Tender For Provision Of Cook House With Dining Hall And Allied Works For Tabn Pattan Under Ge 969 Ews
Tender Value
4.95 Crore
Estimated cost
Bid Submission
22 Oct 2026
19 days left
EMD
5.70 Lakhs
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Baramulla → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of Cook House With Dining Hall And Allied Works For Tabn Pattan Under Ge 969 Ews
BOQ
| Sl. No. | Item Description |
| 1 | Note: (i) Please refer Schedule 'A' Notes given in tender documents.(ii) The Schedule 'A' Part-XV is not estimated by MES and the estimated rate indicated as \\"Rs. 0.00\\" under Col. 5 signifies this fact only. |
| 2 | LUMPSUM/ OTHER PRE-PRICED PROVISIONAL SCHEDULES OF WORKS |
| 3 | Lump sum price worked out by the contractor for BUILDING WORKS carried forward from Pre-Priced Schedule 'A' Part-I. |
| 4 | Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY WORKS carried forward from Pre-Priced Schedule 'A' Part-II. |
| 5 | Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION WORKS carried forward from Pre-Priced Schedule 'A' Part-III. |
| 6 | Lump sum price worked out by the contractor for SEWAGE DISPOSAL WORKS carried forward from Pre-Priced Schedule 'A' Part-IV. |
| 7 | Lump sum price worked out by the contractor for AREA DRAINAGE WORKS carried forward from Pre-Priced Schedule 'A' Part-V. |
| 8 | Lump sum price worked out by the contractor for PROTECTIVE WORKS carried forward from Pre-Priced Schedule 'A' Part-VI. |
| 9 | Lump sum price worked out by the contractor for ROAD, PATH AND CULVERT WORKS carried forward from Pre-Priced Schedule 'A' Part-VII. |
| 10 | Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY WORKS carried forward from Pre-Priced Schedule 'A' Part-VIII. |
| 11 | Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATION WORKS carried forward from Pre-Priced Schedule 'A' Part-IX. |
| 12 | Lump sum price worked out by the contractor for HOT WATER SUPPLY WORKS carried forward from Pre-Priced Schedule 'A' Part-X. |
| 13 | Lump sum price worked out by the contractor for CENTRAL HEATING SYSTEM WORKS carried forward from Pre-Priced Schedule 'A' Part-XI. |
| 14 | Lump sum price worked out by the contractor for REFRIGERATION AND AC WORKS carried forward from Pre-Priced Schedule 'A' Part-XII. |
| 15 | Lump sum price worked out by the contractor for SITE CLEARANCE & EARTHWORKS carried forward from Pre-Priced Schedule 'A' Part-XIII. |
| 16 | MISCELLANEOUS ITEMS OF WORKS (SCHEDULE 'A' PART-XIV)(A) INTERNAL WATER SUPPLY WORKS |
| 17 | S&F of two way bib cock with wall flange quarter turn (Low-flow) 16 mm dia. (flow rate - 8 LPM), ISI Marked, complete all as specified and directed. |
| 18 | S&F Pillar Cock (Low-flow) 16 mm dia. (flow rate - 8 LPM) Chromium plated, ISI Marked complete all as specified and directed. |
| 19 | Supply & fixing of Health faucet (ABS Body) (Low-flow) mild steel chromium plated suitable for 15 mm dia pipe with 1.25 metre long flexible tube and ABS wall hook (flow Rate - 10 LPM) ISI Marked, complete in all respect as specified. |
| 20 | S & F of Angular Stop Cock 15 mm bore of pipe (16 mm outer dia) with Wall Flange chromium plated Stop valves, ISI Marked, complete all as specified and directed. |
| 21 | S &F of 15 mm bore PUSH Cock ( Low-flow) for urinal for iron pipe and fixed.( PRS-CHR-073) (flow rate -3.8 LPF), ISI Marked, complete all as specified and directed. |
| 22 | S & F of Wall Mixer with Provision For Overhead Shower with 115mm Long Bend Pipe On Upper Side, Connecting Legs & Wall Flanges, ISI Marked, complete all as specified and directed. |
| 23 | (B) INTERNAL ELECTRIFICATION WORKS |
| 24 | S & F of modular type 1 module RJ-11 telephone scoket with shutter complete all as specified and directed. |
| 25 | S & F of modular type 1 module co-axial type TV socket, complete all as specified and directed. |
| 26 | Supply and fixing load line distribution board TPN vertical, 4 way double door type, fixed on wall semi flush with suitable for incoming MCCB 4 poles and, busbars , neutral link, blanking plates complete with all accessories complete all as specified and as directed.Note: Outgoing MCCB and MCBs shall be measured and paid separately. |
| 27 | Supply and fixing load line distribution board TPN vertical, 6 way double door type, fixed on wall semi flush with suitable for incoming MCCB 4 poles and, busbars , neutral link, blanking plates complete with all accessories all as specified and as directed.Note: Outgoing MCCB and MCBs shall be measured and paid separately. |
| 28 | Supply and fixing LED light fitting 20 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size. complete all as specified and directed. |
| 29 | Supply and fixing of 12W Surface down light fitting with 220 V AC and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 30 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type PDB-1 (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-chargeMake: Schneider, Siemens, ABBThe PANEL shall comprise of the following: |
| 31 | [A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 100A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection[B] INCOMING[i]80A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set[C] OUTGOING[i]40A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 04 Nos[ii]20A,230 V, Ics = 100% Icu = 10 kA, 50 Hz 2P MCB, conforming to IEC 60947-2, having trip unit, front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos[iii]10A, 230 V, Ics = 100% Icu = 10 kA, 50 Hz 2P MCB, conforming to IEC 60947-2, having trip unit, front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos [iv] LED phase indicators (Red, Yellow, Blue)- 07 Set |
| 32 | (C) EXTERNAL ELECTRIFICATION WORKS |
| 33 | Supply and fix street light junction box mistral IP 65 thermoplastic enclousers with transperent door 4mm thick in 4 modulus in single row of size 210 x 155 x 92 with SP 0.5 Amp MCB and including clamp of size 20x3 mm thick of flate iron with bolt, nut etc required in mounting in steel toolbar pole 8.5 mtr long complete all as specified and directed. |
| 34 | Supply and fixing of providing cement concrete type B1 (1;2;4) (20 mm graded aggregate)in precast posts for cable route indicator of size 500x300x100 mm rounded top as directed and grouting in ground with PCC (1:3;6) block of size 350mmx150mmx200mm including 10 mm thick plastering all around of exposed surfaces of post above ground with CM (1:4) and applying two coats cement base paint on plastered surface and writing with synthetic enamel paint in black colour in suitable size like HT Cable, complete all as specified and directed by Engr-in-Charge complete all as specified and directed. |
| 35 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type MLTP PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge.Make: Schneider, Siemens, ABB The PANEL shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 200A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection[B] INCOMING[i]160A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos. |
| 36 | [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set[C] OUTGOING[i]125A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos ( 1 NOS - DG PANEL , 1 NOS SPARE)[ii]80A, 415 V, Ics = 100% Icu = 25kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos ( 1 NOS - PDB 1(BUILDING)[iii]40A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos ( 1 NOS - APFCR PANEL + 1 NOS-SPARE)[iv]20A, 230 V, Ics = 100% Icu = 10 kA, 50 Hz 2P MCB, conforming to IEC 60947-2, having trip unit, front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos ( 1 NOS - PDB 2 (CHS BUILDING)+ 1 NOS-SPARE)[V] LED phase indicators (Red, Yellow, Blue)- 07 Set |
| 37 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type DG PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. Make: Schneider, Siemens, ABBThe PANEL shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 200A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection |
| 38 | [B] INCOMING[i]125A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set[C] OUTGOING[i] 100A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos (1-CHS PANEL , 1 NOS SPARE)[ii]40A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos (1 NOS- ACDB)[ii] 20A, 415 V, Ics = 100% Icu = 10 kA, 50 Hz 4P MCB, conforming to IEC 60947-2, having trip unit, front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos (FOR STREET LIGHT)[III] LED phase indicators (Red, Yellow, Blue)- 04 Set |
| 39 | Supply, installation, testing and commissioning of free-standing indoor, modular, extendable, 25 kVAr APFC Panel having maintenance friendly semi compartmentalized bolted construction, made out of 1.6 mm thick CRCA sheet and built upon rigid framework, having MPP- HD box type capacitor with 7% aluminium wound reactor units type tested in accordance with fully type tested at an Independent laboratory and conforming to IEC 61439-1&2 and IEC 61921 or IS 16636: 2017 with contactor switching, IP 4X protection and including air system provided by axial flow fan or centrifugal fan, control wiring with FR-LSH copper wires complete as specified and directed by the engineer-in-charge.The APFC Capacitor Bank shall comprise of the following: |
| 40 | [i] 40 A, 415 V, Ics = 100% Icu = Icw (1 sec for total selectivity) = 16 kA, 50 Hz electrical draw-out type 4P MCCB, conforming to IS/IEC 60947-2 & 3, having 100% neutral with inbuilt release protection, no derating up to 50 ⁰C, thermal based trip & LED based display systems with thermal memory providing overload, short-circuit, instantaneous & earth-fault protection, zone selective interlocking, pre-trip alarm & individual fault indicating LEDs, 20 trip record, % loading, bar graph, max. & min. meter and pre-alarm function for overload, short-circuit & earth fault - 01 Nos.[ii] High performance microprocessor based APFC relay with 3 CT sensing auto / manual switch option- 01 Nos.[iv] MPP-HD box capacitor of 25 (2 X 10 + 1 X 5 ) kVAr - 3 steps Please Enable Macros to View BoQ information |
| 41 | [i] 40 A, 415 V, Ics = 100% Icu = Icw (1 sec for total selectivity) = 16 kA, 50 Hz electrical draw-out type 4P MCCB, conforming to IS/IEC 60947-2 & 3, having 100% neutral with inbuilt release protection, no derating up to 50 ⁰C, thermal based trip & LED based display systems with thermal memory providing overload, short-circuit, instantaneous & earth-fault protection, zone selective interlocking, pre-trip alarm & individual fault indicating LEDs, 20 trip record, % loading, bar graph, max. & min. meter and pre-alarm function for overload, short-circuit & earth fault - 01 Nos.[ii] High performance microprocessor based APFC relay with 3 CT sensing auto / manual switch option- 01 Nos.[iv] MPP-HD box capacitor of 25 (2 X 10 + 1 X 5 ) kVAr - 3 steps Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 18, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 22, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysOct 24, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender