| Sl. No. | Item Description |
| 1 | M&L for Carry out 'C' check from authorised rep or service engineer from the manufacturer of DG set of 750/600 KVA capacity with replacement of oil filter,Diesel filter & related accessories such as set of 'O' ring, set of joint /gasket, Set of Copper washer,Set of Fuel Flexible Pipe,Set of cogged belt, Set of Hoses, Instrument fuse, Battery maintenance, descaling of cooling system by radiwash with two times circulation of radiwash by means of running of engine & cleaning of fan blades, crankcase breather, radiator and its fins by means of high pressure air, or water. Make : Cummins ( excluding the cost of the following spares all as per OEM & specified and directed by Engineer in Charge . Note :- Supply of Spares shall be measured & paid seperatly. |
| 2 | Supply only Element Lub oil filter (cat part No.3238204) complete all as directed. |
| 3 | Supply only Kit fuel filter and Ring. (cat part No.3238493) complete all as directed. |
| 4 | Supply only Kit super by pass filter element (cat part No.3879488) complete all as directed. |
| 5 | Supply only SEAL 'O' Ring (cat part No.3010937) complete all as directed. |
| 6 | Supply only Engine oil, VALVOLINE PREMIUM BLUE 7800 PLUS1/210 Ltr (Cat Part no. 504626) complete all as directed. |
| 7 | Supply only air cleaner element (K, QSK, V series) (Cat part no. 3238665) complete all as directed. |
| 8 | Supply only INHIBITOR CORROSION 1/ 10 Ltrs (cat part No.3167222) complete all as directed. |
| 9 | Supply only STRIP TEST (cat part No.4912590) complete all as directed. |
| 10 | Supply only Gasket Rocker Lever Cover (Cat part No. 4920076) complete all as directed. |
| 11 | Supply only Seal O Ring (Cat part No. 3066914) complete all as directed. |
| 12 | Supply only Seal O Ring (Cat part No. 3042542) complete all as directed. |
| 13 | Supply only Coolant for radiator complete all as directed. |
| 14 | S&F PVC 10sqmm copper lead for Battery Terminal of Best Quality suitable for 12/24V with complete all as directed. |
| 15 | Supply and fixing New AVR VARIABLE SPEED DCDG suitable for DG set with input voltage range 415 Volt AC with neutral & Out put DC voltage suitable for DG set of 750/600 KVA complete all as specified and directed by Engineer -in-charge. |
| 16 | Disconnected and opening of self starter assemlly 12/24 volt for repair from DG set of 750/600 KVA & repair unserveceable part of self starter suitable size as required on site complete all as specified and directed.Note :- Supply of Spares shall be measured & paid seperatly. |
| 17 | Supply only Armature complete all as directed. |
| 18 | Supply only Solenoied switch complete all as directed. |
| 19 | Supply only Bush gear complete all as directed. |
| 20 | Supply only'O' Ring assy complete all as directed. |
| 21 | Supply only Bush set complete all as directed. |
| 22 | Supply only FIELD Coil complete all as directed. |
| 23 | Supply only Sealing kit complete all as directed. |
| 24 | Supply only Brush Set complete all as directed. |
| 25 | Supply only the following items of DG Set of various capacity :- |
| 26 | Battery terminal, lug, bolts type suitable for heavy duty battery complete all as directed. |
| 27 | Battery leads of copper conductor multiwired 70 Sqmm Single Core complete all as directed. |
| 28 | Hinges for DG set door of any size, any type as required on site complete all as directed. |
| 29 | V belt for fan pulley for DG set of 750 KVA DG Set complete all as specified. |
| 30 | Fuel hose pipe from fuel filter to fuel pump for DG set of 750/600 KVA, complete all as specified. |
| 31 | Fuel pipe from fuel tank to fuel filter for DG set of 750/600 KVA, complete all as specified. |
| 32 | Material & labour for carrying out complete servicing of DG set (750/600 KVA) PCC3.3 digital panel(power command), including checking and rewiring faulty electrical circuit using 1.5 sqmm FRLS copper conductor, repairing of PCC3.3 card , making all electric connections and testing for smooth operation, complete all as directed. |
| 33 | Supply & fixing following parts of PCC3.3 digital panel of 750/600 KVA (Make: Cummins) DG Set: |
| 34 | PCC3.3 Control card (cat part No.A054J968) complete all as directed. |
| 35 | Display control (cat part No.0300-6315-02) complete all as directed. |
| 36 | Aux card- (cat part No.A028T766) complete all as directed. |
| 37 | PCB assy Governor Card (cat part No.0327-1507) complete all as directed. |
| 38 | M&L for maintenace/testing of RTCC panel by isolating, disconnecting of input/output , supply cable, detecting of fault, ,u/s component in panel ,cleaning of serviceable parts/ component ,including replacement of worn out auto/manual switches LED indicator, cost of spare parts all as specified and directed by Engr-in-Charge. (repacement of spare parts not to be paid separately . |
| 39 | M&L for maintenace/testing of PLC panel by isolating, disconnecting of input/output , supply cable, detecting of fault, ,u/s component in panel ,cleaning of serviceable parts/ component ,including replacement of worn out auto/manual switches LED indicator, all as specified and directed by Engr-in-Charge. Note: (i) Parts not mentioned in above description will be paid separately as supply only but to be fixed under above items. |
| 40 | Supply only following spares parts for PLC Panel:- |
| 41 | SMPS, input 220 V, output 24 V DC, 10 Amp complete all as directed. |
| 42 | Transformer 415 to 24 volt,25 amp complete all as directed. |
| 43 | Multifunctional meter wit MMI suitable for existing PLC Sytem complete all as directed. |
| 44 | Auxiliary contact suitable for existing PLC Sytem complete all as directed. |
| 45 | Thermal relay suitable for existing PLC Sytem complete all as directed. |
| 46 | M&L for maintenace/testing of VRV panel by isolating, disconnecting of input/output , supply cable, detecting of fault, ,u/s component in panel ,cleaning of serviceable parts/ component ,including replacement of worn out auto/manual switches LED indicator, all as specified and directed by Engr-in-Charge. Note: Parts not mentioned in above description will be paid separately as supply only but to be fixed under above items. |
| 47 | Supply only following spares parts for VRV Panel:- |
| 48 | Transformer 500 VA complete all as directed. |
| 49 | 63 amp TP MPCB, 16 KA complete all as directed. |
| 50 | M&L for maintenace/testing of PAC panel by isolating, disconnecting of input/output , supply cable, detecting of fault, ,u/s component in panel ,cleaning of serviceable parts/ component ,including replacement of worn out auto/manual switches LED indicator, all as specified and directed by Engr-in-Charge. Note: Parts not mentioned in above description will be paid separately as supply only but to be fixed under above items. |
| 51 | Supply only following spares parts for PAC Panel:- |
| 52 | Single phase preventer complete all as directed. |
| 53 | Auxiliary contact 9 amp suitable for existing PLC Sytem complete all as directed. |
| 54 | Capacitor upto 10 KVAR complete all as directed. |
| 55 | Adujustable MPCB upto 20 amp ,10/16 KA complete all as directed. |
| 56 | M&L for maintenace/testing of MDB panel by isolating, disconnecting of input/output , supply cable, detecting of fault, ,u/s component in panel ,cleaning of serviceable parts/ component ,including replacement of worn out auto/manual switches LED indicator, all as specified and directed by Engr-in-Charge. |
| 57 | Supply, laying, jointing and testing XLPE insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5 core X 300 Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed. |
| 58 | Same as item No 22 but size 3.5 core X 150 sqmm |
| 59 | Same as item No 22 but size 3.5 core X 25sqmm |
| 60 | Same as item No 22 but size 4 core X 16 sqmm |
| 61 | Same as item No 22 but size 4 core X 10 sqmm |
| 62 | Supply ,jointing and testing straight through , cold shrinkable joint kit suitable for PVC/XLPE insulated heavy duty armoured with aluminium multi stranded conductor 1100 volt grade of size 16 sq mm 4 core and including taking out from faulty portion in any situation /position complete allas specified and directed. |
| 63 | All as serial item No-27 here in before but of size 25 Sqmm 3.5 core. |
| 64 | All as serial item No-27 here in before but of size 150 Sqmm 3.5 core. |
| 65 | Excavation in trenches not exceeding 1.5 mtr and n.exc 1.5 mtr depth in any of soil complete all as directed. |
| 66 | S & F Bricks Burnt clay fly ash building bricks having compressive strength 75 Kg /Sq cm laid in trenches for cable protection complete all as specified and directed. |
| 67 | S&F sand in trenches including spreading & levelling for cushioning of LT UG cable complete all as specified and directed. |
| 68 | Returning filling in including spreading, levelling watering and well ramming in layers n.exc 25cm thick complete all as directed |
| 69 | Removal of excavated material to a distance n exc 50 mtr and depositing where directed at a level n.exc 1.5m above the starting point. |
| 70 | Arranging fault locating machine to pin point the fault in any size of HT/LT under ground cable in any situation , taking out the fault portion of HT/LT Cable of any length from trench , jointing with cable jointing kit and testing for satisfactory serviceability of the HT/LT cable in trench after jointing . Including excavation and earth work in any type of soil complete all as specified and directed. Cable jointing kit shall be measured sepereatly under respective item of Sch 'A'. Retrived old servicable bricks /cable cover willbe relaid in trenches on the cable complete all as directed. |
| 71 | S & F Frequeny meter flush type 3 phase 415 volts AC including removing old meter complete all as directed.Make: AE/AEE/Enercon. |
| 72 | S & F Volt meter of 0-500 Volt, 415 Volt Ac connecting testing including removing of unserviceable meter.complete all as directed. Make : AE/AEE/ Enercon/ RE |
| 73 | S & F Ammeter 0 -3000 A with CT Coil,415 Volt Ac connecting testing including removing of unserviceable meter complete all as directed. Make : AE/AEE/ Enercon/ RE |
| 74 | Disconnecting the existing unservicable /burnt MCCB from the LT panel /stand by DG set panel & Supply & fixing new MCCB ,3 pole ,630 Amp(DN3-630N),50 KA,415 volt,50 Hz, 3 phase,Ics=100% of Icu with thermal magenatic release,installation of MCCB and connecting with existing cable including nut,bolt and washer etc complete.Make: L&T/Havelles/Standard |
| 75 | All as serial item No 39 here in before but of size 400 Amp(DN3-400 N) 50 KA |
| 76 | All as serial item No 39 here in before but of size 200 Amp, 36 KA |
| 77 | All as serial item No 39 here in before but of size 160 Amp, 25 KA. |
| 78 | All as serial item No 39 here in before but of size 100 Amp,16 kA |
| 79 | All as serial item No 39 here in before but of size 63 Amp, 16 KA . |
| 80 | S & F in replacement of 10 amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following single pole complete with connection testing all as specified and directed by Engr-in-charge. |
| 81 | S & F in replacement 63 amp TP rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles complete with connection testing all as specified and directed by Engr-in-charge. |
| 82 | S & F in replacement 32-40 amp TP rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles complete with connection testing all as specified and directed by Engr-in-charge. |
| 83 | Disconnecting the existing unservicable /burnt ATS from the PAC panel & Supply & fixing new ATS ,400 Amp, 3/4 pole ,415 volt,50 Hz, 3 phase with automatic /manual with inbuilt time delay and connecting with existing cable including nut,bolt and washer etc complete.Make:Socomec/Standard |
| 84 | M&L of 12V, 180AH Battery including replacement of any part to make it serviceable. Any Make battery. |
| 85 | M & L in replacement for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including using galvanised iron strip 32×6mm as earthing strip by means of bolts, nuts, check nuts and washers of galvanized iron or steel, earth plate surrounded by packed layer of char coal dust and common salt, 15cm thick all around bottom and top and watering pipe 20mm bore of GI light grade with funnel, wire mesh and 40 mm dia GI protection pipe medium grade all as shown in electrical plate No 3 of SSR Part-I and connected to earthing test point, main switch board and testing on completion including excavation, earth work concrete pit with 80mm thick RCC cover in RCC 1:2:4 type B-1 duly reinforced with MS bars 8mm dia @ 150C/C both ways and pit chamber in PCC 1:2:4 type B-1 with 2 Nos suitable lifting handles of 12mm MS bar complete all as specified. |
| 86 | Supply and lay in trenches GI strip 25 mm x 4 mm galvanised iron strip for earth continuity earthing all as specified and directed |
| 87 | Material & labour for carrying out complete overhauling / servicing of DG set panel / AMF panel / control panel, including checking and rewiring faulty electrical circuit using 1.5 sqmm FRLS copper conductor, Relay, fuse, timer, for DG Set of any type / make / capacity, making all electric connections and testing for smooth operation, complete all as directed. |
| 88 | S&F in replacement of power contactor 4 pole 200Amp model no MCX-33 of L&T or equivalent size and design complete all as directed. |
| 89 | M&L for drilling hole under hard standing /road in different location as per site requirement (between 03 mtr to 12mtr maximum) for laying of pipe for protection of cable etc by means of mannual bookle and without disturbing the top surface and making good the disturbed surface if any complete as sepecified and directed by Engr-in-Charge. |
| 90 | Supply and laying GI tube medium grade 80 mm bore, ISI marked complete as sepecified and directed by Engr-in-Charge. |
| 91 | Supply and laying GI tube medium grade 40 mm bore, ISI marked complete as sepecified and directed by Engr-in-Charge. |
| 92 | S&F in replacemnt of MCCB with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as directed as per existing model/make of the following sizes:- |
| 93 | (a) 100 Amps 4 Pole breaking capasity 35/36 KA . Make : Havells/L&T/ABB. |
| 94 | (b) 125 Amps 3 Pole breaking capasity 35/36 KA . Make : Havells/L&T/ABB. |
| 95 | (c) 160 Amps 4 Pole breaking capasity 35/36 KA . Make : Havells/L&T/ABB. |
| 96 | (d) 200 Amps 4 Pole breaking capasity 36 KA . Make : Havells/L&T/ABB. |
| 97 | (e) 200 Amps 3 Pole breaking capasity 36 KA . Make : Havells/L&T/ABB. |
| 98 | (f) 250 Amps 4 Pole breaking capasity 36 KA . Make : Havells/L&T/ABB. |
| 99 | (g) 250 Amps 3 Pole breaking capasity 36 KA . Make : Havells/L&T/ABB. |
| 100 | (h) 400 Amps 4 Pole breaking capasity 36 KA . Make : Havells/L&T/ABB. |
| 101 | (j) 400 Amps 3 Pole breaking capasity 36 KA . Make : Havells/L&T/ABB. |
| 102 | (k) 630 Amps 4 Pole breaking capasity 50 KA . Make : Havells/L&T/ABB. |
| 103 | (l) 630 Amps 3 Pole breaking capasity 50 KA . Make : Havells/L&T/ABB. |
| 104 | Supply, fixing and erection in replacemnt of steel tubular swaged pole type 410SP-31(9 Mtr long) Swan neck complete with CI base plate,taper plug,bolts,nuts,and screws etc duly painted internally and externally with metal oxide anti corrosive paint before errection and painting with two coats aluminium paint after erection complete all as cofirming to IS 2713 (part-1 to 111) and complete all as specified and as directed.Note : Necessary earth work and concrete shall be measured and paid separately |
| 105 | M&L for Foundation for Tubular swaged pole type including excavation , getting out, pole foundation with PCC (1:4:8) type D 2 (using with 40 mm graded crushed stone aggregate). Coping of pole with PCC (11:3:6) type C ( using with 20 mm graded stone agregate) and removing surplus soil to a distance n.exc 50 m and making good surface complete all as specified and as directed |
| 106 | S&F in replacement for Changeover switch of capacity 250 Amps , 415 Volts , 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge. |
| 107 | S&F in replacement for Changeover switch of capacity 400 Amps , 415 Volts 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge. |
| 108 | S&F in replacement for Changeover switch of capacity 630 Amps , 415 Volts , 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge. |
| 109 | Supply & fixing in replacement of old unservicable feed pump for fuel injection pump complete assy for capacity 750 KVA of DG set complete all as directed.. |
| 110 | Supply & fixing in replacement, of fuel shutoff valve assy , solenoied valve kit including taking outold valve assy and making all connection, testing for smooth opreation complete of all DG set capacity 750 KVA all as directed. |
| 111 | Material & labour for element Air cleaner,inner for DG set 750 KVA complete all as directed.. |
| 112 | Material & labour for opening / taking out of injector of DG set of any type/make and capacity 750 KVA disconnection and opening of fuel injector assembly, carrying complete overhauling/servicing fuel injection system with including replacement of injector repair kit ,including calibration of injector, checking of pressure complete for each injector and re-assembling the same, fitted with DG set properly in original location, checking the allignment, making proper fuel connection, testing for smooth opreatio complete all as directed. |
| 113 | S&F in replacement of old un/sv lifting magnet of existing make suitable for 750 KVA DG set complete all as directed. |
| 114 | S&F in replacement of unsv thermostat with new thermostat alongwith complete assy for DG set of various capacity , including all connection testing complete all as specified and directed. |
| 115 | Supply and fixing, in replacement of Old unserviceable water temp meter complete all as directed. |
| 116 | Supply and fixing, in replacement of Old unserviceable OIL PRESSURE METER complete all as directed. |
| 117 | Supply and fixing, in replacement of Old unserviceable OIL TEMP METER complete all as directed. |
| 118 | Supply and fixing, in replacement of Old unserviceable H.C.T. SWITCH complete all as directed. |
| 119 | Supply and fixing, in replacement of Old unserviceable LLOP SWITCH complete all as directed. |
| 120 | Repair of door by removing and replacement of damage hinges,acoustic material and providing / fixing of glass wool,tissue paper, MS perforated sheet with painting complete. |
| 121 | Supply and fixing, in replacement, of Automatic Voltage Regulator (AVR) suitable for DG Set of 750 KVA capacity, with and including taking out old AVR and making all connection, testing for smooth operation complete all as directed. |
| 122 | Supply & fixing in replacement of battery charging unit including rectifier unit , voltage regulator,two Nos clamp,,nuts, bolts and suitable length of stranded copper conductor PVC cable 2.5 sq mm 3 run from power point to battery charger and 2 run fro battery charger to battery etc suitable for 12 volt battery charging unit complete all as directed. |
| 123 | Taking out and replacement of unservicable/blocked residential silencers of existing make suitable for 100 to 200 KVA and cutting welding and fixing of pipe complete allas directed. |
| 124 | Labour for attending of any breakdown of standby supply in any location ,whenever required round the clock ,rectify the fault and restore the standby supply within three hour after receipt of complaint of any nature i.e. Engine, alternator,control panel,AMF panel etc . Note -(i) The cost of replaced spare parts will be paid and measured seperatly. (ii) If complaint is not attended by contractor with in three hour the penality of Rs 500 / per hour to be imposed and amount of penality will be deducted from RAR. (iii) The cost of transportation (to and fro) for all kind of necessary equipment / T&P shall be arranged/brought by contractor to complete the job at site or at E/M yard and no extra cost shall be paid to the contractor to this effect. (iv) Complaint shall be lodged by telephonically ,so contractor to specify the telephone no who will receive the complaint round the clock. |
| 125 | M&L for capacity 750 KVA complete descaling of cooling system by radiwash with two times circulation of radiwash by means of running of engine & cleaning of fan blades, crankcase breather, radiator and its fins by means of high pressure air or water complete all as directed. |
| 126 | Supply & filling distilled water in sealed packing suitable for DC 12 volt battery complete all as directed. |
| 127 | Supply & Fixing in repalcement of 630A, Electrically operated Draw-out type ACB 3 pole fixed type with Microprocessor basedSR18G relay with protection aganist over current, earth fault and short circuit, 50KA=Icu=Ics=Icw for protection against common outgoing of change over switch all as specified and directed.. |
| 128 | Supply & Fixing in repalcement of 1250A, Electrically operated Draw-out type ACB 4 pole fixed type with Microprocessor basedSR18G relay with protection aganist over current, earth fault and short circuit, 50KA=Icu=Ics=Icw for protection against common outgoing of change over switch all as specified and directed.. |
| 129 | Supply and fix in replacement LED street light fitting 200 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. This item includes the hydra or any machinery required to replace to light. The light should be such that it should fit in the existing bracket complete all as directed. |
| 130 | M&L for repair of LED street light fitting 45/60/70 Watt 230 V AC outdoor type of any make. Note - This item includes hydra or any machinery required to dismantle and refix and repair to the street light pole. This item also includes all the componenets required to make serviceable and no any extra payment will be paid complete all as directed.. |
| 131 | S&F as in repairs LED street light 90 watt 230 volts pressure die cast aluminium housing, heat resistant toughened glass with frame, IP protection IP-66 batter optics for uniform distribution having surge protection 10 KV, sealed driver .Make : Crompton Cat Part No. TRP-411-90-57-SL-GL-NSG or equivalent make in wipro and Philips .This item includes the hydra or any machinery required to replace to light on pole The light should be such that it should fit in the existing bracket. |
| 132 | S&F as in repairs Junction box (Bus bar chamber box) of size 250 x 200x 105 mm made out palstic suitable for 415 Volt, 4 Way TPN aluminium bus bars of capacity 100 amps with 01 No. MCB, SP, 6 Amp, 240 volts, 10 KA for controlling the street light complete fixing arrangement to the pole with nut, bolts and washers including providing the electrical connection for incoming / outgoing cable through proper lugs/thimbles complete all as directed. |
| 133 | Supply and fix in replacement of MCB SP 6-32 Amps 230 volts 'B' series complete all as specified and as directed. |
| 134 | Supply and fix in replacement of MCB SPN 40-63 Amps 230 volts 'B' series complete all as specified and as directed. |
| 135 | Material and labour for PVC flat twin core 2.5 sq mm aluminium wire 1100 volt grade laid in 20 mm dia medium grade rigid PVC conduit (and fixing brackets on PCC pole) from Loop-in-loop out junction box to light fitting terminal complete all as specified and as directed.Note :- PVC conduit shall be clamped properly with suitable clamps and no extra payment shall be done on this account. |
| 136 | M & L for prepration of old painted steel tubular pole 9 meter height by scraping with steel wire brush and cleaning the rust of pole and cross arm and applying two coat of Aluminium paint over and including a coat of red oxide primer above 1.5 m height and painting red and white strips ( 30 cm width ) with synthetic enemel paint upto 1.5 m height from bottom point, and writing the exhisting pole number with black paint in yellow circle of dia 150 mm , complete all as specified and as directed . |
| 137 | S&F as in repairs GI pipe 40 mm dia, light grade for cable protection fixed along the pole, with suitable size MS Clamps made out of 25x3mm thick flat including nuts bolts and washers complete all as directed by Engineer in charge. |
| 138 | S& F Astronomical timer switch 110/240 volts Cat No SWADEEP -66-12 KW 3p complete all as directed. |
| 139 | S&F as in repairs Aviation light 2 x 10 watt fitting complete LED type double with alternate flashing and dusk automatic control housing cast aluminium base with red diffuse lens , complete all as specified and as directed . |
| 140 | Supply and fix LED post top lamp spherical/Oval shape with polycarbonate diffuser and IP 65 protection 40 W, LED warm white complete all as specified and as directed. Make : Crompton Cat part No-LPTO-40-CDL or equivalent make in wipro and Philips . |
| 141 | Taking down the LT air circuit breakers of various capacities form 630 amps to 1600 amps for repairs, servicing comprising the following and refixing the same, re-orientation and labour for taking down the defective parts and refixing the same spare parts (including spare parts cost ) all as specified and directed (a) Checking/repair of mechanical system of ACB.(b) Checking/repair of the manual closing/tripping of breaker. |
| 142 | Supply & Fixing in repalcement of 630A, 3 Pole 415 V Electrically operated Draw-out type ACB fixed type with Microprocessor based SR18G relay with protection aganist over current, earth fault and short circuit, 50KA=Icu=Ics=Icw for protection against common outgoing of change over switch incuding testing and commissioning all as specified and directed.. |
| 143 | Supply & Fixing in repalcement of 1250A, 4 Pole 415 V Electrically operated Draw-out type ACB fixed type with Microprocessor basedSR18G relay with protection aganist over current, earth fault and short circuit, 50KA=Icu=Ics=Icw for protection against common outgoing of change over switch incuding testing and commissioning all as specified and directed.. |
| 144 | Supply & Fixing repalcement of 1600A, 4 Pole 415 V Electrically operated Draw-out type ACB fixed type with Microprocessor based SR18G relay with protection aganist over current, earth fault and short circuit, 50KA=Icu=Ics=Icw/ for protection against common outgoing of change over switch incuding testing and commissioning all as specified and directed.. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 13 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender