Educational and Research Institute Government Departments Closing in 1 days TDR #57562844

Tender For Shifting And Reinstallation Of Lt Panels From Low-Lying Areas Including Rerouting Of Lt Cables In The Academic Area At Iit Delhi.

Issued by Government Departments · Delhi, Delhi
Tender Value
12.35 Lakhs
Estimated cost
Bid Submission
01 Oct 2026
1 days left
EMD
24718
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Shifting And Reinstallation Of Lt Panels From Low-Lying Areas Including Rerouting Of Lt Cables In The Academic Area At Iit Delhi.

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 24-Sep-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 01-Oct-2026

BOQ

Name of Work:- Shifting and Reinstallation of LT Panels from Low-Lying Areas Including Rerouting of LT Cables in the Academic Area at IIT Delhi.
Sl. No. Item Description
1Dismantling, shifting, fixing, and reinstallation of existing LT panels of the following sizes from the basement to the ground floor, including loading, unloading, transportation, positioning, alignment, fixing with suitable fasteners, grouting with cement concrete at the new location, reconnection of all incoming and outgoing cables, earthing connections, testing, commissioning, and all other allied works required for satisfactory completion of the work as per direction of Engineer in charge.
2Panel Size:- Height:69 inch ,Width: 38 inch, Depth: 17 inch; having one number Outgoing of 3.5 Core X 70 sqmm, one number Outgoing of 3.5 Core X 95 sqmm, one number Outgoing of 3.5 Core X 35 sqmm, four number Outgoing of 3.5 Core X 50 sqmm, one number incoming cable: 3.5 Core X 240 sqmm
3Panel Size:- Height:69 inch ,Width: 39 inch, Depth: 17 inch; having four number Outgoing of 3.5 Core X 35 sqmm, one number incoming cable: 3.5 Core X 95 sqmm
4Panel Size:- Height:85 inch ,Width: 39 inch, Depth: 17 inch; having three number Outgoing of 3.5 Core X 185 sqmm, one number outgoing of 3.5 Core X 240 sqmm, two number outgoing of 3.5 Core X 95sqmm, one number outgoing of 3.5 Core X 150 sqmm, two number incoming cable: 3.5 Core X 400 sqmm
5Panel Size:- Height:65.5 inch ,Width: 52.5 inch, Depth: 17.5 inch; having three number Outgoing of 3.5 Core X 35sqmm, two number incoming of 3.5 Core X 185 sqmm, four number incoming of 95 sqmm number, outgoing of 3.5 Core X 95sqmm, having one number Outgoing of 3.5 Core X 50 sqmm
6Panel Size:- Height:72 inch ,Width: 39.5 inch, Depth: 14 inch; having two number Outgoing of 3.5 Core X 50 sqmm, two number outgoing of 3.5 Core X 95 sqmm, one number outgoing of 3.5 Core X 35 sqmm, one number outgoing of 4 Core X 25 sqmm, one number outgoing of 4 Core X 16 sqmm,one number incoming of 3.5 Core X 120 sqmm
7Dismantling, shifting, fixing, and reinstallation of existing LT panels of the{size:Height:63inch ,Width: 59 inch, Depth: 24 inch}; having four number Outgoing of 3.5 Core X 50 sqmm, incoming cable: 3.5 Core X 185 sqmm height extension, including loading, unloading, transportation, positioning, alignment, fixing with suitable fasteners, grouting with cement concrete at the new location, reconnection of all incoming and outgoing cables, earthing connections, testing, commissioning, and all other allied works required for satisfactory completion of the work as per direction of Engineer in charge.
8Dismantling, shifting, fixing, and reinstallation of existing 12 way Vertical DB, including positioning, alignment, fixing with suitable fasteners at the new location, reconnection of all incoming cables & outgoing wires, connectors required for extension joint of wires, earthing connections, testing, commissioning, and all other allied works required for satisfactory completion of the work as per direction of Engineer in charge.
9Dismantling of existing cables of various sizes (3.5 Core X 50/70/95/120/150/185/225/240/300/ 400) sqmm, rearranging / rerouting them as required, and reconnecting the cables in accordance with the shifting of the LT panels to the new location, including all necessary dressing and commissioning for proper operation.
10Dismantling, shifting, fixing, and reinstallation of existing Havells ATS 400A from the basement to the ground floor, including opening nut bolts of cables, glands ,GI, loading, unloading, transportation, positioning, alignment, fixing with suitable fasteners, grouting with cement concrete at the new location, reconnection of all incoming and outgoing cables, earthing connections, testing, commissioning, and all other allied works required for satisfactory completion of the work as per direction of Engineer in charge.
11Dismantling, shifting, fixing, and reinstallation of existing FN switch 250A from existing location to new location alignment, fixing with suitable fasteners, reconnection of all incoming and outgoing cables, earthing connections, testing, commissioning, and all other allied works required for satisfactory completion of the work as per direction of Engineer in charge.
12Dismantling, shifting, fixing, and reinstallation of existing 125A MCCB in Enclosure from existing location to new location alignment, fixing with suitable fasteners, reconnection of all incoming and outgoing cables, earthing connections, testing, commissioning, and all other allied works required for satisfactory completion of the work as per direction of Engineer in charge.
13Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying/extraction of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer -in -Incharge.
15Nominal Concrete 1:3:6 or richer mix
16Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
174X16 sq.mm
184X25 sq.mm
193.5X 35 sq.mm
203.5X 50 sq.mm
213.5X 70 sq.mm
223.5X 95 sq.mm
233.5X 150 sq.mm
243.5X 185 sq.mm
25Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
264X16 sq.mm (28mm)
274X25 sq.mm (28mm)
283.5X 35 sq.mm (32mm)
293.5X 50 sq.mm (35mm)
303.5X 70 sq.mm (38mm)
313.5X 95 sq.mm (45mm)
323.5X 120 sq.mm (45mm)
333.5X 150 sq.mm (50mm)
343.5X 185 sq.mm (57mm)
353.5X 240 sq.mm (62mm)
363.5X 400 sq.mm (82mm)
37Supplying & Installation following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I suspenders including G.I bolts & nuts etc as required.
38450 mm width X 62.5 mm depth X 2.0 mm thickness
39300mm width X 50mm depth X 1.6mm thickness
40Supplying, laying and fixing of following size PVC insulated and PVC sheathed XLPE aluminium conductor armoured power cable of 1.1 KV grade on wall surface clamped with saddle conforming to I.S-1554/1/8 as required.
413.5 Core X 50 sqmm
423.5 Core X 150 sqmm
433.5 Core X 70 sqmm
443.5 Core X 95 sqmm
453.5 Core X 35 sqmm
464 Core X 25 sqmm
47Supplying and Laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium armoured power cable of 1.1 KV grade of following size direct on cable tray as required.
483.5 Core X 240 sqmm
493.5 Core X 185 sqmm
50Supplying, Installation, Testing and Commissioning of stand made by MS L shaped heavy Angle frame of 50mm X 50mm X 6mm thick of weight 4.5 kg per meter , stand of dimensions 1490mm Length X 430mm Width and height 700mm with support and fixing LT panels of the{size:Height:63inch ,Width: 59 inch, Depth: 24 inch}; having four number Outgoing of 3.5 Core X 50 sqmm, incoming cable: 3.5 Core X 185 sqmm, including loading, unloading, transportation, positioning, alignment, fixing with suitable fasteners, grouting with cement concrete at the new location, reconnection of all incoming and outgoing cables, earthing connections, testing, commissioning, and all other allied works required for satisfactory completion of the work as per direction of Engineer in charge.
51Demolising RCC work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material within 50metres lead as per direction of Engineer in Charge.
52Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
53Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
54Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
55Supplying, installing, testing and commissioning (SITC) of sheet steel enclosure of 2.0 mm thickness, dimensions : 400mm width,900 mm height,121 mm depth suitable for accommodating one 400 A, four-pole MCCB, including drilling/cutting of panel, fixing the enclosure with suitable fastners, gland plate modifications, ferrules, lugs, nuts, bolts, washers, earthing connections, and all other accessories required for complete installation, testing and commissioning, as required at site.
56Installing, testing and commissioning of existing 125 A TP MCCB in existing cubicle panel board including drilling/cutting of panel, fixing modifications, ferrules, lugs, nuts, bolts, washers, earthing connections, and all other accessories as required at site.
57Supplying, Installation, Testing & Commissioning of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.
58400 A,50KA,FPMCCB
59250 A,50KA,FPMCCB
60125 A,36KA,FPMCCB Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57562844
AUTHORITY Government Departments
TENDER VALUE 12.35 Lakhs
LAST DATE 01-10-2026
Authority
Authority Name Indian Institute Of Technology
Work Description Tender for Shifting And Reinstallation Of Lt Panels From Low-Lying Areas Including Rerouting Of Lt Cables In The Academic Area At Iit Delhi.
Basic Detail
Tender No IITD/WORKS (SP-5402)/2026
Bidding Type Tender
Location
City Delhi
State Delhi
Key Dates
Publish Date 24 Sep 2026
Submission Date 01 Oct 2026
Open Date 02 Oct 2026
Finance
Tender Value 12.35 Lakhs
Tender Fee Ref. Documents
EMD 24718
Exemption Not Available
Document List
76d95b42-24d9-4cde-a770-dd54800a9ebc.html
BOQ_973692.xls
Tendernotice_1 (10).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 24, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 01, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 1 day
Oct 01, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 1 day
Oct 02, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 2 days

Tender Documents

Download All (ZIP) ↓
html

76d95b42-24d9-4cde-a770-dd54800a9ebc.html

xls

BOQ_973692.xls

pdf

Tendernotice_1 (10).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender