Tender For Provision Of Internal & External Arrangements To The Proposed Additional District Court For Accomodation In Harur Sub Court And Renewal Of Main Distribution Line And Renewal Of Fan , Light Fitting At Harur Sub Court In Harur Block At Dharm
Tender Overview
Project Description
Tender for Provision Of Internal & External Arrangements To The Proposed Additional District Court For Accomodation In Harur Sub Court And Renewal Of Main Distribution Line And Renewal Of Fan , Light Fitting At Harur Sub Court In Harur Block At Dharmapuri District.
BOQ
| Sl. No. | Item Description |
| 1 | Rewiring with 2 x 1.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade insuitable PVC rigid pipe on wall and ceiling with PVC accessories and with TW switch box and 5A FT switch with painting of suitable colour for open PVC light point / fan point (for electronic regulator) (5 points per coil). |
| 2 | Rewiring with 2 x 1.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade insuitable PVC rigid pipe on wall and ceiling with PVC accessories and with TW switch box and 5A FT switch with painting of suitable colour for open PVC light point / fan point (for electronic regulator) (6 points per coil). |
| 3 | Supply and fixing of 1 no.6/16A two module socket , 1 no. 16A one module switch on surface module surface mounting box (plastic) with module cover plate(plastic) on wall with connections. Higher End |
| 4 | Supply and fixing of 3nos.6A two module 3 pin socket , 3 nos. 6A one module switch on suitable module surface mounting box (plastic )with module cover plate (plastic ) on wall with connection Higher End |
| 5 | Supply and fixing of 4 Feet LED 20W Fitting with LED 20W tube (Higher End) complete with TW round blocks on wall or ceiling with PVC unsheathed FRLS Copper leads from terminals to the fitting |
| 6 | Supply and fixing of 9W LED BH point. |
| 7 | Supply and fixing of 1200mm (48\\") sweep AC ceiling fan high speed complete with 2 module 100W fan step regulator (Higher end) with 300mm down rod on existing fan clamp |
| 8 | Supply and fixing of 300mm (12\\") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall |
| 9 | Supply and fixing of louvers shutters arrangements for 300mm (12\\") sweep (light duty) AC exhaust fan. |
| 10 | Supply and Run of 2 of 2.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection of 2.5 sq.mm copper wire with painting of Suitable colour |
| 11 | Supply and Run of 2 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe in wall and ceiling with continuous earth wire connection by 4 sq.mm. copper wire with painting of suitbale colour.(For 16A plug,LDB ) |
| 12 | Renewal by Supply and fixing of 400mm Oscillating type wall mounting fan with regulator complete on wall with connection complete. (Higher end) |
| 13 | Supply, Erection, testing and Commissioning of 1.5 TR (6000K cal / hr) ABS plastic split type Air conditioner confirming to IS 1391 [part 2] 1992 with Rotary compressor operating on refrigerant R-32/Non CFL suitable for wall mounting for operation on 230V, 50 HZ single phase AC Renewal by supply with Five Star rating as per BEE Specification and capable of performing the following functions.(A) Cooling (B) Dehumidifying (C) Air Circulating. (D)Filtering.The installation work for the above split type AC units includes the following.1. Mounting / fixing indoor and outdoor units at their respective locations.2. Laying refrigerent pipe line of 6mtrs. distance, both units after drilling hole / holes in the wall if required. Thickness of the copper tubing shall not be less than 0.7mm.3. Installing the suction pipe with expanded polythene foam 5mm thick tubing.4. Laying 15mm dia flexible PVC drain pipe of 6mts. Length to throw out the condensate water being formed in the indoor unit.5. Leakage testing the entire gas unit.6. Charging refrigerant gas in the unit.7. Suitable electric wiring to be provided with 2.5 sqmm PVC insulated copper wire between indoor and outdoor units up to 4mtr. length and up to switch within the 3 mtrs. of location of indoor unit. (Make - Carrier / Voltas / Blue Star make only) |
| 14 | Supply and installation of 4KVA capacity Automatic Voltage Stabilizer with time delay relay |
| 15 | Supply and fixing of MS stand for fixing outdoor unit. |
| 16 | Supply and run of 2 of 1.5sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V gradein suitable PVC rigid on wall and ceiling with continuous earthwire connection of 1.5sq.mm copper wire with Painting of suitable colour |
| 17 | Supply and fixing of 4 way vertical tripole pole and neutral MCB Sheet steel enclosure ditribution board with double door (metal) with 1 No 63 4P MCB as incoming and 12 nos 6A to 32A SP MCB as outgoing on suitable angle iron frame on wall with earth connection only HIGHER END |
| 18 | Supply, erection, testing and commissioning of Uninterrupted power supply (UPS) (Sine wave) (Make Microtech/ Alpha/ Amron /Exide/Luminous) unit of capacity 2 KVA with input voltage 60 V DC supply, output voltage 230V -50Hz AC supply with following accessories / Circuits and with 1 hr of battery backup of full load respectively. 1.Battery Charging Device2.Inverter Circuit3.Overload as well as short circuit 4.Indication for all operation like battery charging over load, low battery etc.5.Reset switch6. Exide Inva Tubular Battery 2 No. of 12V AC IT 500 150AH (Make Microtech/ Amron/ Exide/ Luminous)7.One layer wooden / steel fabricated stand. |
| 19 | Renewal by Supply and clarnping of 3½ x 95 sq.mm. PVC LTUG armoured cable on post or on wall with MS clamps. |
| 20 | Renewal by Supply and fixing of cable end box below meter board. |
| 21 | Renewal by Supply and run of 4 of 16 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade insuitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection by 16 sq.mm copper wire and making good of the concealed portion with suitable colour. |
| 22 | Supply and fixing of 20A Flush type Wall Socket 32A DP MCB complete set for AC Plug in flush with wall with earth connection (For AC Plug). |
| 23 | Renewal by Supply and fixing of 3 phase 100A aerial fuse unit for 3 Nos. 100A fuse units (500V) on suitable MS sheet covered with 6mm thick hylem sheet on suitable angle iron work the tapping pole with necessary clamps |
| 24 | Renewal by Supply and providing cable and Termination of 3½ x 95 sq.mm. PVC LTUG Aluminium Armoured cable with necessary Aluminium cable socket by crimping Etc., with Electrical connection complete. |
| 25 | Supply and run of 1 of No.8 SWG GI wire in suitable PVC rigid pipe on wall/floor/Ground for Earth Connection |
| 26 | Earthing as per PWD Standard with an earth Electrode of 2 Mtr. Class 'B' GI pipe of dia not less than 32 mm Complete with Necessary Masonary Work. |
| 27 | GST@18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender