Tender For Repair/Maint Of Lt Cable Mccb, Lt Panel With Connected Items Of External Lt Electric Supply At Ms-10 To Ms-13 Umder Ge Gangtok
Tender Overview
Project Description
Tender for Repair/Maint Of Lt Cable Mccb, Lt Panel With Connected Items Of External Lt Electric Supply At Ms-10 To Ms-13 Umder Ge Gangtok
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 29-Sep-2026 | Date Corrigendum | Date | 12-Oct-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exceeding 1.5 M in wide and not exc. 1.5 M in depth for taking out or laying of under ground cable in soft / loose soil complete all as specified and as directed. |
| 2 | Returning, filling in including spreading, levelling, watering and well ramming in layers, not exceeding 25 cm thick in soil complete all as specified and as directed. |
| 3 | Removing surplus soil to a distance not exceeding 50 M and deposited at a level not exceeding 1.5 M above the starting point complete all as specified and as directed. |
| 4 | M&L for PCC 1:2:4 type C–2 (using 20 mm crushed graded stone aggregate/as in foundation for stay and necessary form work for rough finished surface complete all as specified and as directed. |
| 5 | M&L for 50mm dia bore galvanised iron light grade for cable protection and sealing both ends including taking out old pipe complete all as specified and as directed. |
| 6 | M&L for 80mm dia bore galvanised iron light grade for cable protection and sealing both ends including taking out old pipe complete all as specified and as directed. |
| 7 | Supply, laying, testing and commissioning in trenches or fixing on wall or passing through pipe or in cable ducts XLPE insulated PVC FRLS, screened , PVC bedded and PVC tape sheathed galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 Sqmm 2 core including cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 8 | All as per Item No 7.00 here in above but 10 Sqmm 4 core. |
| 9 | All as per Item No 7.00 here in above but 16 Sqmm 2 core. |
| 10 | All as per Item No 7.00 here in above but 16 Sqmm 4 core. |
| 11 | All as per Item No 7.00 here in above but 25 Sqmm 3.5 core. |
| 12 | All as per Item No 7.00 here in above but 35 Sqmm 3.5 core. |
| 13 | All as per Item No 7.00 here in above but 50 Sqmm 3.5 core. |
| 14 | All as per Item No 7.00 here in above but 70 Sqmm 3.5 core. |
| 15 | All as per Item No 7.00 here in above but 95 Sqmm 3.5 core. |
| 16 | S&F in repairs MCCB of 50Hz, 415 V adjustable type including necessary cable lugs & wire etc. of size 63 Amps, 4 pole & 16 KA thermal magetic based complete all as specified and as directed. |
| 17 | All as per Item No 16.00 here in above but 100 Amps, 4 pole & 16 KA. |
| 18 | All as per Item No 16.00 here in above but 160 Amps, 4 pole & 25 KA. |
| 19 | All as per Item No 16.00 here in above but 200 Amps, 4 pole & 25 KA. |
| 20 | All as per Item No 16.00 here in above but 250 Amps, 4 pole & 36 KA. |
| 21 | All as per Item No 16.00 here in above but 400 Amps, 4 pole & 36 KA Please Enable Macros to View BoQ information |
| 22 | All as per Item No 16.00 here in above but 400 Amps, 4 pole & 36 KA Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 9 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 12 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender