Tender For Repair Maintenance Of Miscellaneous Electrical And Mechanical Items Including Eot Crane At Bhisiana Under Ge (Af) Bhisiana
Tender Overview
Project Description
Tender For Repair Maintenance Of Miscellaneous Electrical And Mechanical Items Including Eot Crane At Bhisiana Under Ge (Af) Bhisiana
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 13-Oct-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 20-Oct-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply and fixing in replacement MCCB of rating 100 Amps, 4 Pole, 415 Volts AC, breaking capacity 16 kA, with adjustable thermal and magnetic protection, Ics = 100% of Icu, conforming to IEC 60947-2, mounted and connected in the existing distribution board/panel. Including necessary modifications/adjustments for proper fitment in the existing space, termination of incoming and outgoing connections, tightening of all terminals, testing for satisfactory operation and commissioning, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 2 | Supply and fixing in replacement MCCB of rating 125 Amps, 4 Pole, 415 Volts AC, breaking capacity 16 kA, with adjustable thermal and magnetic protection, Ics = 100% of Icu, conforming to IEC 60947-2, mounted and connected in the existing distribution board/panel. Including necessary modifications/adjustments for proper fitment in the existing space, termination of incoming and outgoing connections, tightening of all terminals, testing for satisfactory operation and commissioning, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 3 | Supply only self-adhesive PVC Electrical Insulation Tape, 25 mm wide, 0.125 mm thick and 25 m long per roll, polyvinyl chloride (PVC) pressure-sensitive adhesive tapes designed for electrical insulation, as per IS 7809 Part-3 Sec-1, in manufacturer's standard packing, undamaged and complete in all respects as specified and directed by the Engineer-in-Charge. |
| 4 | Excavation in trenches (Manual), not exceeding 1.5m wide and not exceeding 1.5m in depth for pipe line, cable in trenches etc., not exceeding 10 Sqm on plan and getting out in any type of soft including trimming the sides and forming bottom surfaces to required levels complete all as specified and as directed. |
| 5 | Returning, filling including spreading, leveling watering and well ramming in layers not exceeding 25cm thick in soft/loose soil complete all as specified and as directed. |
| 6 | Removing excavated material (surplus soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed. |
| 7 | Material and labour for boring of holes (trenchless horizontal Directional Drilling) under road pavement, hard standing or any other situation by using trenchless boring manual manpower by using manpower auger machine/spiral-bladed drill /Boki/mechanically or any other means suitable for accommodate/inserting pipe upto 100mm bore in the drilled holes, including excavation, returning filling in the both ends working space including removal of surplus soil and making good the surface complete all as specified and as directed.Note ; (i) Only length of the road/hard standing/Pavement will be measured for payment and cost for excavation, returning filling and making good at both side of bore shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account. (ii) Pipe shall be measured and paid separately) |
| 8 | Supply, laying, fixing and drawing in replacement XLPE LT Cable of size 10 Sqmm, 4 core, 1100 Volt grade heavy duty with XLPE insulated, stranded aluminium conductor served with an inner sheathening of PVC tape armoured with Galvanized steel strip or wire and over all PVC Sheathed stranded conductor conforming to IS- 7098 (Part-I) with latest amendments, in trenches, on floors, along poles, walls or any other open surface, including drawing the cable through protection pipes/conduits wherever required, dressing, aligning and securing the cable in position with necessary minor consumables such as binding wire, saddles etc, and making necessary end connections including supply and fixing of suitable size thimbles and testing, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 9 | Supply, laying, fixing and drawing in replacement XLPE LT Cable of size 16 Sqmm, 4 core, 1100 Volt grade heavy duty with XLPE insulated, stranded aluminium conductor served with an inner sheathening of PVC tape armoured with Galvanized steel strip or wire and over all PVC Sheathed stranded conductor conforming to IS- 7098 (Part-I) with latest amendments, in trenches, on floors, along poles, walls or any other open surface, including drawing the cable through protection pipes/conduits wherever required, dressing, aligning and securing the cable in position with necessary minor consumables such as binding wire, saddles etc, and making necessary end connections including supply and fixing of suitable size thimbles and testing, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 10 | Supply, laying, fixing and drawing in replacement XLPE LT Cable of size 50 Sqmm, 3.5 core, 1100 Volt grade heavy duty with XLPE insulated, stranded aluminium conductor served with an inner sheathening of PVC tape armoured with Galvanized steel strip or wire and over all PVC Sheathed stranded conductor conforming to IS- 7098 (Part-I) with latest amendments, in trenches, on floors, along poles, walls or any other open surface, or drawing the cable through protection pipes/conduits wherever required, dressing, aligning and securing the cable in position with necessary minor consumables such as binding wire, saddles etc, and making necessary end connections including supply and fixing of suitable size thimbles and testing, complete in all respects as specified and directed by the Engineer-in-Charge.Note ; (i) Excavation, returning filling, removal and protection pipe shall be measured and paid separately) |
| 11 | Material and labour for Sand cushioning, with dry and clean river fine sand (for under ground cable) 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and as directed. Note:- (i) Punned thickness shall be considered for payment purpose (ii) Approved sand free from vegetations, grass and other deleterious substances shall be used. |
| 12 | Supply and laying Best quality, locally available, sub class ‘B’ bricks (Old Size) for cable protection cover, laid flat and dry in trenches over the cable, perpendicular to the direction of cable with width equal to length of brick, and gap between adjacent brick not exceeding 10mm, complete all as specified and as directed. |
| 13 | Material and labour for providing and fixing GI tubing, galvanized, light grade, ISI marked, 50 mm nominal bore, laid in trenches, inserted through bored holes under roads, or fixed along poles, walls, ceilings or other surfaces, as required for protection of earth strips and/or cables, including all necessary pipe fittings such as elbows, tees, sockets, couplers and other accessories, cutting, threading, bending and jointing as required, and fixing in position with suitable MS clamps, saddles, spacer blocks, nuts, bolts, washers and other fixing accessories, including sealing/filling of open ends with oil putty to prevent ingress of water, complete all as specified and as directed by the Engineer-in-Charge. |
| 14 | Supply and fixing in replacement of digital voltmeter, 0–500 V AC, complete with compatible voltmeter selector switch, in the existing LT panel. fixing of the new voltmeter and selector switch with all necessary hardware and accessories, making all electrical connections with suitable lugs/ferrules, testing for correct voltage indication on all phases, and commissioning, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 15 | Supply and fixing in replacement of digital ammeter, 0–400 Amp, complete with compatible ammeter selector switch, in the existing LT panel, fixing of the new digital ammeter and selector switch with all necessary hardware and accessories, making all CT secondary and control wiring connections with suitable lugs/ferrules, ensuring correct CT polarity and ratio compatibility with the existing current transformers, testing for accurate current indication on all phases through the selector switch, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 16 | Material and labour for servicing of existing LT panel of any size, type and rating, comprising isolation of electrical supply after obtaining necessary shutdown, opening the panel, thorough inspection, cleaning of all internal and external surfaces by removing dust, dirt and other foreign matter using an air blower, dry cloth. The work shall include removal of burnt/damaged control and power wiring, cable joints, lugs/thimbles and replacement/re-jointing of all defective connections using suitable size copper cable (same or next higher size, wherever required), supply and replacement of damaged rubber beading/gasket for panel doors, replacement of defective RYB phase indicating lamps, replacement of nuts, bolts, washers, screws and other hardware, tightening of all power and control connections, checking of bus bar joints and earthing connections, dressing and proper routing of wiring, and carrying out continuity, insulation resistance and operational tests after reassembly, complete in all respects as specified and directed by the Engineer-in-Charge.Note : MCCB, Ammeter, Voltmeter, cable gland if required for replacement same shall be measured and paid separately under respective item of BOQ. |
| 17 | Supply, installing, commissioning and testing of factory made LT panel board (out door type with top canopy, 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, minimum IP-54 class protection, outer shell made out of 3.15 mm thick and inner shell (partition, supporting channel, compartment etc) made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, fully comparted type to accommodate the incoming and outgoing each switch gear, bus bar chamber shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and stainless steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size \\"F\\" class insulator at an interval not more than 250 mm throughout the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle iron of size 40 x40 x5mm, legs shall be 750 mm long, 300 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 450 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going, all as directed and comprising of following accessories :-(a) Four Pole, Aluminium bus bar 600 Amps - 01 Set(b) MCCB 400 Amps, Four pole, 50 KA, 415 V, adjustable thermal magnetic protection, Icu=Ics (100%) - 01 No (incoming)(c) MCCB 200 Amps, Four pole, 36 KA, 415 V, adjustable thermal magnetic protection, Icu=Ics (100%) - 01 No (outgoing)(d) MCCB 160 Amps, Four pole, 25 KA, 415 V, adjustable thermal magnetic protection, Icu=Ics (100%) - 02 No (outgoing)(e) MCCB 125 Amps, Four pole, 25 KA, 415 V, adjustable thermal magnetic protection, Icu=Ics (100%) - 02 No (outgoing)(f) ON load changeover switch 4 pole, 415 v, 400 Amps, open execution - 01 No (incoming/outgoing)(g) Multifunction meter Digital type showing Voltage, Amp , Frequency, KW , KWH inbuilt selector switch with CT coils for three phase- 01 No (h) Indicating lamps RYB - 01 Set of three(i) Internal power and control wiring with suitable size PVC insulated multistranded copper conductor cable FRLSH IS 694 sheathed 1100V gradeNote :- (i) Necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of chamber shall be approved by GE before fabrication (iii) The item shall also include dismantling, disconnecting, taking out the existing panel complete with all fittings and accessories, and removing the same from the site |
| 18 | Supply and fixing of Cable Route Indicator fabricated from 4 mm thick MS plate, 150 mm diameter, welded to a 25 × 25 × 3 mm MS angle iron single leg/stand of 500 mm minimum length on the rear side of the plate. The indicator shall be cleaned, provided with one coat of red oxide zinc chromate primer followed by two coats of approved synthetic enamel paint, and neatly lettered with \\"LT CABLE 1100 VOLT\\" in approved colour and size as directed by the Engineer-in-Charge. The cable route indicator shall be fixed in position by grouting the angle iron in PCC (1:3:6) (Type C-1) using 20 mm graded stone aggregate in a concrete block of suitable size, including excavation, backfilling, ramming and making good the disturbed surface. The indicators shall be installed along the LT cable route at the spacing directed by the Engineer-in-Charge and shall invariably be provided at every change in direction (turning point) of the cable route. The item includes all materials, labour, consumables, T&P and incidental works required for satisfactory completion, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 19 | Material and labour for dismantling PCC around existing poles and taking out old PCC poles of any height and size, whether broken above ground level, broken into parts or complete with embedded portion, from any condition, including excavation as required and removing from site. The work shall include backfilling of the excavation, dressing and making good the disturbed ground surface, and all labour, tools & plant, consumables and incidental works required for satisfactory completion, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 20 | Material and labour for providing and erecting factory-fabricated, hot-dip galvanized octagonal steel poles, 8.0 m long, having 130 mm nominal outside diameter at bottom and 70 mm at top, fabricated from 3 mm thick high-tensile steel sheets conforming to IS 2062 / BS EN 10025, complete with 220 × 220 × 12 mm thick base plate, including:(a) 1.0 m long hot-dip galvanized single-arm (swan-neck) bracket, fabricated from 40 NB dia GI pipe, suitable for mounting at the top of the pole and for fixing the street-light fitting;(b) Inbuilt junction box within the pole, suitable for incoming 3-phase LT cable, complete with hinged and lockable access door, 6A SPN 'B'-curve MCB mounted on Bakelite sheet and suitable stud-type connectors;(c) 2 × 2.5 sq mm copper flexible wire, drawn internally from the junction box through the pole and arm up to the end of the bracket for connection to the street-light fitting;(d) Four Nos. M20 × 600 mm long 'J'-type foundation bolts, EN8 grade, complete with nuts, washers and other necessary accessories;(e) Excavation for pole foundation, providing and laying PCC (1:1.5:3), Type B1, including positioning, alignment and grouting of foundation bolts in accordance with the approved manufacturer's drawings/instructions, including all necessary formwork, backfilling, compaction and making good the surrounding surface;(f) All necessary cutting, welding, fabrication, galvanizing, fixing accessories, lifting, erection, alignment, levelling and other incidental works required for complete installation, complete all as specified and as directed by the Engineer-in-Charge. |
| 21 | Supply and fixing in replacement of energy-efficient LED security light fitting/street light of 45 Watt, complete with pressure die-cast aluminium housing/body with top-opening driver cover for easy maintenance, heat-resistant clear toughened glass and suitable optical system for uniform distribution of light, complete with LED module, LED driver and all necessary internal components, terminals, connectors. Fixing the light fitting on the existing bracket/support, making necessary electrical connections, proper alignment and adjustment, testing for satisfactory illumination and ensuring proper and safe functioning of the complete fitting, complete in all respects as specified and directed by the Engineer-in-Charge.Technical specification :- (a) Lumen system efficacy of luminaire should be minimum 120 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range: Minus 10°C to Plus 50°C (d) Power factor: Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP66. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Minimum 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily) |
| 22 | Supply and fixing in replacement of energy-efficient LED wide-angle flood light fitting of 90 W capacity, complete with suitable LED driver, epoxy powder-coated pressure die-cast aluminium alloy housing/body and front cover of clear heat-resistant toughened glass, suitable for outdoor applications, including LED module, optical system, heat dissipation arrangement, terminals, connectors, gaskets and all necessary internal components and accessories. Fixing the flood light on the existing bracket/support, replacement of nut-bolts if required, including necessary electrical connections, proper alignment and adjustment for required wide-angle illumination, testing and commissioning, complete in all respects as specified and directed by the Engineer-in-Charge.Technical specification :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP66. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : More than 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily) |
| 23 | Material and labour for preparation and painting of existing steel tubular poles of 8 m to 11 m height, including all brackets, clamps, supports and other connected steel components of any description, by thoroughly cleaning the existing surface, removing dust, dirt, rust, loose/peeling paint and other loose particles using sandpaper, clean cloth, dry paint brush and other suitable means, and applying one coat of suitable aluminium paint over the entire exposed height of the pole, including brackets/clamps and connected steelwork. The work shall further include marking and painting of 5 Nos. alternate black and yellow strips, each 300 mm wide, from 1.50 m height above PCC coping, using one coat of suitable synthetic enamel paint in black and yellow colours. The pole number shall also be marked in red synthetic enamel paint in letters and figures of not less than 100 mm height at a suitable visible location, complete in all respects as specified and directed by the Engineer-in-Charge. |
| 24 | Material and labour for preparing the existing/old steel surfaces of EOT Crane, including removal of loose paint, rust, scale, dirt, grease and other foreign matter, cleaning and making the surface sound and suitable for painting, and applying one coat of approved synthetic enamel paint in Ivory / Yellow & Black colour by spray machine over the exposed surfaces of the EOT Crane, including necessary masking/protection of electrical components, cables, glass, nameplates and other parts not to be painted, and rewriting the required specifications/identification markings of the EOT Crane in the existing font and style, complete all as specified and as directed by the Engineer-in-Charge.Note: The Contractor shall be fully responsible for the safety of all personnel engaged in the work and shall provide all requisite PPE, safety equipment, protective clothing, working-at-height equipment and other necessary safety arrangements. The work shall be carried out in accordance with applicable safety requirements and under the supervision of the Contractor's authorised representative. The Contractor shall be responsible for any accident, injury or mishap arising due to failure to provide or use the required safety measures. |
| 25 | Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6-6.3 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing wire of size 4 mm dia by means of GI bolts/nuts/washers and protected by 15 mm bore GI light grade pipe upto 7.5 mtr length, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I), PCC pit chamber made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, including suitable size of cast iron frame grouted in PCC and cast iron cover and including finishing/plastering work, complete all as specified and as directed by Engineer-in-charge.Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. (iii) The item shall also include dismantling, disconnecting, taking out the existing earthing system, and removing the same from the site. |
| 26 | Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6-6.3 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing strip 25mmX4mm by means of GI bolts/nuts/washers and protected by 40 mm bore GI light grade pipe upto 7.5 mtr length, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I), PCC pit chamber made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, including suitable size of cast iron frame grouted in PCC and cast iron cover and including finishing/plastering work, complete all as specified and as directed by Engineer-in-charge.Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. (iii) The item shall also include dismantling, disconnecting, taking out the existing earthing system, and removing the same from the site. |
| 27 | Material and labour for Earthing complete with copper earth plate electrode of size 600 x 600 x 3.15 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including copper earthing strip 20mmX3mm by means of GI bolts/nuts/washers and protected by 40 mm bore GI light grade pipe upto 7.5 mtr length, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I), PCC pit chamber made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, including suitable size of cast iron frame grouted in PCC and cast iron cover and including finishing/plastering work, complete all as specified and as directed by Engineer-in-charge.Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. (iii) The item shall also include dismantling, disconnecting, taking out the existing earthing system, and removing the same from the site. Please Enable Macros to View BoQ information |
| 28 | Material and labour for Earthing complete with copper earth plate electrode of size 600 x 600 x 3.15 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including copper earthing strip 20mmX3mm by means of GI bolts/nuts/washers and protected by 40 mm bore GI light grade pipe upto 7.5 mtr length, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I), PCC pit chamber made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, including suitable size of cast iron frame grouted in PCC and cast iron cover and including finishing/plastering work, complete all as specified and as directed by Engineer-in-charge.Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. (iii) The item shall also include dismantling, disconnecting, taking out the existing earthing system, and removing the same from the site. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 2 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender