminium impeller (HUB & BLADES), mounting clits,anchor faster with vibration isolation pad and rated motor with class -H insulation suitable for high temperature operation once for 250° for 2Hours.Motor shall be suitable for 415±10% volts,50 cycles,3 phase AC supply.(MR)Noise Level @ 3m from Fan shall beless than 70 dBA. |
| 90 | 22000 CFM,1400 RPM |
| 91 | 6000 CFM,1400 RPM |
| 92 | Electrical Control PanelSupply, Installation and Commissioning of Distribution Cum Starter Cubical Panel, duly powder coated and suitable Aluminium Bus Bar consisting of the followingIncomer-400Amp 4 Pole MCCB-2 Nos.Outgoing 32Amp MCCB for 5HP Fan motor starters -9 Nos. (3 Nos as spare with complete items)63Amp MCCB for Terrace pump motor -3 Nos (1 No as spare with complete items)80Amp MCCB for 20 HP Fan motor starter-5 Nos (2 Nos as spare with complete items)Changeover Switch-400A 4 Pole - 1 No.Complete digital metering-1 NoEach starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light :(MR) |
| 93 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Thickness 0.80 mm sheet DSR 2025 SI no. 30.12.2.2 |
| 94 | Providing and fixing double scaffolding system (cup lock type) on the exterior side, up to seven story height made with 40 mm dia M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after. The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspectionof work at required locations with essential safety features for the workmen etc. complete as per directions and approval of Engineer-in-charge. The elevational area of the scaffolding shall be measured for payment purpose. The payment shall be made once irrespective of duration of scaffolding.Note:- This item to be used for maintenance work judicially, necessary deduction for scaffolding in the existing item to be done. as per Civil DSR SI No 14.72 |
| 95 | Supply, installation ,testing and commissioning of 18 gauge galvanizhed steel mesh bird screen shall be provided on all discharge cowls around the outlet area (MR) |
| 96 | Supply Installation, testing and Commissioning of Canvas connection with 1/2 hr. fire rating as per specification.(MR) |
| 97 | Supply and Fixing of MS Stand complete Fabricated with 'C' channel pf size 3''x1.5'' and angle iron legs (4Nos.) with welding and two more coats of approved enamel paint for holding the outdoor units on terrace with the help of cement & concrete sand (as per drawing enclosed) complete etc. as reqd.(MR) |
| 98 | Supply Installation, testing and Commissioning of CO Sensors,suitable for RS 485/ModBus Network Communication,complete with display ,controllers,wall/duct housing asper specifications & drawings Range:0-100 ppm ,24 volt AC/DC,50 Htz.Operating Temp.range:0-50°C (MR) |
| 99 | Providing bricks masonry holes of size 36 Inch X 36 Inch at the wall of Height 12 feet.as per site requirement and repairing the same properly finished with Cement ,Paint etc.complete to the satisfaction of the Engineer Inc charge as required (MR) |
| 100 | Cost of Minor Repair,repainting and necessary maintenance works (MR) |
| 101 | Covering of DG Set and Terrace Pumps with Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. 1.00 mm thick with zinc coating not less than 275 gm/m²Civil DSR 2023 SI No 12.1.1 |
| 102 | Supply and fixing of 2 metres high cage fabricated with 3mm thick expanded metal fixed on 50mm x 50mm x 6mm angle iron frame having vertical members spaced at 1 to 1.25 mts and horizontal members spaced at 1 mt. The vertical members shall be grouted in floor and horizontal members in the wall to a depth of 300mm with ends forked. The cage shall have 2000mm x 1000mm size one leaf door with locking device having door frame fabricated with 35mm x 35mm x 6mm angle iron and 3mm expanded metal duly fixed with the cage member with hinges etc. The cage shall be painted with red oxide primer and synthetic enamel paint. The job includes all materials, labour, T&P etc. for proper completion of work. as per SOR 2018 SI No 1142 |
| 103 | Supplying, installation, testing and commissioning of silent type DG sets, AMF panel, bus ducting/ cables from DG sets to essential panel, synchronizing panel where required, DG set enclosure room sound insulation/ventilation/smoke exhaust as required, earthing of DG set system, control cabling, fuel tank/piping, DG set exhaust piping/ exhaust chimney as per CPCB norms, civil works connected with DG sets including foundation as required. CPWD Plinth Area rate 2023 Sl. No.6.3.1 |
| 104 | Supply of 48 mm Thick Metal Fire Door of 120 Minutes fire Rating confirming to BS-476, Part-22. part-II; and IS 3614 (Part 2). Fabricated with 2 nos. 1.2 MM galvanized steel sheet sandwiching with propprietary fire resistant insulation. The door frame are manufactured from 1.6MM galvanized steel sheet pressed form to Single rebate profile of size 100mm X 60 mm. The door frame and door shutter are finished with powder coating. MR |
| 105 | Metal Fire Door. Size 1800X2000 mm. (1 No.) MR |
| 106 | Metal Fire Door. Size 1650X2100 mm. (1 No.) MR |
| 107 | Metal Fire Door. Size 2350X2100 mm. (1 No.) MR |
| 108 | Metal Fire Door. Size 1600X2500 mm. (1 No.) MR |
| 109 | Metal Fire Door. Size 2400X2500 mm. (1 No.) MR |
| 110 | Supply of 48 mm Thick Metal Fire Door of 120 Minutes fire Rating confirming to BS-476, Part-22. part-II; and IS 3614 (Part 2). Fabricated with 1 nos. 1.2 MM galvanized steel sheet sandwiching with propprietary fire resistant insulation. The door frame are manufactured from 1.6MM galvanized steel sheet pressed form to Single rebate profile of size 100mm X 60 mm. The door frame and door shutter are finished with powder coating. MR |
| 111 | Metal Fire Door. Size 1150X2100 mm. (1 No.) MR |
| 112 | Metal Fire Door. Size 1150X1850 mm. (1 No.) MR |
| 113 | Supply of SS BB Hinges of Size 100X75X3 mm. Make RK/GRAG/GEZE MR |
| 114 | Supply of Double Leaf Panic Bar.and single leaf panic bar Make- GARG/GEZE/Yale MR |
| 115 | Supply of Door Closer with Std Arm. Make Yale/GARG MR |
| 116 | Supply of 6 mm thick Vision Clear Glass. Size 200X300 MR |
| 117 | Supply of Panic trim. MR |
| 118 | Supply of Fastner. Size 10X125 mm long. MR |
| 119 | Installation Charges. |
| 120 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, upto 90 metre depth below ground level. (Civil DSR 2023 SI 23.1.)All Types of Soil350mm dia up to 60mtrs SI no 23.1.1.2 |
| 121 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, upto 90 metre depth below ground level. (Civil DSR 2023 SI 23.1.)All Types of Soil 300mm dia |
| 122 | 60-90 mtrs SI no.23.1.1.1 |
| 123 | 90-150 mtr SI No 23.2.1.1 |
| 124 | 150-220 mtr SI No 23.2.1.1 |
| 125 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 mild steel screwed and socketed/plain ended casing pipes of required dia, conforming to IS: 4270, of reputed & approved make, including painted with outside surface with two coats of anticorrosive paint of approved brand and manufacture, including required hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer-in-charge.(Civil DSR 2023 SI 23.10.2) |
| 126 | 150mm nominal size dia having minimum wall thickness 5.00 mm (SI No 23.10.2) |
| 127 | 200mm nominal size having minimum wall thickness 5.4 mm(SI No 23.10.3) |
| 128 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed/ plain bevel ended pipe (type A) of required dia, conforming to IS: 8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer -in-charge. 150 mm nominal size dia (Civil DSR 2023 23.11.2) |
| 129 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tube well as per IS: 2800 (part I), including necessary bolts & nuts of required size complete..200 mm clamp(Civil DSR 2023 SI 23.14.3) |
| 130 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tube well as per IS:2800 (part I). 150 mm dia(Civil DSR 2023 SI 23.15.2) |
| 131 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.. (Civil DSR 2023 SI 23.6) |
| 132 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \\"V\\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tube well, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge..(Civil DSR 2023 SI 23.12) |
| 133 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for bore well of 200 mm dia Civil DSR 2023 SI 23.13.3 |
| 134 | Supply of Submersible Pump set suitable for clear and cold water with chrome steel impellers and built in non-return valve and suitable to run on 400 volts,3 phase 50 hz AC supply at 2900 RPM (nominal) speed and complete with 3 mtrs .Submersible cable.The detailed specification as follows:Capacity in LPM: 500Total head in mtrs: 55Model : BPD 273/6+UMAI-150O.D of pump set in mm : 144 No of Stages :6Pump outlet size : 75 in mmH.P of motor :10Method od starting : S.D.Size of submersible cable in sq.mm.:2x3x2.5 sqmm (MR) |
| 135 | Supply of sheet steel fabricated cubical type wall mounting type panel with front opening door.The panel will be complet with internal wiring and will have 3 Nos.instrument fuses and 3 nos.toggle switches and will have the following intrument nounted within:T.P switch fuse unit with HRC fuses 63amps.-1 No100 mm dial size ammeter of suitable range-1 No100 mm dial size 0 to 500 volts voltmeter with selector swtich-1 NoSingle phasing preventor -1 NoL & T make FASD starter -1 No.Capacitor of suitable rating -1 NoSubmersible cable 1x3x4sqmm -110MtrL.S. Power wiring material incuding 2 mtrs long 3 core leadL.S Earthing material for earthing of starter and panelcaution board -2 No (MR) |
| 136 | Supply of MAIN PIPING AND VALVES :C.I.D/F Reflux valve IVC Make-01 No.C.I.D/F Sluice valve with hand wheel VC Make-02 Nos.01 D/F bend-01 No.Enlarger with nipple-1 NoC.I.A.F Tee-1 No.M.S.D/F. Pipe 1.5 mtr long -2 Nos.M.S.D/F. Pipe 2 mtr long -1 No. M.S.D/F Column pipes-39 Mtr.Column Pipe Clamps- 2 PairsL.S Necessary no rubber insertion packing,M.S. nuts and bolts for jints inside the pupm houseHousing cover of M.S.sheet- 1 NoCross ring for reducer- 1 NoNote: The size pipes,valves and fittings will be 100 mm and thickness as per Class C (MR) |
| 137 | Supply of pressure and depth gauges:1 set100 mm dial size pressure gauge fiebiq make-1 No100 mm dial size depth gauge fiebiq make -1 Nocontrol cock for pressure gauge-1 Nosteel iron line with sockets-45 MtsUnion joints,Schraeder valve and gauge board etc.-1 Set (MR) |
| 138 | Supply of Lifting Tackle: Indef make spur geared lifting tackle of capacity 2 tonnes and hand chain for 4 mts.lift (MR) |
| 139 | Supply of Special tools and Spanners:1 Set Wooden tool board-1 NoHammer with handle -1 NoO.E spanners consisting of 6 pcs-1 Setscrew drivers-2 No35mm size pipe wrenches-1NoInsulated plier-1 NoHand air pump-1 No (MR) |
| 140 | Installation,Painting & Testing (MR) |
| 141 | Supply of Electronic chlorinator of 6 LPH capacity complete with accessories and PVC solution tank |
| 142 | Supply of Orifice plate assembly (150mm Dia) |
| 143 | Supply of Solution Hypochlorite (70 Ltr.Drum) |
| 144 | Cartage |
| 145 | Installation charge |
| 146 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and for all lift, as directed by Engineer-in-charge. All Kind of Soil (DSR 2.6.1) |
| 147 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering-All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) (DSR 4.1.8) |
| 148 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size de rived from natural sources)(D.S.R 5.1.2) |
| 149 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 15 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) UP TO PLINTH(D.S.R 6.1.2) |
| 150 | Reinforced cement concrete work in vertical and horizontal fins individually or forming box louvers, facias and eaves boards above plinth level u p to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). (DSR 5.3) |
| 151 | Steel reinforcement for R.C.C. work including straightening, cutting bending, placing in position and binding all complete up to plinth level. Mild Steel and Medium Tensile steel bars (DSR 5.22.1) |
| 152 | Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete (DSR 5.9.6) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender