Tender For Major Capital Works Maintenance Of 346 Mig Housing At Dwarka Sector 16 B , Pkt -Ii (Hs-2021. Sh:- Supply/Replacement & Repairing Of Damaged Fire Fighting Systems At 346 Mig Ms Housing At Sector 16 B , Pkt - Ii Dwarka Ph-Ii .
Tender Overview
Project Description
Tender for Major Capital Works Maintenance Of 346 Mig Housing At Dwarka Sector 16 B , Pkt -Ii (Hs-2021. Sh:- Supply/Replacement & Repairing Of Damaged Fire Fighting Systems At 346 Mig Ms Housing At Sector 16 B , Pkt - Ii Dwarka Ph-Ii .
BOQ
| Sl. No. | Item Description |
| 1 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 2 | Supplying and fixing single headed internal hydrant valve with instantaneous Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Stainless Steel cap and chain as required. |
| 3 | Supplying and fixing 63 mm dia, 15 m long stainless steel RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required. |
| 4 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Stainless Steel(Grade 304) |
| 5 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 6 | Integration of lift pressurization system with existing fire alarm system to keep system on auto in case of fire complete as required |
| 7 | Dismantling, Cutting, resizing in two parts the existing door shutter of shaft size upto 2300 x 1500 mm including providing partition for glazing, removing the existing glass and providing & fixing new glass of suitable size on both portion of the partition complete as required. The job includes providing putty, primer and painting of the same as per specification. |
| 8 | Reconditioning, overhauling, servicing, cleaning of existing 3 way / 2 way fire brigade connection etc. including repairs/replacement of internal defective parts, greasing, oiling, so as to make them in proper functional condition etc. complete as required as per site location. |
| 9 | Supply, installation, testing & commissionig of Photoluminescent Signage of suitable size and thickness Acrylic Single Side Non Toxic non radio active maintenance free self-glowing exit sign or any other fire or emergency signs , comprising zinc sulphide chargeable crystals which glow in dark printed on u-1000 photoluminescent base chemical cover with u-v stabilized coating which glow in dark complete as required. (3mm thick) a) Lift Both Side |
| 10 | Floor Level |
| 11 | Don't use Lift In Case of Fire |
| 12 | Supplying, installation, testing and commissioning of Lit Laser Etched Exit Sign or any other Sign like hydrant, lift etc Made of 20 MS housing Powder Coted having acrylic sheet 8 single side 8+8mm in double side etched with super bright LED glass epoxy PCB Strip less then 2 watt having NICD battery with back up of 10 hours of standard size of 350mmx220 mm recharge period of 12 hours operating voltage of -190 to 230V.Double Sided |
| 13 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. (a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 (b) 20 mm nominal internal dia gun metal globe valve & nozzle. (c) Drum and brackets for fixing the equipmets on wall. (d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket 30 mtr |
| 14 | Supply, Installation, Testing and Commissioning 25 mm Air release valve, having threaded connection including the cost of required fittings as per standard design complete in all respect. |
| 15 | Checking, servicing, dehumidifying, reconditioning of the Main Electrical panel for Hydrant Main Electric pump, Sprinkler Main electric pump, Diesel Engine, Hydrant Jockey pump, Sprinkler Jockey Pump & water curtain pump along with starter for the same as required i/c cleaning, dusting, checking for loose & burned wires and fixing the same re-testing & commissioning etc., complete as required. The job includes automation of Main Electric Fire Pump for sprinkler & hydrant, Diesel Engine Pump in sequence as per specification consisting of relays, timers, sensors for fault indication, complete as per specification and requirement of local fire authority. |
| 16 | Checking, reconditioning, servicing of the diesel engine driven pump set up to 75 HP including cleaning, oiling, greasing, tightning of wires, checking & fixing of burned wires of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 17 | Checking, reconditioning, servicing of the Electric driven hydrant main pump set up to 100 HP including cleaning, oiling, greasing, tightning of wires, checking & fixing of burned wires of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 18 | Checking, reconditioning, servicing of the Electric driven main sprinkler pump set up to 50 HP including cleaning, oiling, greasing, tightning of wires, checking & fixing of burned wires of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 19 | Checking, reconditioning, servicing of the Hydrant Jockey pump set up to 15 HP including cleaning, oiling, greasing, tightning of wires, checking & fixing of burned wires of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 20 | Checking, reconditioning, servicing of the Sprinkler Jockey pump set up to 15 HP including cleaning, oiling, greasing, tightning of wires, checking & fixing of burned wires of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 21 | Checking, reconditioning, servicing of the Electric driven water curtain main pump set up to 25 HP including cleaning, oiling, greasing, tightning of wires, checking & fixing of burned wires of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 22 | Reconditioning, overhauling, servicing, cleaning of existing installed Hose Reel Drum including repairs/replacement of internal defective parts, greasing, oiling, tracing leakages & repairing and repair of pipe connection with GI Fittings, painting so as to make them in proper functional condition etc complete as required as per site requirement. |
| 23 | Checking, servicing, refixing, testing and commissioning of existing Sluice valve i/c changing gasket, repairs/replacement of internal defective parts, greasing, so as to make it in proper functional condition etc. as per direction of Engg in charge etc. complete as required.150 mm dia Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline