Tender For Providing Of Lt Distribution Network To Otm Accn At Rms Chail Under Ge (I) Jutogh
Tender Value
44.98 Lakhs
Estimated cost
Bid Submission
07 Oct 2026
15 days left
EMD
89960
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Solan → Himachal Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Providing Of Lt Distribution Network To Otm Accn At Rms Chail Under Ge (I) Jutogh
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches in soft/loose soil n.exc 1.5 Mtr deep and n.exc 1.5 mtr wide for laying of XLPE cable and getting out including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed. |
| 2 | All as per Srl item No 1.00 above but exceeding 1.5 Mtr and not exceeding 3 mtr deep complete all as specified and directed. |
| 3 | Returning, filling, including leveling, watering and well ramming excavated soil in layers n.exc 25cm thick in trenches after cable have been laid complete all as specified and directed. |
| 4 | Removing of excavated surplus soil obtained from excavation to a distance n. exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr of the starting point complete all as specified and directed. |
| 5 | Excavation in trenches in hard/ dense Soilsoil n.exc 1.5 Mtr deep and n.exc 1.5 mtr wide for laying of XLPE cable and getting out including dressing/ trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed. |
| 6 | All as per Srl item No 5.00 above but exc. 1.5 Mtr and n. exc. 3 mtr deep complete all as specified and directed. |
| 7 | Supply, laying , jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 300 Sqmm 3.5 core confirming to IS : 7098 (Part - I) laid in trenches, under road or passing through pipes/ ducts or fixed to walls/poles complete with proper thimbles complete all as specified and directed. |
| 8 | Supply, laying, jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 240 Sqmm 3.5 core confirming to IS : 7098 (Part - I) laid in trenches,under road or passing through pipes/ducts or fixed to walls/poles complete with proper thimbles complete all as specified and directed. |
| 9 | Supply, laying, jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 95 Sqmm 3.5 core confirming to IS : 7098 (Part - I) laid in trenches,under road or passing through pipes/ducts or fixed to walls/ poles complete with proper thimbles, complete all as specified and directed. |
| 10 | Supply, laying, jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 50 Sqmm 3.5 core confirming to IS : 7098 (Part - I) laid in trenches,under road or passing through pipes/ducts or fixed to walls/poles complete with proper thimbles, complete all as specified and directed. |
| 11 | Supply, laying, jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 25 Sqmm 4 core confirming to IS : 7098 (Part - I) laid in trenches,under road or passing through pipes/ducts or fixed to walls/poles complete with proper thimbles all as specified and directed. |
| 12 | Supply, laying , jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 16 Sqmm 4 core confirming to IS : 7098 (Part - I) laid in trenches,under road or passing through pipes/ducts or fixed to walls/poles complete with proper thimbles all as specified and directed. |
| 13 | Supply, laying , jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 10 Sqmm 2 core confirming to IS : 7098 (Part - I) laid in trenches,under road or passing through pipes/ducts or fixed to walls/poles complete with proper thimbles complete all as specified and directed. |
| 14 | M&L for painting of steel tubular HT/LT poles including removing rusted particles and painting with two coats of synthetic enamel aluminium paint including cross arms, supports, clamps, etc and providing different colour strip upto height 1.5 mtr from from coping including writing pole no, complete all as specified and directed.Note: Colour of paint for strips and no of strips will be approved by Engr-in Charge. |
| 15 | Supply and fixing of sheet steel enclouser distribution boards, double door factory made TPN Vertical 4 way 3 phase 415 volts 4 way with 200 amps rating copper bus bar and PVC insulated copper jumpers of suitable size from the MCCB to the out going circuits one incoming MCCB and 12 outgoing MCBs circuits comprising of 3 phase 4 wire of suitable rating including making disturbed surface even and smooth complete all as specified and directed with the following accessories :- (a) MCCB 100 amps, 25 KA, ics=100% icu,TPN, 415 volts, 50 Hz = 01 No, complete all as specified and directed.Note:- Out going MCB shall be measured and paid for separately. |
| 16 | Supply, installation, testing and commissioning outdoor type cubical LT panel of size not less than 1.2 m x 1.2 m x 0.6 m with outer shell made out of 3.15 mm thick MS sheet and MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-2 platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front openable , lockable, having pad lock arrangement , louvers and air vent, gasket ‘u’ type for natural flow of air, completed dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factor fabricated ( Factory approved from CPRI) having modern fabrication followed by powder coated painting having thickness not less than 100 microns TPN aluminum bus bar 500 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:- |
| 17 | The panel board shall be suitable for AC, 415 Volts, 50 Hz, 3 phase, 4 wire supply complete with and comprising of the following:- (i) Epoxy insulated common aluminium bus bar of capacity 500 Amp TPN each with Color Coding, including aluminium lugs to connect the cable. (ii) MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA-01 No (For main Incomming )(ii) MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA-01 No (For Outgoing No.-1 ) (iii) MCCB 4 Pole, 415 V, Adjustable type, 100 Amps with breaking capacity 25 KA-01 No (For Outgoing No.-2 ) (iii) MCCB 4 Pole, 415 V, Adjustable type, 63 Amps with breaking capacity 25 KA-02 No (For Outgoing No.-3 & 4 ) (iv) Digital Multifunction meter with V, A, F, PF, kW, kVA, Load hours, site selectable kWh/ kVAh Amps range (0-500) Amps & Voltage range (50-520) volt flush mounting type 4\\"X4\\" square dial with CT secondary site selectable 1A / 5A(v) Indicator lamp RYB :01 Set complete |
| 18 | Supply, installation, commissioning of Busbar panel outdoor Step Type Design of size 0.8x0.8x0.5m with DMC insulators locking arrangement MS sheet covering 3.15 mm thick pedestal mounted vermin and weatherproof including four legs of 100 cm long of angle iron 40x40x5mm, front openable door having canopy for protection all surfaces painted with powder coated painting, embedding and including 400 Amp rated aluminium bus bars 4 Nos duly drilled for making connection with nut bolts of suitable size with colour code tape complete with PCC 1:3:6, type C-1, using 20 mm graded crushed stone aggregate for foundation for legs and make good electrical connection complete all as specified and directed. |
| 19 | The Bus bar panel borad shall be suitable for AC ,415 VOLT,4 wire supply complete with and comprising of following:-(i) Epoxy insulated common aluminium bus bar of capacity 400 Amp TPN each with Color Coding , including aluminium lugs to connect the cable.(ii) MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA-01 No (For main Incomming ) (iii) Digital Multifunction meter with V, A, F, PF, kW, kVA, Load hours, site selectable kWh/ kVAh Amps range (0-500) Amps & Voltage range (50-520) volt flush mounting type 4\\"X4\\" square dial with CT secondary site selectable 1A / 5A(iv) Indicator lamp RYB :01 Set complete Note: The rate are included with thimbles lugs, nut bolts,PCC foundation and aggregate. Please Enable Macros to View BoQ information |
| 20 | The Bus bar panel borad shall be suitable for AC ,415 VOLT,4 wire supply complete with and comprising of following:-(i) Epoxy insulated common aluminium bus bar of capacity 400 Amp TPN each with Color Coding , including aluminium lugs to connect the cable.(ii) MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA-01 No (For main Incomming ) (iii) Digital Multifunction meter with V, A, F, PF, kW, kVA, Load hours, site selectable kWh/ kVAh Amps range (0-500) Amps & Voltage range (50-520) volt flush mounting type 4\\"X4\\" square dial with CT secondary site selectable 1A / 5A(iv) Indicator lamp RYB :01 Set complete Note: The rate are included with thimbles lugs, nut bolts,PCC foundation and aggregate. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 16, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 07, 2026
17:00 IST