Housing Urban and Rular Development Government Departments Closing in 6 days TDR #57619572

Tender For Up-Gradation Of Estate Electrical Services For Residential Buildings In Police C Us At Police Station Civil Lines, District Karnal.

Issued by Government Departments · Karnal, Haryana
Tender Value
34.55 Lakhs
Estimated cost
Bid Submission
28 Sep 2026
6 days left
EMD
25000
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Karnal → Haryana
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Up-Gradation Of Estate Electrical Services For Residential Buildings In Police C Us At Police Station Civil Lines, District Karnal.

BOQ

Name of Work:- Up-gradation of Estate Electrical Services for Residential Buildings in Police C us at Police Station Civil Lines, District Karnal.
Sl. No. Item Description
1HSR PART[10.33.1]Providing and laying of brick on edge flooring with bricks of class designation 7.5 on a bed of 12 mm cement mortar, including filling the joints with same mortar, with common burnt clay non modular bricks: 1. 1:4 (1 cement : 4 coarse sand) [Through Rate]
2[10.78]Providing and laying 100mm thick factory made cement concrete interlocking paver block of M -35 grade made by block making machine with strong vibratory compaction, of approved size, design and shape, laid in required colour and pattern over (BIS 15658:2006) and including 60mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge. [Through Rate]
3[11.60]Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. [Through Rate]
4[11.69.1]Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content. 1. With ready mixed pink or grey primer on wood work (hard and soft wood) having VOC content less than 50 grams/ litre [Through Rate]
5[11.71.1]Wall painting on a cement plaster surface with acrylic emulsion paint of approved brand and manufacture to give an even shade : 1. Two or more coats on new work [Through Rate]
6[11.82.1]Painting the wooden / metal surface with synthetic enamel paint of approved brand and manufacture to give an even shade : 1. Two or more coats on new work [Through Rate]
7[12.52]Providing and fixing hard drawn steel wire fabric 75x25 mm mesh of weight not less than 7.75 Kg per sqm to window frames etc. including 62x19 mm beading of second class teak wood and priming coat with approved steel primer all complete. [Through Rate]
8[13.2]Providing and fixing angle iron frames for doors, windows and ventilators of mild steel Angle sections of size 35x35x5 mm, joints mitred and welded by angle iron 35x35x5 mm or 35x 5 mm flat pieces to the existing T-iron frame or to the wall with dash fastener, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer, all complete as per the direction of Engineer-In-charge. [Through Rate]
9[20.71.1]Supply, erection, testing of Ceiling fans IS marked (as per IS code 374) with suitable GI pipe complete in all respects complete as per directions of Engineer-in-charge 1. 48\\" (1200mm) [Through Rate]
10[20.72]Supplying, errection, testing of Exhaust fan (as per IS code 374) having a capacity of 45 cubic metre per minute complete with suitable G.I sheet ducting in structure confirming to latest IS specifications complete in all respect to satisfaction of Engineer-in-charge. [Through Rate]
11[20.84]Providing and fixing of insulated rubber matting suitable for 11 KV installation 1 M x 2 M x 12 mm thick (IS code 15652-40091) as per specification complete and as per directions of Engineer-in-charge [Through Rate]
12[20.86]Supply, erection, testing and commissioning of G.O. Switch two poles, with blade, pin 6 insulators operating handle with GI pipe 25 mm class B complete in all respects. [Through Rate]
13[20.88]Supply, erection, testing and commissioning of CT meter of standard make with cubical meter box as per HVPNL specifications including 3 phase electrical meter 100/5 of standard make approved by HVPNL including CT/PT of suitable rating complete in all respect as per directions of Engineer-in-charge [Through Rate]
14[22.173.1]Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design : 1. With common burnt clay non-modular bricks of class designation 7.5 [Through Rate]
15[22.174.1]Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : 1. With common burnt clay non-modular bricks of class designation 7.5 [Through Rate]
16[22.175.1]Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : 1. With common burnt clay non-modular bricks of class designation 7.5 [Through Rate]
17[23.15]Replacement of ball bearing of a ceiling fan including greasing, re-assembling and testing etc. [Through Rate]
18[23.16]Replacement of a bush bearing of any fan including turning, oiling, re-assembling and testing etc. [Through Rate]
19[23.17.1]Replacement of a fan condenser complete with connections and testing etc. 1. 2 to 3.5 mfd. [Through Rate]
20[23.22.1.12]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.12. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 300 to 400 amp , 50 KA [Through Rate]
21[23.22.1.3]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.3. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. TRIPLE POLE MCCB 16 to 100 Amp, 25 KA [Through Rate]
22[23.22.1.4]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.4. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. TRIPLE POLE MCCB 125 to 160 Amp, 25 KA [Through Rate]
23[23.22.1.5]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.5. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. TRIPLE POLE MCCB 200 to 250 Amp, 25 KA [Through Rate]
24[23.22.5.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.1. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Single Pole [Through Rate]
25[23.22.5.3]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.3. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Double POLE [Through Rate]
26[23.22.5.6]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.6. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. MCBs TRIPLE POLE [Through Rate]
27[23.22.5.8]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.8. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. MCBs FOUR POLE [Through Rate]
28[23.22.8.5]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 8.5. SITC Four pole ON LOAD Manual change over switch in SS enclosure of following Ratings 400 amp 415 volts [Through Rate]
29[23.24.1]MS STAND, BUS BAR CHAMBER AND PANELS 1. Supply and erection of M.S. angle iron frame duly welded for housing M.S. sheet & main switches etc. on it, fixed on wall by means of suitable size of rag bolts with cement concrete, duly painted with three coats of approved paint including one coat of red oxide. [Through Rate]
30[23.24.4.4]MS STAND, BUS BAR CHAMBER AND PANELS 4.4. Supply, installation, testing and commissioning of load bank with digital meter module cost of digital Amp. / volt meter with selector switch wiring ( but EXLUDING COST of incoming and outgoing MCCBs ) etc.suitable for operation of 240/415 volts A.C. Supply with both side cable allay, inter connection and fixing the same in existing MS pedestal/wall complete with all labour and material required for the same up to the entire satisfaction of Engineer-in-Charge of work. Load Bank 8 way 400 amp. [Through Rate]
31[23.26.4]SAFETY ITEMS 4. Supply & Erection of mild steel bucket stand suitable for 6 Nos. fire buckets,(but without bucket) including the cost of welding and painting of complete stand will one coat of red oxide and 2 coats of approved paint of red colour with all labour and material required to complete the job in all respect up to the entire Satisfaction engineer in charge of the work (size 6x4 made of GI pipe 32mm dia). [Through Rate]
32[23.27.1]Supply and erection of Godrej Almirah typeM.S. pedestal made of 50 mm x 50 mm x 6 mm angle iron frame with 3.00 mm thick M.S. sheet covering including shutters with suitable hinges and locking arrangement with Godrej type handle including round bars . The top covering should have downward overhang of 75 mm on all sides of pedestal , having two sets of water proof ventilation holes of suitable size on the sides , at top and bottom , each set containing four Nos. holes to discharge the heat produced by the current . The shutters fixed with rubber gasket of superior quality and of suitable size to make it water proof . The pedestal duly painted both inside and outside with two coats of approved paint and primary coat and its legs are embeded upto the entire depth in 1:2:4 cement concrete block , projected 75 mm all around the pedestal and and 200 mm above the ground level including the cost of all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work:- 1. M.S. pedestal of size 600 mm wide , 750 mm high ,300 mm deep and bottom totally open , duly embeded in 1:2:4 cement concrete block of size 750 mm x 450 mm x 200 mm above ground level , having a base of size 900 mm x 600 mm x 250 mm below ground level. 0 0 [Through Rate]
33[23.28.12.13]Supplying, installation, Testing and Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency )85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency )85%,THD ( 10% as per IEC 61000-3-2 , P. F.=0.95, IP- 66,IK-10, CRI )80, under voltage and over voltage protection, EMI- EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver and electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) (5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy =105 (120 lm/Watt output . LM79 and LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 13. 72 watt [Rate]
34[23.28.15.3]Supplying, installation, Testing and Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency )85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4- 5, Driver efficiency )85%,THD ( 10% as per IEC 61000-3-2 , P. F.=0.95, IP- 66,IK-10, CRI )80 , under voltage and over voltage protection, EMI- EMC as per CISPR -15 , lenses for beam angle 30 deg-120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver and electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) (5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy 105 (120 lm/Watt output . LM79 and LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 3. 100 watt [Rate]
35[23.28.15.5]Supplying, installation, Testing and Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency )85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4- 5, Driver efficiency )85%,THD ( 10% as per IEC 61000-3-2 , P. F.=0.95, IP- 66,IK-10, CRI )80 , under voltage and over voltage protection, EMI- EMC as per CISPR -15 , lenses for beam angle 30 deg-120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver and electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) (5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy 105 (120 lm/Watt output . LM79 and LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 5. 200 watt [Rate]
36[23.3.6.1]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.1. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 1.50 Sqmm(1/1.40mm) [Through Rate]
37[23.3.6.3]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.3. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 4 Sqmm(1/2.24mm) [Through Rate]
38[23.3.6.4]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.4. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 6 Sqmm(1/2.80mm) [Through Rate]
39[23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. [Through Rate]
40[23.7.6.4]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.4. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 40 mm dia. [Through Rate]
41[23.8.1.12]FITTING AND ACCESSORIES 1.12. Providing and fixing Piano type accessories of approved make in existing box and Bakelite sheet including fixing and making necessary connections, complete in all respect. Bakelite angle/straight button holder large size. [Through Rate]
42[23.8.1.2]FITTING AND ACCESSORIES 1.2. Providing and fixing Piano type accessories of approved make in existing box and Bakelite sheet including fixing and making necessary connections, complete in all respect. Wall socket 5 amp on existing sheet. [Through Rate]
43[23.8.1.6]FITTING AND ACCESSORIES 1.6. Providing and fixing Piano type accessories of approved make in existing box and Bakelite sheet including fixing and making necessary connections, complete in all respect. Call bell 220/230 volts musical type [Through Rate]
44[23.8.10.1]FITTING AND ACCESSORIES 10.1. Providing and fixing GI concealed sheet metal boxes with inner and outer face plate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material required for the job complete in all respects. 1 & 2 Modules including combined plate for Telephone and data [Through Rate]
45[23.8.10.2]FITTING AND ACCESSORIES 10.2. Providing and fixing GI concealed sheet metal boxes with inner and outer face plate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material required for the job complete in all respects. 3 Modules [Through Rate]
46[23.8.10.3]FITTING AND ACCESSORIES 10.3. Providing and fixing GI concealed sheet metal boxes with inner and outer face plate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material required for the job complete in all respects. 4 Modules [Through Rate]
47[23.8.10.4]FITTING AND ACCESSORIES 10.4. Providing and fixing GI concealed sheet metal boxes with inner and outer face plate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material required for the job complete in all respects. 6 Modules [Through Rate]
48[23.8.10.5]FITTING AND ACCESSORIES 10.5. Providing and fixing GI concealed sheet metal boxes with inner and outer face plate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material required for the job complete in all respects. 8 Modules [Through Rate]
49[23.8.10.6]FITTING AND ACCESSORIES 10.6. Providing and fixing GI concealed sheet metal boxes with inner and outer face plate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material required for the job complete in all respects. 12 Modules [Through Rate]
50[23.8.11.1]FITTING AND ACCESSORIES 11.1. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. 5 amp 1 way switch [Through Rate]
51[23.8.11.10]FITTING AND ACCESSORIES 11.10. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. Blanking plate [Through Rate]
52[23.8.11.2]FITTING AND ACCESSORIES 11.2. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. 5 amp 2 way switch [Through Rate]
53[23.8.11.3]FITTING AND ACCESSORIES 11.3. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. 15 amp 1 way switch [Through Rate]
54[23.8.11.4]FITTING AND ACCESSORIES 11.4. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. 5 amp Socket [Through Rate]
55[23.8.11.5]FITTING AND ACCESSORIES 11.5. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. 15 amp 6 pin Socket [Through Rate]
56[23.8.11.6]FITTING AND ACCESSORIES 11.6. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. Bell Push [Through Rate]
57[23.8.11.7]FITTING AND ACCESSORIES 11.7. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. step type Fan Regulator 2 modules 300 watt [Through Rate]
58[23.8.11.9]FITTING AND ACCESSORIES 11.9. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. T.V. Socket outlet modular type [Through Rate]
59[23.8.2.1]FITTING AND ACCESSORIES 2.1. Supply and Fixing Bakelite sheet on existing MS/GI/wooden/PVC box etc including fixing with brass screws and washers. 5 mm thick [Through Rate]
60[23.8.5]FITTING AND ACCESSORIES 5. Supply and erection 5-30 A single phase A.C. energy metre , LCD display and optical port , with rag bolts on wall/existing pedestal including the cost of rag bolts required to complete the job in all respect with necessary connections and bonding to earth. [Through Rate]
61[23.8.9]FITTING AND ACCESSORIES 9. Supply and erection direct reading LCD Display Digital Ammetre/Voltmetre ( without CT or PT ) on wall/existing penal complete in all respect with necessary connections [Through Rate]
62[24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. [Through Rate]
63[24.1.10]EARTHING AND LIGHTENING ARRESTOR 10. Providing and fixing 25 mm x 5mm copper strip on surface or in recess for connections etc. as required with all labour and material. [Through Rate]
64[24.1.13]EARTHING AND LIGHTENING ARRESTOR 13. Providing and fixing 4.00 mm dia G1. Wire on surface or in recess for loop earthing as required. [Through Rate]
65[24.1.14]EARTHING AND LIGHTENING ARRESTOR 14. Supply and erection of 20mm x 3 mm thick GI, tape fixed with suitable G.I. staples of same size. [Through Rate]
66[24.1.16]EARTHING AND LIGHTENING ARRESTOR 16. Supply and erection of 25mm dia 1.5 metre long lightning GI. tube rod tapered into a point at the top with 16cm x 16cm x 3mm thick G.I. base plate and necessary nuts and bolts with washers. [Through Rate]
67[24.1.17]EARTHING AND LIGHTENING ARRESTOR 17. Providing and fixing testing joints made of 20mm x 3mm thick G.I. strips 125 mm long with 4 nos. G.I. bolts and nuts with washers complete. [Through Rate]
68[24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required. [Through Rate]
69[24.1.3]EARTHING AND LIGHTENING ARRESTOR 3. Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required. [Through Rate]
70[24.1.4]EARTHING AND LIGHTENING ARRESTOR 4. Earthing with tinned copper earth plate 600mmx600mmx3mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) etc. complete as required. [Through Rate]
71[24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode. [Through Rate]
72[24.1.7]EARTHING AND LIGHTENING ARRESTOR 7. Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required. [Through Rate]
73[24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. [Through Rate]
74[24.1.9]EARTHING AND LIGHTENING ARRESTOR 9. Providing and fixing 25 mm x5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required. [Through Rate]
75[24.10.1]CIVIL ITEMS (USED COMMONLY IN ELECTRICAL WORKS) 1. Digging & refilling of trench 30 cm wide below ground level for erection of pipe/cable (up depth of 1 Metre. underground cable excluding the cost of cable/pipe complete in all respect. [Through Rate]
76[24.10.4]CIVIL ITEMS (USED COMMONLY IN ELECTRICAL WORKS) 4. cement concrete 1:2:4 with stone aggregate 20 mm nominal size in Kerbs and the like items, finished smooth with 6 mm thick cement plaster 1:3 on exposed surface including from work, placing and fixing in position, complete at the ground level or in first storey [Through Rate]
77[24.10.6]CIVIL ITEMS (USED COMMONLY IN ELECTRICAL WORKS) 6. Digging of pucca road in required width for laying of cable / pipe complete in all respect up to the entire satisfaction of Engineer-in charge [Through Rate]
78[24.13.13]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 13. 10 Sq mm 2 core (UnArm.) [Through Rate]
79[24.13.24]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 24. 16 Sq mm 4 core (Arm.) [Through Rate]
80[24.13.32]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 32. 25 Sq mm 4 core (Arm.) [Through Rate]
81[24.13.48]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 48. 50 Sq mm 4 core (Arm.) [Through Rate]
82[24.13.88]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 88. 240 Sq mm 3.5 core (Arm.) [Through Rate]
83[24.16.2]HT CABLES (Aluminium Conductor, Armoured and Unarmoured) Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches/Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the Works 2. Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches/Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the Works 50 Sq mm 3 core [Through Rate]
84[24.16.4]HT CABLES (Aluminium Conductor, Armoured and Unarmoured) Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches/Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the Works 4. Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches/Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the Works 95 Sq mm 3 core [Through Rate]
85[24.3.4.1]HT CABLE 4.1. Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :70 to 120 sqmm [Through Rate]
86[24.4.8.5]STREET LIGHT 8.5. Supply and erection of Hot Dip Galvanized octagonal pole of 3mm thickness, with base plate including cost of nut and bolts , earthing studs, Integral Cable termination arrangement 5 mm thick Bakelite base plate on suitable welded MS/GI bracket 32 A four way connector 2 no 10 A SP MCB , end cover and all accessories as supplied by the manufacture including Providing RCC foundation of M25 grade (1 Cement:1 Stone aggregate: 2 Coarse sand) i/c excavation, steel reinforcement (Fe 500) @80 kg/cum of concrete contents, concrete cover 50mm, anchor bolts etc. over a bed of PCC 1:5:10 of required dimensions for octagonal poles of various heights as per following specifications complete in all respects and as per directions of Engineer-in-charge 7 Metre Long pole with top dia 75 0mm and bottom dia 150 mm with base plate of size 300 x 300 x 20 mm [Through Rate]
87[24.5.2.3]MISCELLANEOUS ITEMS 2.3. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 63/50 mm outer dia/inner dia [Through Rate]
88[24.5.2.4]MISCELLANEOUS ITEMS 2.4. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 90/75 mm outer dia/inner dia [Through Rate]
89[24.5.2.7]MISCELLANEOUS ITEMS 2.7. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 180/150 mm outer dia/ inner dia [Through Rate]
90[24.6.1]DISMANTLING 1. Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required. [Through Rate]
91[24.6.2]DISMANTLING 2. Dismantling of pole/ street light standard/ strut embedded in brick ballast foundation etc. as required. [Through Rate]
92[7.21.1]Brick work with common burnt clay non-modular bricks of class designation 10.5 in foundation and plinth in: 1. Cement mortar 1:4 (1 cement : 4 coarse sand) [Through Rate]
93NS PARTSupply and filling of fresh transformer oil complete in all respect including etc.
94Supply and filling of Silicone Gel in existing breather of transformer complete in all respect including cost of material and labour etc.
95Replacement of Silica Gel Breather complete in all Respect including cost of material and labour etc.100 KVA to 315 KVA Transformer
96Replacement of Tap Changer Switch competes in all Respect including cost of material and labour etc.100 KVA to 315 KVA Transformer
97Supply, installation, testing and commissioning of wall / free standing floor mounting dust and vermin proof compartmentalized cubical panel made out of 2 mm thick CRCA sheet, fabricated at site or fabricated at workshop with required hardware 3-mm thick Bakelite sheet provided all along the bus bar and cable alley separating switches compartment and supporting suitable channel duly painted by 2 coat of Zinc / Red oxide primer followed by 2 coats of powder coating in grey or required shade after rinsing. Complete in all respect as entire satisfaction of engineer in charge.
98Supply, installation, testing and commissioning of 9.6w / mtr led strip with AC to DC Driver, Operating voltage 140-270v, cct 3000k, PF )0.5. The fixture shall be designed for a system life of 30,000 hours. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. (Approved Makes : Philips / Havells/ Wipro /Bajaj)
99S/E of ACSR bare (uninsulated) conductor confirming to DHBVN Specification with all labour, material required to complete the job on the existing pole. (i) Size 50 Sqmm (Bared)
100S/E of ACSR conductor confirming to ISS 398/1976/ part-II with latest amendment duly ISI marked with all labour, material required to complete the job on the existing pole. (2) Size 80 Sqmm (insulated)`
101SITC of Powder coated, 2MM CRCA sheet steel enclosed outdoor weatherproof type 11KV H.T. Metering Panel complete with the following:1set of 11/ v3KV / 110/ v3 Volt, 100/75 VA per phase burden and accuracy class 0.5/0.2 S, single phase construction, dry type cast resin PT. 03 Nos. of dual core 50/5A, 15 VA burden, accuracy class CL 0.5/0.2 S plus 5P10, 11 KV cast resin CTs, One Set of Phase Indicating Lamps.2 Sets of HRC fuses with fuse base (H.T. Fuse - 1A and LT fuse 2-6A)., 2 Nos. indoor cable end box suitable for 3C x 240 sq.mm. 11/33 KV, aluminum conductor XLPE Ar. cable (Incoming and Outgoing cable)., 1 No. UHVBN/ DHVBN approved digital Trivector meter with MDI in KVA of accuracy class - 0.5/0.2 S (Accuracy class shall be as per local board), With Sealing, Earthing, Interlock, IP55 Protection, vermin and dust proof mounted on suitable MS Channel, Danger Plate etc. complete in all respect up to the entire satisfaction of Engineer - in - charge of the work including making necessary connections etc.Note: The contractor shall get the Tri vector meter, CTs` and PT tested by UHVBN/ DHVBN and the charges for lesioning for the same will be paid extra. Note: The contractor shall ensure that the above panel meets the requirement as insisted by State/Local authorities (As per UHVBN/ DHVBN) for satisfactory operation and as per the Drawings.
102Supply and Erection of 11 Kv lighting arrester s/stn type 9kva 10ka heavy duty with Housing Material Polymeric (Silicone Rubber) or Porcelain. Hermetically sealed with neoprene gaskets to prevent moisture ingress. Vertical Mounting on a self supporting steel structure or insulating base. Includes a surge monitor (discharge counter) and a leakage current meter. Conforms to IEC 60099-4 or IS 3070 (Part 3). System Voltage: 11 kV (Nominal), 12 kV (Highest). Rated with Voltage 9 kV RMS. Nominal Discharge Current: 10 kA. Station Class Arrester, heavy-duty, gapless Zinc Oxide (ZnO). Continuous Operating Voltage 7.65 kV to 8 kV RMS. with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in- charge of the work
103Supply and Erection of 11 Meter PCC pole including excavation and refilling with soil. Having a standard weight typically around 365 kg. Suitable for a working load (WL) of 400 kg applied 0.6 meters from the top. Designed with a factor of safety (F.O.S) of at least 2.5 for 11kV lines. Made from High-grade concrete (e.g., M420 or M42) with 53-grade Ordinary Portland Cement (OPC) and cold-drawn indented prestriking wire. with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in- charge of the work.
104Supply and erection of mild steel hot dip galvanized stay set with stay plate having size of stay rod 1.8m to 2.4m long, stay wire 12 Mtr with threading, square anchor plate size 200mm to 300mm wide 6mm thick. with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in- charge of the work. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57619572
AUTHORITY Government Departments
TENDER VALUE 34.55 Lakhs
LAST DATE 28-09-2026
Authority
Authority Name Haryana Police Housing Corporation Limited
Work Description Tender for Up-Gradation Of Estate Electrical Services For Residential Buildings In Police C Us At Police Station Civil Lines, District Karnal.
Basic Detail
Tender No 20263A6DB262 B353 4428 96B7 C877C2C7EA6C57HHC
Bidding Type Tender
Location
City Karnal
State Haryana
Key Dates
Publish Date 21 Sep 2026
Submission Date 28 Sep 2026
Open Date 29 Sep 2026
Finance
Tender Value 34.55 Lakhs
Tender Fee 5900
EMD 25000
Exemption Available
Document List
2XE54AZ175957.pdf
BOQ_625947.xls
c79cd1d6-db7a-4e42-89b5-61faf181f780.html
OT0175957.pdf
Tendernotice_1 (20).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 21, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 28, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 6 days
Sep 29, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 7 days

Tender Documents

Download All (ZIP) ↓
pdf

2XE54AZ175957.pdf

xls

BOQ_625947.xls

html

c79cd1d6-db7a-4e42-89b5-61faf181f780.html

pdf

OT0175957.pdf

pdf

Tendernotice_1 (20).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders