Tender For Electrical Installation Work Of Gas Manifold Room, Common Collection Point, New Dialysis & Kitchen Building At Howrah District Hospital, Howrah.Rn 23002383. --- Supply Installation Testing and Commissioning of Ups System.
Tender Overview
Project Description
Tender for Electrical Installation Work Of Gas Manifold Room, Common Collection Point, New Dialysis & Kitchen Building At Howrah District Hospital, Howrah.Rn 23002383. --- Supply Installation Testing and Commissioning of Ups System.
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation Testing & commissioning of 10 KVA 1 Phase, 50 Hz, 160V-300V input, 1 phase output UPS system with required nos of SMF Battery, Rack DC connecting cables and complies with following feature/ specifications. (Make- APC/Numeric/Emmerson/Power One/Microtek/Orion) [NS] |
| 2 | UPS Technology & Capabilites |
| 3 | i) True online configuration with Double Conversion ii) Fully digital control with three Digital Signal Processor including rectifier, Invertor, Charger. iii) Input power factor to load > 0.99 lag iv) Main back feed protection v) Lightning Protection Device vi) Sinusoidal Waveform vii)Display:LED+LCD |
| 4 | UPS input |
| 5 | i) Connection - 1P+N+PE ii)Voltage:230V AC iii) Power Supply-1 Phase, 50 Hz,160V- 300V AC iv) Voltage Range 110V-300 VAC @ 50% load v) Input power frequency range 50 Hz-60Hz± 5% auto sensing vi)THD of input current <10% vii) DC Voltage: 192-240 V |
| 6 | UPS Output |
| 7 | i) Phase- Single ii) Voltage - Single Phase - 220/230/240 VAC iii) Frequency - 50 Hz iv)Frequency Synchronisation - 47.5 Hz to 52.5 Hz v) Output Voltage Regulation - ±1% vi) THD of output Voltage THD < 3% (Linear Load) THD < 5% (Non Linear Load) vii) Power Factor 0.8 viii) Crest Factor 3.1 ix) AC to AC overall efficiency: 92% x) ECO mode: NA xi)Converter : Yes xii)Configurable bypass: Yes |
| 8 | Static Bypass Switch |
| 9 | 1. The statich shall consist of fully rated Silicon Controlled Rectifiers (SCRs) 2. The static bypass switch shall automatically transfer the critical load to bypass input supply without interruption after the logic senses one of the following conditions Inverter overload beyond rating. Battery runtime expired and bypass available. Inverter failure. Fatal error in control system. 3. The static bypass switch shall be equipped with a manual means of transferring the load to bypass and back to inverter. 4. Also UPS should have separate manual bypas switch |
| 10 | Overload Capacity |
| 11 | i) 105-110%- 3 mins. ii) 111-130%- 30 sec. A) The Display panel should capable for display of following measurement/ as per standard availability of specified manufacturer. i) Input - Voltage/ Frequency/ Current. ii) By- pass - Voltage/ Frequency. iii) Output - Voltage/ Frequency/ Current. iv) Battery - Voltage/ Current/ Percentage v) Load - KVA/ KW/ Percentage vi) Others standard measurement as per manufacturer standard & IS specification. B) The display panel should also capable to display following indication i) DC bus boltage - High/ Low ii) Inverter - Overload / Short Circuit iii) Over Temperature -Battery / By-pass/ Inverter iv) Fault - Rectifier/ By-pass / Inverter/ Paralleling v) Fuse failure- Input / Output vi) Battery - Low/ Overcharged |
| 12 | Alarms |
| 13 | The UPS should generates an audioble alarm for following condition. Mains failour Battery Low UPS Over Load (>_ 110 %) Fault Shut Down |
| 14 | Battery Bank / Charger/ Rack |
| 15 | i) Backup Capacity - 30 min on Full load ii) Battery Bank VAH - 10080 VAH iii) Battery Type - 12V, VRLS SMF type (Make- Amara Raja/ Exide/Quanta) iv) Minimum charger rating- 10% of battery AH rating offered v) Battery recharge time (after complete discharge) to 90% capacity - 10-12 Hrs. vi) Battery Protection - DC MCCB (Internal/ External) vii) Battery Housing - MS steel rack of compact & space saving design. viii) Battery End Cell Voltage - 1.75/ 1.80 V |
| 16 | UPS Physical Condition |
| 17 | i) Operating Temperature- 0-40°C Continuous ii) Humidity-O - 95% Rh (non-condensing) iii) Protection Class - IP-20 iv) Type of Cooling - Forced Air v) Noice Level - <58db at 1 mtr distance vi) All the electronic cards inside shall be with conformal coating to protect from harsh / Moist environment. vii) UPS panel should have Dust filter protection with sensor. |
| 18 | Certification |
| 19 | Standard IS/IEC certification must be submit along with offer. Product should have BIS,CE &RoHS,PEP(Product Environmental Profile) Compliance.EN 62040-2 (EMC), EN 62040-1(Safety),IEC 62040-3(Performance) |
| 20 | Terms & Condition |
| 21 | i) 24 months onsite warrantee on complete installation inclusive of spare parts. ( except physical damages of installation i.e. Rat etc. attack) ii) Any Problem must be set right with 24 hrs after reporting. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender