Tender For Repair/Maintenance Of Internal Electrification Including Wiring, Lightning Fixtures, And Attending Day To Day Complaints At Asl, Mes Qtrs, Pcda & Newly Taken Over Buildings From Cce R&D Area Under Ge (I) R&D Kanchanbagh, Hyderabad.
Tender Overview
Project Description
Tender for Repair/Maintenance Of Internal Electrification Including Wiring, Lightning Fixtures, And Attending Day To Day Complaints At Asl, Mes Qtrs, Pcda & Newly Taken Over Buildings From Cce R&D Area Under Ge (I) R&D Kanchanbagh, Hyderabad.
BOQ
| Sl. No. | Item Description |
| 1 | Supplying and fixing in replacement LED light fitting 2x16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size. |
| 2 | Supplying and fixing in replacement post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. |
| 3 | Supplying and fixing in replacement LED security light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. |
| 4 | Supplying and fixing in replacement LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. |
| 5 | All as per item no 4 above, but of rating 70 watt all as specified and directed by Engr-in-Charge. |
| 6 | S&F in replacement of LED tube 20Watt, 6500K CCT,proffesional luminaries with luminous efficiency not less than 120Lm/watt, Single side connection with < 10% THD incluidng taking down of exisitng fixture all as specified and directed. |
| 7 | S&F in replacment indoor industrial type surface/wall mounted LED integral batten 20W (4 feet), 6500K CCT, aluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete removing unserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. . |
| 8 | S&F in replacment indoor industrial type surface/wall mounted LED integral batten 10W (2 feet), 6500K CCT, aluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete removing unserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed.. |
| 9 | S&F in replacment indoor industrial type recess mounted LED Surface mounted for POP/Grid ceiling round/square downlight with white powder coated polycarbonate housing and pressure die-cast heat sink having high efficiency.15W, 6500K CCT, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable as required at site with suitable size complete removing unserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 10 | Supply & Fix in replacement recess mounted LED luminaire 36W 2'x2' , 5700K CCT, luminous efficacy of not less than 120lm/watt designed for metric false ceiling type or alongwith frame suitable for Grid/POP ceiling or similar mounting system with concealed or exposed 'T' sections, Glare free light alongwith electronic driver complete with all accessories prewired and connecting up with three core twister flexible copper conductor cable with suitable size including making good to the disturbed portion of ceiling complete removing unserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 11 | S&F in replacement recess mounted LED high bay light with IP-66 protection pressure die cast body with high power SMD LEDs as light source of luminous efficacy 150lm/watt 120W, 240V, 5000K CCT, aluminium heat sink alongwith inbuilt elctronic driver, wide beam angle , including hanging the fitting with required hook arrangement required at site, complete removing unserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 12 | Taking down ceiling fan/exhaust fan/ wall mounted fan / Air circulator fan of any sweep for servicing / repairing / maintenance, opening up, identifying and replacing the defective parts, cleaning, greasing,etc, reassembling and hanging up/fixing back at its original position, connecting up and testing complete all as directed.Note : 1. Cost of spares such as capacitors, bearings, Shaft etc will be measured and paid for separately under respective Item of sch A as supply only. |
| 13 | Supply only capacitor of 2.5 mfd for ceiling fan/exhaust fan. Make: Epcos/Havells/Tibcon or its equivalent |
| 14 | Supply only capacitor of 4 mfd for air circulator/exhaust fan. Make: Epcos/Havells/ Tibcon or its equivalent |
| 15 | Supply only bearing No.6201/6202/6203/6204 or any other No matching to the existing size and suitable for ceiling fan/exhaust fan/wall mounted fan. Make: SKF/TATA/ARB or its equivalent |
| 16 | Supply only carbon steel shaft as suitable for ceiling fan/Exhuast fan/ Pedestal Fan/ Air Circulator fans matching to the existing size. |
| 17 | Disconnecting electric connection and taking down carefully fan of any type and size/sweep as described below, removing the burnt winding of fan motor and cleaning the stator completely removing the burnt sludges from the slots and rewinding with super enameled copper winding wire of suitable gauge or of matching size to the existing wires with same turns ratio including all insulating material such as insulation paper sleeve, tape, varnishing etc and reassembling, testing, transporting back to site and refixing to original position all as directed by Engineer-in-charge. |
| 18 | Celling fan of size 1200/1400mm sweep. |
| 19 | Air circulator fans size 600 mm sweep wall mounting Oscillating type |
| 20 | Wall mounted/Pedstal fans size 350/450 mm sweep Oscillating. |
| 21 | Exhaust fan of 300/350/450 mm sweep. |
| 22 | Material and Labour for sub main wiring with 2 runs of 2.5 Sqmm single core PVC insulated unsheathed FRLS copper cable 1100 Volts grade multistranded drawn through non metallic rigid PVC conduit ISI marked 25 mm dia including conduit accessories concealed/surface type on walls, roof, floors etc including one run of 2.5 Sqmm PVC copper conductor as earth continuity wire including taking down unserviceable sub main wiring including conduit all as specified and directed. Note : 2 Runs of 2.5 sqmm cable 1 run of 2.5 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. |
| 23 | All as per srl item No. 18 here-in-before but with 2 runs 4 sqmm including 1 run of 4 sqmm PVC copper conductor FRLS cable as earth continuity wire in not less than 25mm dia ISI marked PVC conduit..Note : 2 Runs of 4 sqmm cable 1 run of 4 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. |
| 24 | All as per srl item No. 18 here-in-before but with 2 runs 6 sqmm including 1 run of 6 sqmm PVC copper conductor FRLS cable as earth continuity wire in not less than 25mm dia PVC conduit.Note : 2 Runs of 6 sqmm cable 1 run of 6 sqmm cable and 1 run of PVC conduit shall measured as one unit for the purpose of payment. |
| 25 | All as per srl item No. 18 here-in-before, but sub main wiring with 4 runs of 4sqmm with 2 run of 4 sqmm copper conductor FRLS as earth continuity wire in not less than 25mm dia PVC conduit.Note : 4 Runs of 4 sqmm cable 2 run of 4 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. |
| 26 | All as per srl item No. 18 here-in-before, but sub main wiring with 4 runs of 6 sqmm with 2 run of 6 sqmm copper conductor FRLS as earth continuity wire in not less than 25mm dia PVC conduit.Note : 4 Runs of 6 sqmm cable 2 run of 6 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. |
| 27 | All as per srl item No. 18 here-in-before, but sub main wiring with 4 runs of 10 sqmm with 2 run of 10 sqmm copper conductor FRLS as earth continuity wire in not less than 25mm dia PVC conduit.Note : 4 Runs of 10 sqmm cable 2 run of 10 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. For Copper wire : Finolex/Nicco/Havells/Gloster/KEI or its equivalentFor PVC conduit : Sudhakar/Polyplast/Supreme/GM or its equivalentMake of Gang Boxes: GM/Havells/Legrand or its equivalent |
| 28 | Taking down old unserviceable point wiring (Light, Fan, Socket or power) complete including fixture and fittings such as switches, ceiling roses, regulators, sockets, light fittings etc and making good to the disturbed surfaces of walls,ceilings and floor etc complete all as directed |
| 29 | Material and labour for point wiring complete with ISI marked 1.5 Sqmm PVC insulated multistranded single core cable with copper conductor (FRLS) 1100 volts grade drawn through and including PVC rigid conduit 20 mm or higher dia ISI marked as required at site including conduit accessories such as Junction Boxes, Inspection Covers etc, concealed/surface type on stone/brick masonry walls, roofs, floors etc by means of saddles and clamps etc including PVC gang boxes as required at site for concealed/surface conduit wiring and modular plates & covers as required at site for housing switches sockets, regulators etc. including providing of 1.5 Sqmm PVC insulated multistranded unsheathed FRLS copper conductor as earth continuity conductor and connecting to common earth dolly all as specified for and connecting up complete for the following:-One light/ fan point controlled by one, one way switch |
| 30 | One light point controlled by one, two way switch |
| 31 | One 5 Amps socket point on independent board. |
| 32 | One 5 Amps socket point on same board with other switches |
| 33 | All as per item No. 8 here-in-before but wiring with 2.5 Sqmm FRLS for 15 Amps switch socket combination on independent board/two pin earth plug and socket including providing 4 Sqmm PVC insulated multi stranded FRLS copper earth continuity conductor and connected to common earth dolly. |
| 34 | S&F in replacement for Modular socket 6A 2/3 Pin 2 module. |
| 35 | S&F in replacement for Modular socket 16A 2/3 Pin 2 Module. |
| 36 | S&F in replacement for modular switch 1 way 6A 1 module. |
| 37 | S&F in replacement for modular switch 1 way 16A 1 module. |
| 38 | S&F in replacement of modular fan regulator 120W,240V, 1 module, suitable for ceiling fan of 1200/1400mm sweep. |
| 39 | S&F in replacement of modular fan regulator 120W,240V, 2 module, suitable for ceiling fan of 1200/1400mm sweep. |
| 40 | S&F in replacement of piano type fan regulator 120W,240V, 1 module, suitable for ceiling fan of 1200/1400mm sweep. |
| 41 | S&F in replacement of piano type fan regulator 120W,240V, 2 module, suitable for ceiling fan of 1200/1400mm sweep. |
| 42 | S&F in replacement for modular switch 2 way 6A 1 module. |
| 43 | S & F in replacement of switch piano flush type 5 Amps SP one way all as specified. |
| 44 | S & F in replacement of switch piano flush type 15 Amps SP one way all as specified. |
| 45 | S & F in replacement of socket & switch combination 5 Amps flush mounted 3/5 pin multi purpose all as specified. |
| 46 | S & F in replacement of socket & switch combination 5/15 Amps flush mounted 3/5 pin multi purpose all as specified. |
| 47 | S&F in replacement for ceiling rose, 3 terminals /PVC/Polycarbonate, isolated body.Make for item no 9 to 22:- Anchor/GM/Cona or its equivalent |
| 48 | M&L for earthing complete with galvanised steel earth plate electrode 600x600x6.3mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0 mm dia of minimum 15m length by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 in SSR PART-I connected to earthing test point all as specified or indicated including provision of earthing lead protection pipe, PCC earth pit with cover, excavation & earth work, testing on completion etc all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
| 49 | M&L for earthing complete with galvanised steel earth plate electrode 600x600x6.3mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0 mm dia of minimum 15m length by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 in SSR PART-I connected to earthing test point all as specified or indicated including provision of earthing lead protection pipe, PCC earth pit with cover, excavation & earth work, testing on completion etc all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender