Defence Statutory Bodies & Commissions/Committees Closing in 24 days TDR #57626962

Tender For Increment Of Mr Facility For A Vehs Under Ge I P No 1 At Leh

Issued by Statutory Bodies & Commissions/Committees · Leh, ladakh
Tender Value
2.09 Crore
Estimated cost
Bid Submission
28 Oct 2026
24 days left
EMD
2.85 Lakhs
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Leh → ladakh
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender For Increment Of Mr Facility For A Vehs Under Ge I P No 1 At Leh

BOQ

Name of Work:-
Sl. No. Item Description
1NOTE: Schedule ‘A’ Part - I to Part -X are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
2Total amount of Sch 'A' Part - I (BUILDING Works)
3Total amount of Sch 'A' Part - II (SITE CLEARANCE, EXCAVATION & EARTH WORK)
4Total amount of Sch ‘A’ Part - III(INTERNAL WATER SUPPLY)
5Total amount of Sch ‘A’ Part - IV(INTERNAL ELECTRIFICATION)
6Total amount of Sch 'A' Part -V (ROAD, PATH AND HARD STANDING)
7Total amount of Sch ‘A’ Part - VI(SECURITY FENCING AND GATE)
8Total amount of Sch 'A' Part -VII (EXTERNAL ELECTRIC SUPPLY)
9Total amount of Sch ‘A’ Part - VIII(CENTRAL HEATING SYSTEM)
10Total amount of Sch ‘A’ Part -IX (STAND BY POWER SUPPLY)
11Total amount of Sch ‘A’ Part - X(REFRIGERATION)
12SCH 'A PART - XI (Miscellaneous B/R and E/M works for Sch 'A' Part-II to Part-X)Note: This schedule is not pre-priced by MES and the rate indicated as \\"Rs 0.00\\" under Col 5 signifies this fact only
13M&L for concertina coil of 610 mm dia razor type made out of 2.5 mm dia SG hot Galvanised spring tensile wire 145 to 150 N/sqmm zinc coating 240 gms /sqm (min ) weight of coil shall be minimum 8.57 kg/coil when being not streched ,strech length of coil shall be 6.25 Rm after laying ,min nos of turns in each coil shall be 49/50 .Galvanised razor ribbon type shall be of size 0.5 mm thick ,19 mm wide before wrapping on central core wire .Concertina coil shall be fixed to existing angle iron swan neck supports using GI clips 125 to 127 Nos per coil and special nuts and bolts for holding Z coil together and extra two rows parallel wire of 10 gauge etc complete all as specified and as dircted.
14M&L for fabrication and Erection of MS Steel gate of 4m wide and 3m height complete all as shown on drg No CELZ/TD/ST-08/2017 sheet 1R/1 and as directed.
15Supply, installation, testing and commissioning LT panel of suitable size as per IE rule and latest IS, factory made dust and vermin proof outdoor type made out of 3.15 mm thick CRCA sheet including seperate compartment for each MCCB & for cable and busbar, mounted on frame of MS angle iron 40mmx40mmx6 mm with front and back openable door with lock & Key including necessary grouting and double coat powder coated of grey colour painting complete with following accessories.The degree of protection of panel shall be IP-54 including foundation all as specified and directed.:-
16INCOMING:(i) 4P, MCCB 160 A ,with rupturing cap 25 KA (INCOMER & Spare)-02 Nos(ii) Aluminium bus bar 3 phase 4 strip suitable for 250 Amps current carrying capacity complete with post insulators and heat shrinkable sleeves- 01 No.OUTGOING(I) 3P, MCCB 63 A ,with rupturing cap 16 KA -01 Nos(ii) 3P, MCCB 100 A ,with rupturing cap 16 KA -01 Nos(iii) Change Over 160 Amps-01 Nos(iv) RYB indication lamp -01 No(v) Voltmeter digital type with range 0-500 Volts, -01 No.(vi) Ammeter digital type with range 0-200 Amp .
17Supply, installation, test and commissioning of silent, Diesel engine driven factory assembled, floor mounted generating set of capacity 625 KVA at NTP 0.8 power factor or nearest higher size, 3 phase, 4 wire, 50 Hz as per IS 10001/ 10002 and Alternator as per IS: 13364 to take 10% overload complete with safety control and metering equipments mounted on & including common base frame with acoustic enclosure (canopy), weather proof as per CPCB IV+,including APFC panel, powder coated all as per manufacturer's instructions manual and all as specified and comprising of the items/ accessories listed hereinafter :-
18(A) Prime Mover : Directly coupled diesel engine, water cooled for deriving 625 KVA capacity, alternator electric start, four stroke confirming to latest IS-10001/10002 for continuous running and capable for taking 10% over load for 01 hour complete with following accessories :- (i) Fly wheel to suit flexible coupling. (ii) Flexible coupling with guards. (iii) Air cleaner with filters. (iv) Lubricating oil filter (v) Heavy duty radiator assembly with fan. (vi) Anti-vibration pads as recommended by manufacturers. (vii) PT pump with electronic governor of suitable capacity. (viii) Self starter 12 volts DC. (ix) Necessary arrangement for charging battery. (x) Maintenance free battery 12 volts, 180 AH, duly charged -02 Nos, as recommended by manufacturer alongwith flexible copper battery lead and connector. (xi) Battery rack made out of MS angle iron 40 mm x 40 mm x 5 mm & 150 mm height - 01 No.(xii) Standard safety device. (xiii) Daily services fuel tank for full running capacity of DG set for min 12 hours enclosed within the canopy all as per CPCB with lever indicator inlet, fuel outlet drain plug, air vent and locking arrangements etc including fuel pipe connections with connected GI pipe medium grade from fuel tank to DG set and over flow from the DG set to fuel tank complete with gate valve.
19(xiv) Exhaust system shall be provided with thermal insulation by using fire retardant/ non igniting foam conforming to BS-4735 to prevent excess heat radiation on the engine and safe for operator. (xv) Mechanical panel having following accessories :- (aa) Digital Lubrication oil temperature guage - 01 No. (ab) Digital Lubrication oil pressure guage - 01 No. (ac) Digital Water temperature guage - 01 No. (ad) Starting switch with key - 01 No. (ae) Battery voltmeter. (af) Indicator lamp etc.(ag) Digital Ammetar DC-01 No.(ah) Digital RPM meter-01 No.(aj) Safety measures:- (i) Low lubricant oil pressure trip. (ii) High coolent temp trip.(iii) Engine over speed trip.(iv) Battery charging alternator.(v) Emergency stop pressed.
20(B) Alternator : Self regulated 3 phase with neutral 415 volts 50 Hz as per IS : 13364 complete with automatic voltage regulator and foot mounted including making cable connection. (C) Control AMF Panel: AMF control panel inside the floor mounted accoustic enclosure suitable for 625 KVA DG set with bypass assessment including all necessary operating and control device (to meet the requirement of above capacity plus 25% over load) such as contactors, MCCBs, CTs, volts meter, Ammeter, indicating lamp, frequency meter, energy meter with protection fuses for panel instrument battery charging ststem with indicator and cut off relays low and high oil pressure, high speed over load and earth fault protection, reverse current protection duly wired copper conductor cable and cable connection with lugs/thimbles complete as recommended by manufacturers and as directed.(D) Repair tools and 2 years maintenance spare parts as per following :- Repair Tools :- (i) Ring spanner set of 10 - 01 set. (ii) Screw driver 6”, 8”, 12”, 14” & 24”- 02 each (iii) Double End Spanner set of 10 - 01 set. (iv) Adjustable spanner 12” – 04 Nos. (v) Cutting pliers – 01 No. (vi) Techo meter- 01 No. (vii) Tools kit box (only box) – 01 No. 2 Years' Spares :- (a) Fan belt set complete - 01 No (b) Lub oil filter - 01 Set (c) Fuel filter - 01 Set (d) Service manual and spare part catalog with guarantee card (e ) Shock treatment chart dully framed - 01 Set (f) First Aid Box - 01 set (g) Fire extinguisher foam type - 01 set (h) Fire extinguisher (Class 'A' &Class 'B' Type ) - 01 set.
21(E) ACOUSTIC ENCLOSURE :- Acoustic enclosure (canopy) suitable for 625 KVA DG shall be with the following provisions/ specifications :- (i) The enclosure fabricated out of CRCA sheet of 14 SWG suitable to accommodate the DG Set properly. (ii) The sheet metal components are hot dip seven tank pretreated. (iii) It is pure polyester based powder coated (inside as wall as outside). All nuts/bolts/hardwares are zinc coated with salt spray test as per ASTMB- 117. (iv) Battery is accommodated in a tray in the enclosure. (v) The doors are fitted with gasket with high quality EPON gasketed to avoid leakage of sound.(vi) Sound proofing of enclosure is done with high quality rock wool/mineral wool conforming to IS 8131 of 50 mm thickness and density of 96 kg/cum.(vii) The wool is further covered with fiber glass cloth and perforated powder coated sheet, insulation level conforming to UL 94 HF1 class flamability. (viii) A special residential silencer is provided within the enclosure to control exhaust noise. (ix) Specially designed alternators are provided to control sound at air entry to the container and exhaust from the container. (x) Adequate ventilation is provided to meet requirement for combustion and heat removal. If required a blower is used to meet total air requirement and air changes. Please Enable Macros to View BoQ information
22(E) ACOUSTIC ENCLOSURE :- Acoustic enclosure (canopy) suitable for 625 KVA DG shall be with the following provisions/ specifications :- (i) The enclosure fabricated out of CRCA sheet of 14 SWG suitable to accommodate the DG Set properly. (ii) The sheet metal components are hot dip seven tank pretreated. (iii) It is pure polyester based powder coated (inside as wall as outside). All nuts/bolts/hardwares are zinc coated with salt spray test as per ASTMB- 117. (iv) Battery is accommodated in a tray in the enclosure. (v) The doors are fitted with gasket with high quality EPON gasketed to avoid leakage of sound.(vi) Sound proofing of enclosure is done with high quality rock wool/mineral wool conforming to IS 8131 of 50 mm thickness and density of 96 kg/cum.(vii) The wool is further covered with fiber glass cloth and perforated powder coated sheet, insulation level conforming to UL 94 HF1 class flamability. (viii) A special residential silencer is provided within the enclosure to control exhaust noise. (ix) Specially designed alternators are provided to control sound at air entry to the container and exhaust from the container. (x) Adequate ventilation is provided to meet requirement for combustion and heat removal. If required a blower is used to meet total air requirement and air changes. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57626962
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 2.09 Crore
LAST DATE 28-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender For Increment Of Mr Facility For A Vehs Under Ge I P No 1 At Leh
Basic Detail
Tender No 180170/E8
Bidding Type Tender
Location
City Leh
State ladakh
Key Dates
Publish Date 21 Sep 2026
Submission Date 28 Oct 2026
Open Date 30 Oct 2026
Finance
Tender Value 2.09 Crore
Tender Fee 2000
EMD 2.85 Lakhs
Exemption Available
Document List
BOQ_886057.xls
d90cc5f0-c329-45dd-9ff5-f2793b5fea0a.html
Tender180170.pdf
Tendernotice_1 (10).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 21, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 28, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 24 days
Oct 30, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 26 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_886057.xls

html

d90cc5f0-c329-45dd-9ff5-f2793b5fea0a.html

pdf

Tender180170.pdf

pdf

Tendernotice_1 (10).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders