Tender For special Repair To Lt Panels, Ug Cable Alongwith Connected Items Near Hq Mtn Bde Area Of Phase-Ii Of Age E/M Under Ge Tenga
Tender Value
38.30 Lakhs
Estimated cost
Bid Submission
13 Oct 2026
21 days left
EMD
76600
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
kameng → Arunachal Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for special Repair To Lt Panels, Ug Cable Alongwith Connected Items Near Hq Mtn Bde Area Of Phase-Ii Of Age E/M Under Ge Tenga
BOQ
| Sl. No. | Item Description |
| 1 | Design, fabricate, supply, testing and commisioning of CPRI approved factory made LT Panel Board double door, out door type fabricated out of 3.15mm thick CRCA sheet steel for outer body and 2.00mm thick CRCA Sheet for inner partition walls, independent cabinate with cabinate doors for MCCBs, Bus Bars, cable trays, metering equipment, vertical type floor mounted on angle iron frame of 50x50x6mm with minimum height of legs 45 cm, minimum IP-54 protection, comprising of solid aluminium bus bar 4 strips suitable of 1000 Amps, suitablily grouted to PCC complete with internal wiring, epoxy powder coated, connections of cable ends with suitable size of aluminium cable lugs with the following accessories.(a) INCOMING(i) ACB 4 Pole, 415 V, with Thermal MagneticRelease (Manual Fixed type) of capacity 630 Amps - 01 No(b) OUTGOING(i) MCCB 160 Amps, 4 Pole, 415 V, 25 KA - 04 No(ii) MCCB 100 Amps, 3 Pole, 415 V, 25 KA - 03 No(iii) Digital volt meter of size 4\\"x4\\" - 01 No(iv) Selector Switch for Amp/Volt Meter - 02 Nos(v) Current Transfer (CT) - 3 Nos(vi) Phase indicator lamp (RYB) set of three - 01 No |
| 2 | Design, fabricate, supply, testing and commisioning of CPRI approved factory made LT Panel Board double door, out door type fabricated out of 3.15mm thick CRCA sheet steel for outer body and 2.00mm thick CRCA Sheet for inner partition walls, independent cabinate with cabinate doors for MCCBs, Bus Bars, cable trays, metering equipment, vertical type floor mounted on angle iron frame of 50x50x6 with minimum height of legs 45 cm, minimum IP-54 protection, comprising of solid aluminium bus bar 4 strips suitable of 800 Amps, suitablily grouted to PCC complete with internal wiring, epoxy powder coated, connections of cable ends with suitable size of aluminium cable lugs with the following accessories. S/S- 01)(a) INCOMING(i) MCCB 350 Amps, 4 Pole, 415 V, 36 KA - 01 No(b) OUTGOING(i) MCCB 125 Amps, 4 Pole, 415 V, 25 KA - 04 No(ii) Digital volt meter of size 4\\"x4\\" - 01 No(iii) Selector Switch for Amp/Volt Meter - 02 Nos(iv) Current Transfer (CT) - 3 Nos(v) Phase indicator lamp (RYB) set of three - 01 No |
| 3 | Design, fabricate, supply, testing and commisioning of CPRI approved factory made LT Panel Board double door, out door type fabricated out of 3.15mm thick CRCA sheet steel for outer body and 2.00mm thick CRCA Sheet for inner partition walls, independent cabinate with cabinate doors for MCCBs, Bus Bars, cable trays, metering equipment, vertical type floor mounted on angle iron frame of 50x50x6 with minimum height of legs 45 cm, minimum IP-54 protection, comprising of solid aluminium bus bar 4 strips suitable of 400 Amps, suitablily grouted to PCC complete with internal wiring, epoxy powder coated, connections of cable ends with suitable size of aluminium cable lugs with the following accessories. (a) INCOMING (i) MCCB 200 Amps, 4 Pole, 415 V, 36 KA - 01 No(b) OUTGOING(i) MCCB 125 Amps, 4 Pole, 415 V, 16 KA - 01 No(ii) MCCB 100 Amps, 4 Pole, 415 V, 16 KA - 03 No(iii) MCCB 63 Amps, 4 Pole, 415 V, 16 KA - 02 No(iv) Digital volt meter of size 4\\"x4\\" - 01 No(v) Selector Switch for Amp/Volt Meter - 02 Nos(vi) Current Transfer (CT) - 3 Nos(vii) Phase indicator lamp (RYB) set of three - 01 No |
| 4 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric cables with stranded aluminium conductor, 1100 volts grade, of 185 Sqmm 3.5 core all as specified and directed. |
| 5 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric cables with stranded aluminium conductor, 1100 volts grade, of 120 sqmm 3.5 core all as specified and directed. |
| 6 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric cables with stranded aluminium conductor, 1100 volts grade, of 50 Sqmm 3.5 core all as specified and directed. |
| 7 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric cables with stranded aluminium conductor, 1100 volts grade, of 35 Sqmm 4 core all as specified and directed. |
| 8 | M&L for Precast concrete cable cover class LV Type 1, flat, size 250mm 150mm x 40mm , ISI marked across the cable for protection of cable after sand cushioning complete all as specified & directed. |
| 9 | Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable incl spreading, levelling, watering and consiolidation, thickness 18 cm after punning complete all as specified and directed. |
| 10 | M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles all as specified and directed by Engr-in-Charge. |
| 11 | M&L for steel tubing galvanised, light grade complete with fittings laid in trenches/ fixed along with poles etc as protection to cables of size 80 mm dia bore complete all as specified and as directed. |
| 12 | Excavation in trenches n. exc 1.5 mtr wide and n. exc 1.5 mtr depth for pole / cable / foundation etc including getting out in hard/dense soil complete all as specified and directed. |
| 13 | Returning, filling in, approved earth including spreading, levelling, watering and well ramming in layers n.exc 25 Cm thick after cable are laid and tested complete all as specified and directed. |
| 14 | Removing excavated material / surplus soil to a distance not exc. 50 mtrs & deposited where directed at a level not exc.1.5 mtr above the ground level complete all as specified & directed. Please Enable Macros to View BoQ information |
| 15 | Removing excavated material / surplus soil to a distance not exc. 50 mtrs & deposited where directed at a level not exc.1.5 mtr above the ground level complete all as specified & directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 22, 2026
11:30 IST
Tender Published
Tender notice published.
TodayOct 13, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 21 daysOct 20, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 28 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender