Tender for Construction Of Indoor Swimming Pool At Golf Coruse Sidhra, Jammu (Phase-Ii).
BOQ
| Sl. No. | Item Description |
| 1 | CIVIL WORK |
| 2 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate sections and other sections of approved make conforming to IS:733 and IS:1285, fixed with dash fastener of required dia and size including necessary filling up of gaps at junctions i.e. at top, bottom and sides with required EPDM rubber / Neoprene gasket felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including dash angle, Aluminium angle and beading for glazing / panelling. C.P. brass / stainless steel screws, all complete as per architectural drawings and directions of Engineer-in-Charge. (Glazing, Panelling and Dash Fasteners to be paid for Separately) For fixed portion Powder coated aluminium (minimum thickness of powder coated 50 micron) (12 gauge). |
| 3 | For shutters of Doors, Windows & Ventilators including Providing and Fixing Hinges / Pivot and Making Provision for Fixing of Fittings wherever required including the cost of EPDM rubber / Neoprene Gasket Required (Fitting shall be paid for separately). Powder Coated Aluminium (minimum thickness of powder coated 50 microns). |
| 4 | Providing and fixing of 6mm High Pressure Laminate Jali of (Exterior Grade Compact) of any shade, Excellent Light Fastness Property with 3-Layers of U.V Protection, Fire Retardant, Anti Graffite, Environment Friendly green DNA no U.V/U.VA Contact and also Chemical Resistant and colour fixing with M.S Aluminium Tube structure of any Size as required HPL Jali in this coloured Aluminium Rivet and Shade selected by the Engineer-In-charge at the time of fixing. (Make: Greenlam, Marino, Foundermax etc.) |
| 5 | Providing and fixing glazing in Aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / Neoprene Gasket etc. Complete as per the architectural drawings and the Directions of Engineer-in-Charge. (Cost of aluminium apron beading shall be paid in basic item) with float glass panes of mm thickness Toughened Glass (weight not less than 20.0 kg/sqm). |
| 6 | Steel work welded in built up type framing / tramed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railing, brackets, gates and similar work. |
| 7 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) Trusses etc. including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes. |
| 8 | Providing and fixing factory-manufactured 50mm thick (LENGTH OF 45 FT) PUF insulated Sandwich panels comprising of two outer layers of pre-painted galvanized iron (PPGI) sheet with rigid polyurethane foam (PUF) insulation core, conforming to relevant IS standards, fixed over roof/wall frame work with all necessary accessories complete in all respects. Specification: sheet outer 0.50mm thick pre-painted GI sheet, zinc coating minimum 120 GSM colour coated (as approved) inner sheet 0.40mm thick pre-painted GI sheet, zinc coating minimum 120 GSM, core material Rigid Polyurethane Foam (PUR), density 40 ± 2 kg/m3, CFC-free with thermal conductivity max 0.023 W/mK. Fixing panels shall be fixed on steel structure using self drilling/self tapping screw with EPDM washers, proper side laps and end laps to ensure water tightness, joints sealed with butyl tape / aluminium sealant, including ridge caps, flashing, trims, gutter interface, panels cut to required size at site without damaging coating, complete alignment, levelling and fixing complete. |
| 9 | Providing and fixing pre-coated galvanised steel sheet roofing accessories 0.50 mm (+0.05) total coated thickness, Zinc coating 120 grams per sqm as per IS 277, in 240 mpa steel grade, 5-7 micron epoxy primer on both side of the sheet and polyester top coat 15-18 micron using self drilling / self tapping screws complete. |
| 10 | RIDGES PLAIN (500-600MM) |
| 11 | FLASHINGS/APRONS (UPTO 600MM) |
| 12 | GUTTER (600MM OVER ALL GIRTH) |
| 13 | BARGE BOARD (UPTO 600MM) |
| 14 | Providing and fixing Aluminium Composite Panel (ACP) false ceiling of approved make, colour and shade, comprising 3mm/4mm thick ACP sheets (minimum 0.25mm thick aluminium coating on both sides with LDPE/FR core), fixed over a rigid frame work of aluminium / GI sections. The frame work shall consist of aluminium / GI hollow sections of size 25x25mm or 50x25mm suspended from roofing battens, anchor bolts, ceiling cleats or other approved supports at required spacing, including proper levelling, alignment and grid formation. ACP sheets shall be cut to required sizes and fixed with self-drilling screws / rivets, all joints shall be finished with aluminium trims (U/L sections) and sealed with approved silicone sealant, the item includes cutting openings for light fitting, AC grills, diffusers, access panels and all necessary fixtures, scaffolding up to all heights, complete in all respects as per drawings, specifications and Directions of Engineer-in-Charge. (Make: Alubond, Alstrong etc.). |
| 15 | Providing and fixing of 6mm HIGH PRESSURE LAMINATE sheet of (Exterior Grade Compact) of any shade, Excellent Light Fastness Property with 3-Layers of U.V. Protection, Fire Retardant, Anti Graffite, Environment Friendly green DNA no U.V/UVA Contact and also Chemical Resistant and colour fixing with M.S Aluminium tube structure of any Size as required HPL Sheet size 2000mm x 1000mm fixed with coloured aluminium rivet, one size of piece required 6No rivet and shade selected by the engineer incharge at the time of fixing including all necessary fitting and Tube. (Make: Greenlam, Marino, Foundermax Etc |
| 16 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade on new work (two or more coats) over and including priming coat with water washable cement primer. |
| 17 | Providing and fixing Double Action Hydraulic Floor Spring of Approved Brand and manufacture IS: 6315 marked, having brand logo embossed on the body/plate with double spring mechanism and door weight upto 125 kg for doors including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece MS sheet outer box with slide plate etc. Complete as per direction of Engineer-in-Charge. With stainless steel cover plate minimum 1.25 mm thickness. |
| 18 | Providing and fixing Stainless Steel tubular handle bar 32mm outer dia, 3.0mm thick & 450mm long with SS screw etc., complete as per direction of Engineer-in-Charge. |
| 19 | Providing and fixing Stainless Steel tower bolts 304 grade, with nuts and screws etc. complete: a) 200 × 10 mm |
| 20 | Providing and fixing Stainless Steel sliding door bolts 304 Grade with nuts and screws etc. complete: b) 300 × 16 mm |
| 21 | Surface dressing of the ground including removing vegetation and inequalities not exceeding 15cm deep and disposal of rubbish, lead upto 50m and lift upto 1.5m in all kinds of soil. |
| 22 | Earth work in bulk excavation by mechanical means (hydraulic excavator) over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 m² on plan) including disposal of excavated earth lead upto 50 metres and lift upto 1.5 m, as directed by Engineer-in-Charge in all kinds of soil. |
| 23 | Extra for every additional lift of 1.5 M or part thereof in all kinds of soil. |
| 24 | Extra rates for quantities of works executed in or under water and/or liquid mud, including pumping out water as required. The extra percentage rate is applicable in respect of each item but limited to quantities of work executed in these difficult conditions. The unit, namely metre depth, to be considered for payment shall be the depth measured from the subsoil water level upto the centre of gravity of the quantity executed in difficult conditions. The depth shall be reckoned correct to 0.1 metre; 0.05 metre or more shall be taken as 0.1 metre and less than 0.05 metre ignored. |
| 25 | Supplying & stacking of hard stone (for stone pitching) 22.5cm thick at site. |
| 26 | Dry stone pitching (any thickness) excluding cost of stones. On horizontal surfaces. |
| 27 | Grouting of stone pitching using M-10 nominal mix concrete (max. size of aggregates: 20mm nominal) @ 3.65 cum per 100 sq m on horizontal/side slopes; complete including curing. |
| 28 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering all work upto plinth level in 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate) 40mm nominal size crushed. |
| 29 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering all work upto plinth level in 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). |
| 30 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS:9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-Charge. All works upto plinth level |
| 31 | Extra for providing richer mixes at all floor levels. Note: Excess/less cement over the specified cement content used is payable/recoverable separately. Providing M-30 grade concrete instead of M-25 grade RMC/AMC. (Note: Cement content considered in M-30 is @ 340 kg/cum). |
| 32 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS:9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-Charge. All works above plinth level upto floor V level. |
| 33 | Reinforcement for RCC work including straightening, cutting, bending, placing in position and binding all complete TMT bars (Thermo-Mechanically Treated bars of grade Fe-500D or more). |
| 34 | Centering and shuttering including strutting, propping etc. and removal of form work for: |
| 35 | Foundations, footings, bases for columns |
| 36 | Columns, pillars, piers, abutments, posts and struts. |
| 37 | Lintel, beams, plinth beams, girders, bressumers and cantilevers. |
| 38 | Retaining walls, return walls, walls (any thickness) including attached pilasters buttresses, plinth and string course fillets, kerbs andsteps etc. |
| 39 | Suspended floors, roofs, landings, balconies and access platforms. |
| 40 | Edges of slabs and breaks in floors and walls upto 20cm wide. |
| 41 | 6mm thick cement mortar 1:3 (1 cement : 3 fine sand). |
| 42 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50M & lift upto 1.50M. |
| 43 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry and curing complete, but excluding the cost of nosing of steps etc. complete. 50mm thick with 20mm nominal size stone aggregate. |
| 44 | Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface |
| 45 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacture, over the plastered wall surface to prepare the surface even and smooth complete |
| 46 | Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade. Two or more coats on new work |
| 47 | Disposal of Earth by Mechanical Transport including Loading / Unloading and stacking at site as per the direction of Engineer-in-Charge complete, lead upto 3 Km |
| 48 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 49 | Providing and fixing precoated galvanized iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-Charge) 0.50 mm (+ 0.05%) total coated thickness with zinc coating 120 grams per sqm as per IS:277, in 240 MPa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-Charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5 x 55 mm) with EPDM seal, complete upto any pitch in horizontal/vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 50 | Providing and fixing 15 cm wide 45 cm overall semi circular plain G.I. sheet gutter with iron brackets 40x3 mm size, bolts, nuts and washers etc. including making necessary connections with rain water pipes complete. 0.63 mm thick with zinc coating not less than 275 gram/m². |
| 51 | 40 mm thick fine dressed stone flooring over 20 mm (average) thick base of cement mortar 1:5 (1 cement : 5 coarse sand), including pointing with cement mortar 1:2 (1 cement : 2 stone dust) with an admixture of pigment to match the shade of stone and curing complete. Red sand stone |
| 52 | Spreading of sludge, dump manure or/and good earth in required thickness as per directions of officer-in-charge (cost of sludge, dump manure or/and good earth to be paid separately) |
| 53 | Supplying and stacking of good earth at site including royalty (earth measured in stacks will be reduced by 20% for payment) |
| 54 | Grassing with selection No. 1 grass including watering & maintenance of the lawn for 30 days or more till the grass forms a thick lawn free from weeds & fit for mowing including supplying of good earth if needed (the good earth shall be paid separately) |
| 55 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot, a double action hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, with glass lock all complete as per direction of Engineer-in-Charge |
| 56 | Providing and laying Asbestos bitumen felt sheet of approved quality (Type-2, Grade-1 or as specified) consisting of hessian base impregnated and coated with bitumen, laid over a prepared surface including cleaning, priming with bitumen primer @ 0.3 kg/sqm, and bonding with hot bitumen @ 1.2 kg/sqm. Laying asbestos felt sheet with maximum 100 mm side lap and 150 mm end lap, sealing joints with hot bitumen including all labour, material, heating of bitumen, tools, tackles, scaffolding and complete as per specifications and direction of Engineer-in-Charge |
| 57 | Providing and fixing Frosted window film is a privacy glass film designed to cover your existing windows or doors to give it a ‘frosted glass’ and opaque appearance and good flexibility, easy for cutting. Material are PVC, weight 15 kg and roll type as per the direction of Consultant and Engineer-in-Charge |
| 58 | Providing and fixing of Name plate in stainless steel grade 304 size/dimension 15\\" x 5\\" x wall mounted, thickness of sheet 2 mm, fix with 4 No. cap type SS screws of 2\\" long along with PVC Patti, bolt and chain if required. All words in press steel words with black matt paint. Complete job |
| 59 | Providing and fixing fabric vertical / roller blinds as per design and concept as per direction of Consultant approval |
| 60 | Brick work with common burnt clay (non modular) bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 fine sand). (Below Plinth) |
| 61 | Providing and laying polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent |
| 62 | Providing and fixing SS towel rail (Kerovit Cat No. KA680001 & Cera Cat No. FS002103, Jaguar CAT ACN-1111SM) complete with CP brass screws with concealed fitting arrangement of approved quality and colour: 600 mm towel rail with total length of 645 mm, 78 mm wide and effective height of 88 mm, weighing not less than 190 gms. (MAKE: Kerovit, Essel, CERA, Hindware) |
| 63 | Earth work in excavation by mechanical means (hydraulic excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed |
| 64 | Earth work in excavation by mechanical means (hydraulic excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed 152.99 CUM 256.85 39,294.92 57 RCC M25 Providing and laying in position specified grade of reinforced cement concrete including curing but excluding the cost of centering, shuttering and reinforcement. All works upto plinth level |
| 65 | Reinforced cement concrete work in walls (any thickness) including attached pilasters, buttresses, plinth and string courses, finlets, columns, pillars, piers, abutments, posts and struts upto floor five level including curing but excluding cost of centering shuttering, finishing and reinforcement. |
| 66 | Reinforced cement concrete work in beams, suspended floors, roofs having slope upto 15°, landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases upto five level including curing but excluding the cost of centering shuttering, finishing and reinforcement with 1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size). |
| 67 | Steel work welded in built-up sections/framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required in gratings, frames, guard bar, ladders, railings, brackets, gates and similar work. |
| 68 | 50 mm thick with 20mm nominal size stone aggregate. Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry and curing complete, but excluding the cost of nosing of steps etc. complete. |
| 69 | 12mm cement plaster of mix 1:6 (1 cement : 6 fine sand). |
| 70 | Carriage of material by M.T including loading unloading and stacking at site complete |
| 71 | Sand for an av. Lead 15.00 Km |
| 72 | Stone aggregate Below 40mm size avg. Lead of 15.00 Kms |
| 73 | Stone aggregate Above 40mm size avg. Leade of 15.00 Kms |
| 74 | Bricks for an avg. Lead of 25.00 Kms |
| 75 | MECHANICAL |
| 76 | Supply Installation, Testing & Commissioning of Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll/Twin Rotary Compressor(s), microprocessor based Controller, Minimum 2 Compressors above 14HP Module, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 43°C ambient temperature during Cooling and -10°C during Heating . The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 . |
| 77 | 20 H.P |
| 78 | Supply,installation,testing and commissioning of following minimum capacity VRV/VRF Hi wall Indoor unit equipped with synthetic washable media pre-filter,fan section with low noise fan/dynamically balanced blower,multispeed motor,coils ection with DX Copper coil,electronic expansion valve,outer cabinet,drain pump,grill,necessary supports,vibration isolation,cordless remote controletc.,suitable for perationon single phase230V±10%,50HzAC supply,complete,as required.The Equipment Design Shall be Compatible to Maintain Desired inside Temp. of 22.5 Deg C(+/- 2 Deg C) during Summer and Winter Season. |
| 79 | 2.0 Tr |
| 80 | Supply, Installation, testing and commissioning of Factory built floor/ceiling mounted/suspended DX-type double skin type horizontal/vertical Dedicated Outdoor Air System air handling units of following capacity, made of 50mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and inside layer of 0.8 mm thick plain GI sheet material of 275 GSM with density of 42 Kg/m3 Polyurethane Foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend PVC eliminators, separate coil section with aluminum finned copper tubes (tubes thickness not less than 0.3mm) cooling /Heating coil of 6 row deep, provision of thyristor controlled heater/dehumidifiers in separate sections with a capacity of 6kW, filter section with 50mm thick washable synthetic type air prefilters, complete with mixing chambers with fresh air & return air dampers, direct drive package with Totally Enclosed Fan Cooled (TEFC) drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed & compatible with Variable Frequency Drive (VFD) applications, drain connections, stainless steel (20G) drain pan in PUF insulation casing, necessary vibration Isolation arrangement, noise level shall not exceed 65 dBA at 1 Mtrs. distance. |
| 81 | TFA AHU fan should be spark proof with filter face velocity not less than 2.54 m/s. AHU blower shall be SISW direct driven plug fans with aero foil curved blades construction. Impeller made of high performing composite material with external rotor motor balanced together statically and dynamically according to relevant standard. The fan make should be Rosenberg / ZIEHL-ABEGG / VTS / Greenheck. (External Static Pressure considered is max. 25 - 30 mm WC). Units shall have factory fitted Volume Control Damper at supply side. Unit shall be Eurovent Certified having Classes thermal transmittance – T2, thermal bridging – TB2 & casing leakage - L1. DOAS AHU should be compatible with BMS. Computerized Selection of AHU is required for approval from Engineer-in-Charge. (Starter / Electrical Panel along with necessary power wiring and earthing for the DOAS System shall be included in above prices and the Price shall also include the cost of AHU Kit for integration between AHU and Out Door Units ) |
| 82 | 5000 CFM |
| 83 | Remote ControllerInstallation, testing and commissioning of corded remote controller suitable for indoor units and suitable to work on single phase 230 volt (+)(-) 10% 50 Hz AC supply. |
| 84 | Refrigerant Joints/ HeadersInstallation, testing and commissioning of imported Y-joints fittings and header to all indoor units at all floors including alignments of joints complete as required. |
| 85 | REFRIGERANT PIPINGSupply, Installation, Testing and Commissioning of Interconnecting refrigerant pipe work with (19mm /13mm thick) closed cell elastomeric nitride rubber tubular insulation between each set of indoor & outdoor units as per specifications including cacumization,Nitrogen Testing,Leakage testing and Pressure Testing, all piping inside the room shall be properly supported/ fixed with suitable size of clamps / MS hanger and all external / exposed to Sun piping shall run in M.S. painted cable tray with cover at site. |
| 86 | 41.3 mm outer dia (insulation 19mm) |
| 87 | 28.6mm outer dia (insulation 19mm) |
| 88 | 19.1mm outer dia (insulation 13mm) |
| 89 | 15.9mm outer dia (insulation 13mm) |
| 90 | 9.5mm outer dia (insulation 13mm) |
| 91 | Supplying and installing following size of perforated HotDipped Galvanised Iron cable tray (Galvanisation thickness notless than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended fromthe ceiling with G.I. suspenders including G.I. bolts & nuts, etc.as required. |
| 92 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 93 | DRAIN PIPINGProviding and fixing rigid CPVC piping complete with fittings, supports as per specifications and duly insulated with 6mm thick closed cell nitrile rubber insulation. |
| 94 | 25mm dia |
| 95 | 32 mm dia |
| 96 | Control Transmission Wiring |
| 97 | Providing & fixing control wiring of 2 core x 1.5sqmm copper in PVC conduit pipe of 25mm dia including providing & fixing support @1.5mt distance CIC where it is not recessed between indoor units and out door units |
| 98 | supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT panel Board Suitable for 415 V 3 phase 4 wire 50 HZ AC supply System including incommers, Out Goings , Bus Bars etc.. As required as per the Following.Descripton (IP:55) HVAC Panel-1. The Sucessful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A drawing , wiring diagrams,single line diagram before start of fabrication of LT panel . Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder shall be CPRI/ERDA/ANY NABL ACCREDITED LAB approved. Refer SLD |
| 99 | INCOMER |
| 100 | MCCB 160 A F.P 36 Ka Adj. TMR with Extendable ROH Icu=Ics=100% |
| 101 | Timer |
| 102 | Single Phase Preventer |
| 103 | MCX Contactor F.P 200 A ,415 V,AC-23 Duty |
| 104 | SPD Typ.1 +2 Imax 50 Ka |
| 105 | 200 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 106 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc. |
| 107 | OUTGOING |
| 108 | MCB 63 A F.P 10 Ka \\"C\\" Curve Size of wiring for CTS=2.5 sqmm Size of wiring for voltage sensing Metering:- 4.0 Sq. mm Size of wiring of all push buttons, indicating lamps:- 1.5 Sq.mm Types of wires:- PVC insulated 1100V grade ,Multostrand copper Conductor Flexible FR-LSH Hinged Door Earthing :- Device mounted hinged Doors connected to cubicles body by means of 2.5 sqmm green copper flexible wire . The Complete panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc. Gland Plates to be 3.0 mm Thick. |
| 109 | supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT panel Board Suitable for 415 V 3 phase 4 wire 50 HZ AC supply System including incommers, Out Goings , Bus Bars etc.. As required as per the Following.Descripton (IP:55) HVAC Panel-2. The Sucessful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A drawing , wiring diagrams,single line diagram before start of fabrication of LT panel . Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder shall be CPRI/ERDA/ANY NABL ACCREDITED LAB approved. Refer SLD |
| 110 | INCOMER |
| 111 | MCCB 160 A F.P 36 Ka Adj. TMR with Extendable ROH Icu=Ics=100% |
| 112 | Timer |
| 113 | Single Phase Preventer |
| 114 | MCX Contactor F.P 200 A ,415 V,AC-23 Duty |
| 115 | SPD Typ.1 +2 Imax 50 Ka |
| 116 | 200 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 117 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc. |
| 118 | OUTGOING |
| 119 | MCB 63 A F.P 10 Ka \\"C\\" Curve Size of wiring for CTS=2.5 sqmm Size of wiring for voltage sensing Metering:- 4.0 Sq. mm Size of wiring of all push buttons, indicating lamps:- 1.5 Sq.mm Types of wires:- PVC insulated 1100V grade ,Multostrand copper Conductor Flexible FR-LSH Hinged Door Earthing :- Device mounted hinged Doors connected to cubicles body by means of 2.5 sqmm green copper flexible wire . The Complete panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc.Gland Plates to be 3.0 mm Thick. |
| 120 | supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT panel Board Suitable for 415 V 3 phase 4 wire 50 HZ AC supply System including incommers, Out Goings , Bus Bars etc.. As required as per the Following.Descripton (IP:55) AHU Panel-1. The Sucessful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A drawing , wiring diagrams,single line diagram before start of fabrication of LT panel . Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder shall be CPRI/ERDA/ANY NABL ACCREDITED LAB approved. Refer SLD |
| 121 | INCOMER |
| 122 | MCCB 160 A F.P 36 Ka Adj. TMR with Extendable ROH Icu=Ics=100% |
| 123 | 200 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 124 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc. |
| 125 | OUTGOING |
| 126 | MCCB 63 A F.P 36 Ka Adj. TMR with Extendable ROH Icu=Ics=100% Size of wiring for CTS=2.5 sqmm Size of wiring for voltage sensing Metering:- 4.0 Sq. mm Size of wiring of all push buttons, indicating lamps:- 1.5 Sq.mm Types of wires:- PVC insulated 1100V grade ,Multostrand copper Conductor Flexible FR-LSH Hinged Door Earthing :- Device mounted hinged Doors connected to cubicles body by means of 2.5 sqmm green copper flexible wire . The Complete panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc. Gland Plates to be 3.0 mm Thick. |
| 127 | supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT panel Board Suitable for 415 V 3 phase 4 wire 50 HZ AC supply System including incommers, Out Goings , Bus Bars etc.. As required as per the Following.Descripton (IP:55) AHU Panel-2. The Sucessful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A drawing , wiring diagrams,single line diagram before start of fabrication of LT panel . Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder shall be CPRI/ERDA/ANY NABL ACCREDITED LAB approved. Refer SLD |
| 128 | INCOMER |
| 129 | MCCB 160 A F.P 36 Ka Adj. TMR with Extendable ROH Icu=Ics=100% |
| 130 | 200 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 131 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc. |
| 132 | OUTGOING |
| 133 | MCCB 63 A F.P 36 Ka Adj. TMR with Extendable ROH Icu=Ics=100% Size of wiring for CTS=2.5 sqmm Size of wiring for voltage sensing Metering:- 4.0 Sq. mm Size of wiring of all push buttons, indicating lamps:- 1.5 Sq.mm Types of wires:- PVC insulated 1100V grade ,Multostrand copper Conductor Flexible FR-LSH Hinged Door Earthing :- Device mounted hinged Doors connected to cubicles body by means of 2.5 sqmm green copper flexible wire . The Complete panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc. Gland Plates to be 3.0 mm Thick. |
| 134 | Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required. |
| 135 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 136 | Duct Works |
| 137 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheetthickness complete as required. |
| 138 | Thickness 0.8 mm sheet |
| 139 | Thickness 0.63 mm sheet |
| 140 | Supplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (Class \\"O\\") insulation on existing ductafter applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation completeas per specifications and as required. |
| 141 | 25 mm |
| 142 | Supplying & fixing of powder coated extruded aluminium Return Air Grills/Diffuser with louvers but without volume control dampers complete as required. |
| 143 | Supplying, fixing testing commissioning of Supply air diffusers/Grill of powder coated aluminium without volume control dampers . |
| 144 | Supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:55) ( Main LT Panel Board ) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.Refer SLD . |
| 145 | INCOMER |
| 146 | ACB 800 Amps 4 P EDO Type with Breaking Capacity 50 KA with Microprocessor Release(Icu=Ics=Icw=100%) |
| 147 | 1000 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 148 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set ,including interlocking etc to make the |
| 149 | Controller for D.G Set for On/Off Command. |
| 150 | OUTGOINGS |
| 151 | Adj. TMR Based MCCB 250 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 152 | Adj. TMR Based MCCB 160 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 153 | Adj. TMR Based MCCB 63 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 154 | Adj. TMR Based MCCB 40 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH Load Bearing Members to be made out of 2.0 mm CRCA Sheet. Partitions to be made out of 1.6 mm CRCA Sheet Gland Plates to be 3.0 mm Thick. |
| 155 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket,bend, couplers etc. conforming to IS 14930, Part IIcomplete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sandcushioning and protective covering etc., complete as required. |
| 156 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 157 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 158 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in groundin Existing DWC Pipe including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 159 | 3.5 C X 300 Sq.mm A2XFY |
| 160 | 3.5 C X 95 Sq.mm A2XFY |
| 161 | 4.0 C X 16 Sq.mm A2XFY |
| 162 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPEaluminium conductor cable of 1.1 KV grade as required. |
| 163 | 3½ X 300 sq. mm (70mm) |
| 164 | 3½ X 95 sq. mm (45mm) |
| 165 | 4 X 16 sq. mm (28mm) |
| 166 | Supplying and installing following size of perforated HotDipped Galvanised Iron cable tray (Galvanisation thickness notless than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended fromthe ceiling with G.I. suspenders including G.I. bolts & nuts, etc.as required. |
| 167 | 450 mm width X 50 mm depth X 1.6 mm thickness |
| 168 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 169 | Design, Supply, installation, testing and commissioning of a 500 KVA Servo Controlled Automatic Voltage Stabilizer, 3 phase, oil cooled (transformer oil to be the cooling medium conforming to IS-335 with latest amendments) conforming to IS-8447-1989, IS-9815 I & II of 1994 amended up to date. The voltage stabilizer should be suitable to operate on unbalanced input voltage of 250-460 volts and delivering output voltage of 415 + 1% volts, 3 phase, 50 + 3% cycles/second frequency of A.C power supply. The stabilizer shall be copper wound Out door Type. I) The voltage stabilizer shall be suitable for the following configurations:- a) Input Voltage: 250-460 Voltsb) Output Voltage: 415 + 1%c) Frequency: 50 Hz + 3% A.C supply d) Output current: 180.00 amps per phase e) Duty: continuous 24x7 f)Temp. Rise in Oil:-50 degree C f)Temp. Rise in Oil:-50 degree C g) Temp. Rise in Winding:-55 degree C h)Overload Capacity:100% for 1 minute i)Regulator: Rolling Contact Type j) Type: Unbalanced Type –Suitable for unbalanced inputvoltage and unbalanced load, Outdoor g) Design and Testing Standards:IS:9815/IS 2026 k) The no-load current shall not be more than 5% of the rated output current. II) Instrument Accessories: The voltage stabilizer shall be provided with as under:- a) Mains ON indicating lamps for each phase. b) Indicating lamps in each phase with lights up/ audio alarm when the input voltage exceeds beyond limit or overload or phase failure/phase reversal. c) Voltmeter at input & output with voltage selector switch to read input/output voltage in each phase. d) Switch to change over from automatic to manual operation. e) Auto/manual switch raise/lower push button in each phase. f) Ampere meter with selector switch. g) Control circuit separate in each phase. h) Protection against high & low voltage, single phasing, cut off alarm, its cancellation, short circuiting, overload protection and earth fault relay. i) By Pass Arrangements:- By pass switch shall be provided to by pass the stabilizer in case of any fault. j) Heavy terminal blocks and solid state controlled circuit for input, output and earth connections, which should be clearly marked. k) Protections: Suitable capacity MCCB for tripping the stabilizer in case of under voltage, over voltage, short circuit, overload, single phasing conditions. l) Efficiency at full load more than 95%. The stabilizer should be conforming to IS 9815/1981. |
| 170 | m) Purity of copper shall be minimum 99.97% (Certificate from manufacturer shall be attached along with the Invoice).n) The stabilizer should have aesthetic outlook with screen printed panel.Make of Instrument Accessories: G.E./ L&T / Siemens / Schneider / Havells/other reputed make conforming to relevant ISI code). III) Characteristic features:- The three phase Servo Controlled Automatic Voltage Stabilizer shall have the following characteristic features:- a) Continuous duty performance at ambient temperature 2 °C to 55° C. b) Stable and effective system power factor and frequency fluctuation as well as overload up to 15% and under load up to 50% of the connected load. c) Low internal impedance. d) Negligible wave form distortion during starting, under operation and stopping conditions. e) Accommodate the effect of higher starting current and should be able to recover from the shock. f) No overshooting or hunting. g) Negligible phase shift ensuring no change in system power factor. h) Should ensure fast correction of voltage according to voltage variation specified. i) The stabilizer shall have a suitable breather with leak-proof desludging and drain cock for transformer oil, lifting hook for mechanical handling, guage for oil level etc. j) The three phase unbalanced automatic servo controlled voltage stabilizer should take care of the unbalanced supply with A.C step synchronous motor. |
| 171 | IV) Markings:- The stabilizer shall be marked with manufacture’s name and trade mark on the plate fitted on the stabilizer and indicate KVA rating, range of input and output voltage, rated output current, frequency, number of phases, type of load viz unbalanced input and balanced load, quantity of transformer oil and also reference to I.S. standard. In addition, the information relevant to Servo-Motor viz Rated KW, Rated Voltage, Type of Supply and No. of Phases etc. shall also be given on the rating plate. V) Testing & Inspection:- The equipment shall be inspected and tested before dispatch to the consignee by the third party. The firm shall have adequate testing facilities available at their work site. The scope of inspection shall include testing of stabilizer as per type of test prescribed in IS-9815 of 1994 and 8447 of 1989 as relevant to Servo Controlled Voltage Stabilizers. It shall also include testing of voltage stabilizer for all protections. The testing of the stabilizer shall comprise of the following tests:- a) Insulation resistance test. b) High Voltage test. c) Under voltage test. d) Provision of earthling. e) Leakage current test. f) No load current test. g) Measurement of no load losses. h) Load loss test and efficiency. i) Induced voltage test. j) Test for continuous operation. k) Temperature rise test at lowest voltage of 260 volts. k) Temperature rise test at lowest voltage of 260 volts. l) Test for rate of correction. m) Locked rotor test for servo motor. n) Full load test. VI) Layout of Components/Drawings:- Layout of Components and control wiring shall conform to established engineering practice from the consideration of case for maintenance. VII) The job involves shifting of stabilizer to site by way of lifting, carriage and unloading manually or with mechanical crane and installation of the stabilizer, providing and laying of insulation mats etc. Complete job in all respects. |
| 172 | FLEXIBLE CONNECTION : Supply, Fabricating installing and testing of 150mm long silicon based flexible connection constructed of the resistant material. The silicon shall have backing of glass fibre Quantity is mentioned considering perimeter length |
| 173 | HEAT PUMP |
| 174 | Providing ,Supplying , installation,and commisioning of Heat Pump with 1.High Power Output & EfficiencyOutput Power: Up to 52 KW heating capacity at Air 24°C/ Water 26°C. Input Power: Only 9.8 KW at max output COP: Up to 5.3 at standard conditions. This means for every 1 unit of electricity, you get 5.3 units of heat. Even in cold conditions 7°C air, it still delivers 33 KW output with COP 4.3. 2.Dual Heating & Cooling CapabilityWater Cooling Capacity: 41.6 KW. Water Temperature Range: 10°C~ 45°CSuitable for both pool heating in winter and cooling in summer. 3. Premium ComponentsCompressor: High-efficiency Copeland/Panasonic Scroll Compressor for reliability and low noise. Heat Exchanger: Titanium Tube Heat Exchanger - 100% corrosion resistant. Ideal for chlorinated pool water and sea water applications. Refrigerant: R410A - Eco-friendly and high performance. Defrost Function: Included for stable operation in low ambient temperatures . 4.Durable BuildCabinet: Made of Galvanized steel sheet with sprayed baking paint for weather resistance. Electric Power: 380V / 50Hz/ 3PH - Industrial 3-phase power. Noise Level: Only 58 dB(A) - relatively quiet for a 52K W unit. 5. Installation FriendlyWater Flow Rate: 25-30 m'/h. Water Connection: Exterior 60mm / Interior 50mm. Remote Control: Comes with 5 meters signal wire. Dimensions: 1580x910 x 1180mm | Weight: 280 Kg Net / 310 Kg Gross. 1.Massive Energy SavingsWith COP up to 5.3, it uses ~80% less electricity than traditional electric heaters. For a 52K W output, you only consume 9.8KW input. 2.All-Weather PerformanceWorks efficiently from 7°C to 24°C ambient. The auto-defrost ensures uninterrupted operation in winter. 3.Corrosion Proof for Pools The titanium heat exchanger makes it perfect for swimming pools, as it won't get damaged by chlorine, salt, or chemicals. 4.Eco-Friendly & Low Running CostUses R410A refrigerant and transfers heat from air instead of generating it. Cuts carbon footprint and electricity bills. 5.Commercial Grade ReliabilityBranded Copeland/Panasonic compressor + ISO certified build + galvanized cabinet = long life with minimal maintenance. 6.Quiet & CompactAt 58dB it's quieter than a normal conversation. Compact footprint makes it easy to install in hotels, gyms, and residential complexes. |
| 175 | Providing ,Supplying , installation,and commisioning of Electrical panel The proposed electrical panel shall consist of the following:-Main Incomer: 250 Ampere MCCB-Bus Bar: Rated for 300 Amperes.-Outgoing Cireuits: Five 63 Ampere, 4-Pole MCBs-Control Components: Five 50 Ampere Contactors and Five Timer Controllers.Metering: One VAF MeterEnclosure Dimensions: Approximately 1200mm Height x 1100mm Width x 250mm Depth Technical Specification: --Main Incomer: 250A MCCB -Bus Bar Rating: 300AOutgoing Feeders: 5 Nos. x 63A MCB TPNContactors: 5 Nos. x 50ATimer-Controller: 5 Nos.-VAF Meter: 1 Nos.-Approximate Enclosure Size: 1200mm(H)x 1100mm (W) x 250mm (D) Pool Cover Size Actual size 14x25 Meters Chargeable (14x25 m.) Pool covers triple bubble patented technology chargeable Pool Cover *Imported High quality * Material High quality LLDPE*Colour one side dark blue *Thickness-600 micron*Save water and slows down evaporation *Prevent heat loss*Saves chemical loss Pool cover roller :-Swimming pool cover reels.these are made from stainless steel (SS304) and help in easy handling and storage of the cover. The reels are available in mannual models |
| 176 | Providing ,Supplying , installation,and commisioning of Pool cover size 14x25 Metre chargeable (14x25m) pool covers triple bubble patented technology chargeable pool cover .Imported High Quality, Material- High quality LLDPE, colour- one side dark blue, Thickness-600 micron, Saves water and slows down evaporation, Prevents Heat loss, saves Chemical loss. |
| 177 | Pool Cover Roller:- Swimming pool cover reels, these are made from Stainless Steel (SS304) and help in easy handeling and storage of the covers. The reels are available in manual models. |
| 178 | ELECTRICAL WORK |
| 179 | Sub Head-I(Wiring) Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulatedcopper conductor single core cable etc. as required. |
| 180 | Group A |
| 181 | Wiring for Light /Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in surface/Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required. |
| 182 | Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/ Recessed medium class PVC conduit as required. |
| 183 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 184 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 185 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 186 | Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch,connection,painting etc. as required. |
| 187 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. |
| 188 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper busbar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 189 | 12 way , Double door |
| 190 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/ RCCB/ Isolator) |
| 191 | 8 way (4 + 24), Double door |
| 192 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 193 | Single Pole |
| 194 | Single pole and neutral |
| 195 | Supplying and fixing following rating, Four pole, 415 V, 10 Ka M.C.B in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 196 | 40 A F.P MCB 10 Ka \\"C\\" Curve |
| 197 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 198 | Supply,Installation,Testing and Commissioning of Single Phase 600 mm ,1440 RPM Wall Fan with Plastic Blades and the Cage made out of Metal. |
| 199 | 600 MM |
| 200 | LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per therequirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) |
| 201 | 36 watt |
| 202 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz,Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5,Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70,under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the roadand the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 203 | 120 watt |
| 204 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 205 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 206 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 207 | 2.2 KVA Sine Wave Inverter , Input 1 Phase 3 wire and output 1 phase 3 wire with 2 Nos of 12 V 200 aH Battery. |
| 208 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 209 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 210 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 211 | Supplying,Installation,Testing and Commissioning of Copper Earthing Electrode of Size 50 x 3000mm with Copper Pipe Outer Dia. 50 mm (+-) 5 %),Length 3000 mm,Inner & and Outer Strip Size 25X6mm (Copper),Terminal Hole Two Nos.,Terminal Hole Dia. 14 mm,Seal Plate Thickness 4 mm,Base Plate Thickness 4 mm,Inner filling Material – Highly Conductive Super Crystalline Mixture,Outer filling material - Highly Hygroscopic, Non corrosive Back Fill Compound 50 Kgs. |
| 212 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I.pipe from earth electrode including connection with brass nut,bolt, spring, washer excavation and re-filling etc. as required. |
| 213 | Supply, installation, Testing & Commissioning of 'Silent Type DieselGenerating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings: |
| 214 | (A) Diesel Engine:Turbocharged Diesel engine 4 stroke water cooled, multi cylinder,dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPMsuitable for above output of alternator at 40 Degree C, 50% RH & at 1000Meter MSL , capable of taking 10% over loading for one hour after 12 hours ofcontinuous operation. The engine will be with Electronic governor, Dry typeAir filter with service indicator, first filling of engine fuel (after commissioning)lubricating Oil, Coolant and other consumables complete with all therequired accessories, the Electronic governor shall be as per ISO 8528.Theengine shall comply to the latest CPCB norms (CPCB IV + or better) andConforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as perCPWD specifications. |
| 215 | (B) Engine mounted Instrument Panel fitted with and having digital displayfor following:(i) Start-stop switch with key(ii) Water temperature indication(iii) Lubrication oil pressure indication(iv) Lubrication oil temperature indication(v) Battery charging indication and Voltage indication(vi) RPM indication(vii) Over speed indication(viii) Low lubricantion Oil trip indication(ix) Engine Running Hours indication(x) Fuel Level |
| 216 | (C) Alternator:Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50%RH & at 1000 Meter MSL. The alternator shall be having Screen ProtectedDrip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamicallybalanced rotor, capable of taking 10% over loading for one hour after 12hours of continuous operation, self cooled,self-excited and self-regulatedthrough AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable fortropical conditions and with class- H insulation. |
| 217 | (D) Base Frame & Foundation:Both the engine and alternator shall be mounted on suitable base framemade of MS channel with necessary reinforcement which shall be installedon suitable cement concrete foundation and vibration isolation arrangementas per recommendations of manufacturer. |
| 218 | (E) FUEL TANK:Daily service fuel tank of suitable liters capacity as per CPWD Specifications,fabricated out of 3 mm thick M.S. sheet complete with all standardaccessories and fuel piping between fuel tank and diesel engine with MSclass 'C' pipes of suitable dia. Complete with valves, level indications &accessories as required as per specifications. |
| 219 | (F) Exhaust System:Dry exhaust manifold with hospital type exhaust silencer and catalyticconvertor. |
| 220 | (G) Starting System:12V/24V DC starting system comprising of starter motors: voltageregulator and arrangement for initial excitation complete with suitablenumbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosureof DG Set. |
| 221 | (H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications. |
| 222 | 4. 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering 5. Energy analyser unit to indicate current, Voltage( L-N & L-L), kW, kVA (Phase & Total), Frequency, KWH, PF.6. LED Indicating lamps for load on mains and load on set.7. Fuse/ MCB for instruments. 8. Battery charger, complete with transformer/ rectifier, D.C. voltmeterand ammeter, selector switch for trickle, off and boost and currentadjustment. 9. Main supply failure monitor.10. Supply failure timer. 11. Restoration timer12. Control unit with three impulse automatic engine start/stop and failure to start lockout. 13. Impulse counter with locking and reset facility. 14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for (i) High water temperature(ii) Low lubricating oil pressure (iii) Engine over speed(iv) Engine fails to start (v) Full load/maximum load warning16. Protection for over/under Frequency, Loss of AC sensing, OverCurrent, Unbalancing load with suitable number of relays andaccessories 17. Maintenance notification based on Engine Run Hour & due date. 18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel , interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware andsoftware required to perform the operation shall be provided by thecontractor including all control wiring. |
| 223 | 500 KVA |
| 224 | Supply,installation with foundation as per approved Drawing 11 Mtr SP-56 M.S Pole |
| 225 | Supply,installation of Structural Steel as per Standard Approved Drawing |
| 226 | Supply,Installation and Commissioning of 11 KV Air Break Switch(200 Amps). |
| 227 | Supply,Installation of 11 KV L.A 10 ka (Station Class). |
| 228 | Supply,Installation of 11 KV HG Fuse Unit . |
| 229 | Supply,Installation of Disc Insulator(B&S)70 KN suitable for 100 sq.mm Triple AAAC. |
| 230 | Supply and Installation of 100 Sq.mm AAAC Triple AAAC. |
| 231 | Supply,Installation of 11 KV Pin Insulator suitable for 100 sq.mm Triple AAAC. |
| 232 | Supply and Erection of 150 mm Dia. Heavy Class G.I Pipe for the Cable Protection. |
| 233 | Supply and Installation of Anti Climbing Device |
| 234 | Supply,Installation and Commissioning of 11 KV Meter with suitable size Out door Type combined C.T and P.T's of 30/1A Accuracy Class 0.5 S Burden 100 VA 11 KV/Root3/110 V /Root3 |
| 235 | Supply, installation, testing and commissioning of following capacity (continuous loading) BEE 3 Starrated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer(Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Coregrade MOH or better, suitable for out door/indoor applications with Offload Tap Changer/ On Load TapChanger (OLTC) ( below 500 KVA offload and above 500 KVA On Load Tap Changer) on HV side havingAVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automaticoperation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x300 sq.mm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 and as per CPWD specifications complete in all respects etc as required at site. The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with + 12.5 percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 35 0C for oil and 40 0C up to 200 KVA and 40 0C for oil and 45 0C for above 200 KVA for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. Design ambient condition : a) air temperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible, as per IS: 1180 Part-3. The entries on the rating plate shall be indelibly marked. Fitting and Accessories : The following fittings shall be provided:- |
| 236 | a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal size thread) with cover (for sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent above 200 kVA; k) One filter valve on the upper side of the tank (for transformers above 200 kVA); l) Unidirectional flat rollers (for transformers above 200 kVA); m) Inspection hole (for transformers above 200 kVA); n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); o) Buchholz relay for transformers above 800 kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oil temperature indicator and winding temperature indicators for transformers above 200 kVA with suitable tripping mechanism above permissible limit s) Jacking pads (for transformer above 1 600 kVA); t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge (for transformer above 1600 kVA) with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug for all transformers of capacity 50 KVA and above. bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. |
| 237 | 500 KVA |
| 238 | Supply, Installation testing and commissioning of indoor type termination kit for 3 C x 35 mm² 11 KV XLPE insulated Aluminum. conductor PVC outer sheathed armoured HT Cable with Earth (A2XFY with Earth HT Cable).(Raychem make) |
| 239 | Supply, Installation testing and commissioning of outdoor type termination kit for 3 C x 35 mm² 11 KV XLPE insulated Aluminum. conductor PVC outer sheathed armoured HT Cable with Earth (A2XFY with Earth HT Cable).(Raychem make) |
| 240 | POWER AND CONTROL CABLES :- |
| 241 | Supplying and Laying of XLPE Insulated and PVC Sheathed Power Cable of 11KV/ 1.1 KV Grade of the following size direct in Ground including excavation,sand Cushioning,Protective Covering and Refilling the Trench as Required. |
| 242 | 3 C x35 mm² 11 KV XLPE insulated Aluminum. conductor PVC outer sheathed armoured HT Cable with Earth (A2XFY with Earth HT Cable). |
| 243 | Supplying,Installation,Testing and Commissioning of Copper Earthing Electrode of Size 50 x 3000mm with Copper Pipe Outer Dia. 50 mm (+-) 5 %),Length 3000 mm,Inner & and Outer Strip Size 25X6mm (Copper),Terminal Hole Two Nos.,Terminal Hole Dia. 14 mm,Seal Plate Thickness 4 mm,Base Plate Thickness 4 mm,Inner filling Material – Highly Conductive Super Crystalline Mixture,Outer filling material - Highly Hygroscopic, Non corrosive Back Fill Compound 50 Kgs. |
| 244 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 245 | Supplying,Installation,Testing and Commissioning of G.I Earthing Electrode of Size 50 x 3000mm with GI Pipe Outer Dia. 58 mm (+-) 5 %,Length 3000 mm,Inner & Outer GI Strip Size 32X6mm,Terminal Hole Two Nos.,Terminal Hole Dia. 14 mm,Seal Plate Thickness 4 mm,Base Plate Thickness 4 mm,Inner filling Material – Highly Conductive Super Crystalline Mixture,Outer filling material - Highly Hygroscopic, Non corrosive Back Fill Compound 50 Kgs. |
| 246 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 18, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 09, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysOct 10, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender