Tender For special Repair To Oh Line And Provn Of 01 X 62.5 Kva Genr Set Alongwith Accessories At 996 Ad Regt Wksp In Mil Stn Bhuj Under Ge (A) Bhuj.
Tender Value
37.27 Lakhs
Estimated cost
Bid Submission
07 Oct 2026
18 days left
EMD
74540
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kachchh → Gujarat
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for special Repair To Oh Line And Provn Of 01 X 62.5 Kva Genr Set Alongwith Accessories At 996 Ad Regt Wksp In Mil Stn Bhuj Under Ge (A) Bhuj.
BOQ
| Sl. No. | Item Description |
| 1 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in soft loose soil complete as specified and as directed. |
| 2 | Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil complete as specified and as directed. |
| 3 | Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils complete as specified and as directed. |
| 4 | M & L for sand filling in trenches for cushioning of LT cables punning after filling complete as specified and as directed.Note: Punned thickness shall only be measured and paid |
| 5 | Supply and lay un-reinforced precast concrete cable cover , class , LV , Type I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables complete as specified and as directed. |
| 6 | S & F in replacement GI pipe, light grade, of size 50 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection . |
| 7 | Dismantaling of any type and size of ACSR conductor complete all as specified and directed. |
| 8 | Disconnecting, taking out, removing old existing unserviceable LT cable, overhead service cable of any size etc complete all as specified and directed. |
| 9 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 10 Sqmm 4 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 10 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 16 Sqmm 4 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 11 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 25 Sqmm 4 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 12 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 70 Sqmm 3.5 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 13 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 95 Sqmm 3.5 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 14 | Supply, installing ,testing and commissioing factory made and tested LT Outdoor Street/Flood Light Control Panel having platform mounted,suitable for 415 Volts 3 Phase and neutral 4 wire,50 HZ AC supply system shall be dust and vermin proof,protection class(IP-65) and made of CRCA sheet steel enclusure 3.0 mm thick suitable framework/Support made out of 40x40x5 mm MS Iron angle frame ,front opening type with aprons for cable entry,with proper ferrul and cable gland,internal wiring with PVC insulated multistranded copper conductor FRLS Cable of adequate size but not less than 4 sqmm,minimum 0.5 meter height from ground level,marking of outgoing area as per site, Air vent , PCC foundation 1:2:4 for foundation etc complete all as specified and directed. Note : The contractor shall submit detail Schematic Layout of the Panel Board for approval from Engr-in-Charge before procurement.The scope of work also comprising of the following :-(i) RYB Phase indicating LED type -01 set. (ii) MCB TPN 40Amps 4 polez,10 KA,50 HZ,415 Volts-01 No (iii) Power contactor 3 Pole,40 Amps.50 Hz,415 Volts-02 No(01 Stand by). (iv) Time switch Digital Type,one dial daily,240/415 Volts,50 Hz-01 No. (v) Auto/Manual selector switch 6A-01 No.(vi) RYB Phase indicating light LED Type -03 No. |
| 15 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :- |
| 16 | Incoming (a) Copper Bus bar, 400 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 250 A 36 KA-01 (c) Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) (e) Digital voltmeter 0 to 500V with selector switch - 01No(f) Digital Multifunctional meter - 01 No |
| 17 | Outgoing(a) MCCB 4 Pole thermal adjustable magnetic release 415 volts 160A 36 ka -2 nos (b) MCCB 4 Pole thermal adjustable magnetic release 415 volts 63A 16 ka -2 nos |
| 18 | Supply and drawing through the pole for making connections to the light fittings, three core, PVC insulated and sheated, Heavy duty,1100 volts grade,multistranded copper conductor (FRLS) cable 3C x 2.5 sqmm complete all as specified and directed. |
| 19 | Supply and fixing PVC pipe 25/20 mm through FRP Junction to street light fitting on the pole including all connecting accessories to the pole complete all as specified and directed. |
| 20 | Supply and fixing PVC coated flexible pipe 40 mm for protection of cable etc complete all as specified and directed. |
| 21 | Supply and fixing in replacement LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with system efficacy greater or equal to 120 lumen/watt, beam angle =120 degree complete with IP 66 and min IK07 protection with integrated surge protection 4kV to 10kV and optics designed for Road lightning ,PF>0.95 and IEC safety class 1 protection complete all as directed. Make : Philips Cat Part No BRP334 LED 110 or Equivalent makes specified in Appx B. |
| 22 | Supply and fixing cable junction box with new pole mounted polycarbonate cable junction box of min size 300x200x105 mm or next higher size for street light with IP-66 protection, weather proof with metric knockouts for cable entry for outdoor installation with front door opening system, cable gland, cable terminal for incoming and outgoing cable according to cable size including terminals for one incoming and one outgoing cables of size 16/25 sqmm 4 core, tapping of 3Core 2.5/1.5sqmm from terminals, with one MCB SP 6 Amp 240V AC with mounting on DIN rail, pole clamp of flat iron, nut, bolt and washers complete all as specified and directed . Make: Hensel/Sintex/National |
| 23 | M&L for taking down old damged PCC pole and carefully taking down street light fiitings, bracket, Aluminium conductor of any size and other connected items all as specfied and directed. |
| 24 | Supply, erecting and fixing in true vertical position, Prestressed cement concrete pole 9 mtr long confirming to IS-1678 (latest) with minimum cross sectional area 102 mm x 152 mm at top and 102 mm x 289 mm at bottom , class - 10 ,removing of old pole to side and refixing of MS channel , restringing of conductor, providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30cm in between 2 bands and numbering of poles, and numbering of the poles shall be done with synthetic enameled painted letter of shape & size complete( M&L)all as specified and directed. (Note -SSR part I clause No.19.5 & 19.52 and other relevant clauses of SSR refers for execution of work and poles shall be procured directly from the manufacturer mentioned in tender documents.) |
| 25 | Excavation in trenches not exceeding 1.5m wide and exceeding 1.5m in depth and not exceeding 3.0m depth for foundation, laying of cable/pipe etc or for shaft, walls, cesspts, manholes, pier holes etc not exceeding 10 sqm on plan and getting out in hard/dense soil complete all as specified & directed. |
| 26 | M&L for PCC 1:2:4 type B-1 using 20 mm graded aggregates as in copings, kneelers, apex stones, bed plates, kerbs etc., water troughs and the like including weathering, slightly rounded for chamfered angles and throating including necessary form work complete all as specified and as directed. |
| 27 | M&L for PCC (1:3:6) type C-2 using 40 mm graded crushed stone aggregate in foundation, filling and mass concrete for poles/struts etc including necessary formwork as required complete all as specified and directed. |
| 28 | M&L for PCC 1:4:8 type D2 using 40 mm graded aggregates as in copings, kneelers, apex stones, bed plates, kerbs etc., water troughs and the like including weathering, slightly rounded for chamfered angles and throating including necessary form work complete all as specified and as directed. |
| 29 | M&L for cross arms bracings, supports, clamps and back plates fabricated from structural steel sections incl nut & bolts , washers welding, bending cold or hot drilling holes for bolts, washers in any shape of size as indicated or directd . |
| 30 | Material and labour for cutting of existing road ,insert the required size pipe for drawn of cable etc and repair the same with PCC 1:2:4 type B2 (using 40 mm graded stone aggregate) for filling the disturbed road opening for cable crossing include levelling with road surface and smooth finishing complete all as specified and directed. ( for Road Cutting Repair) |
| 31 | Material and labour in replacement for earthing complete with GI earth plate electrode 600x600x6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground lavel) with top edge of the plate not less than 1.5mtr below normal ground lavel connected to Galvanised iron earth strip 32x6 mm by mean of bolts, nuts, check nuts and washer of brash all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including PCC pit and CI cover fullel with watering pipe, wire mess and copper lugs etc GI protection pipe 40 mm dia medium grade including testing on completion all as specified and directed. |
| 32 | Note :- (i) The unit rate shall also included for earth work in hard /dense soil , PCC type C-I (1:3:6) chamber , PCC 1:2:4 type B-I cover 50 mm thick reinforced with 8 mm dia TMT bars,150 mm c/c both ways, funnel with watering pipe 20 mm dia medium graded , GI protection pipe light grade 15 mm dia and wire mesh complete in addition to items No. 1(a) to (e) of preamble (notes) under sub heading earthing specified on SI page No. 389 of SSR Part - II.(ii) Earthing strip and GI protection pipe beyond 7.5 mtrs will be measured and paid separatelly if required under appropriate Schedule.(iv) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On teting after complataion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his on risk and cost to the entire satisfaction of the Engr - in - charge |
| 33 | S & F GI pipe, light grade, of size 80 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection . |
| 34 | Supply install testing and commissioning of Diesel engine driven genrating set 415 Volts, 3 Phase 4 wire, engine as per latest and alteranator as per latest IS with inbuilt AMF panel complete with foundation as per design, control panel with necessary meter and sound proof canopy as per latest CPCB norms of capacity 62.5 KVA. Tools and spares complete all as specified and directed and comprising of the following :- |
| 35 | AMF Panel : The AMF Panel microprocessor based shall be designed for Automatic ON mains failure operation of the generator sets and panel shall complete with interconnections, insulators, two number of earthing lugs and with suitable rating of MCCB at incoming and outgoing ends and shall incorporate the followings - |
| 36 | (i) Electric contactors for both DG and main supply |
| 37 | (ii) Main Supply voltage monitor |
| 38 | (iii) AMF logic unit having protection for over frequency, under frequency, over voltage, under voltage, low lube oil, and high water temperature for engine |
| 39 | (iv) Battery charger consisting of Transformer, Rectifier, DC Voltmeter, DC Ammeter, Charging rate selector switch |
| 40 | (v) Auto / Manual mode switch |
| 41 | (vi) MCB using for indicators and meters |
| 42 | (vii) Hooter 24 V DC |
| 43 | (viii) By pass arrangement |
| 44 | (a) Engine: Diesel engine,direct injection, water cooled as per manufactured standard BHP @ 1500 RPM for continuous duty of suitable for 62.5 KVA alternator with provision of 10% over load for one hour in every 12 hour running confirming to latest BS 5514/ISO 3046 Std , totally enclosed .The engine shall consists of following specification :- The scope of supply includes: |
| 45 | -Electrical starter motor 12V DC, Battery charging alternator |
| 46 | -Radiator cooling,with turbo charged after cooling |
| 47 | -Fuel injection Pump |
| 48 | -Governor |
| 49 | -fuel filter |
| 50 | -Spin-on full flow lub oil filter |
| 51 | -Residential silencer |
| 52 | -Dry type air cleaner |
| 53 | -Shut-off coil with safeties for LLOP/HWT |
| 54 | -Flywheel and flywheel housing to suit single bearing alternator |
| 55 | (i) Alternator: suitable for operation at 1500 RPM, 415 Volts, 0.8 pf (lag) suitable for 50 Hz, 3 phase, 4 wire system, conforming to latest BS/IS. The Alternator is brushless type, screen protected, revolving field, self excited, self regulated through an AVR. The alternator has the following features: -+ 1.0 % Voltage regulation (max.) in static conditions -Permissible overload of 10%.operation as per standards |
| 56 | (ii) Mounting arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. The steel shall be TESO / SAIL or equivalent make |
| 57 | (iii) Control panel: The control panel is manufactured with standard gauge CRCA sheet and is powder coated for a weather-proof, long lasting finish. The control panel consists of following parts: -Standard engine instrumentation -Multi function meter which measures: 1) Individual phase current (Amps) 2) Phase voltages (V) 3) Generator output frequency (Hz) 4) Engine water temperature (Deg.C) 5) Lube oil pressure (kg/cm2) and equipped with hour counter -MCCB of suitable rating -Key switch -Push button (Starter) -LED: Battery charging alternator fail indication -Current transformers -Instrument fuses duly wired and ferruled |
| 58 | (iv) Others: -Fuel tank suitable for 8 hours of operation -One charged battery 12V, suitable rating AH with battery leads & cable |
| 59 | Acoustic enclosure: The acoustic enclosure is made of standard CRCA sheets and structural/ sheet metal base frame duly painted. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75 dBA at 1mtr sound levels specified by Ministry of Environment & Forest. The enclosure has the following features: -Specially designed to meet stringent MOEF/ CPCB norms of 75 dBA @ 1mtr at 75% load under free field conditions, -Single point lifting for easy handling, -Designed to have optimum serviceability -Air inlet louvers specially designed to operate at rated load, -Made on special purpose CNC machines for consistency in quality and workmanship, -Powder coated for long lasting service life and superior finish, -With UV resistant powder coating, can withstand extreme environments, -Use of special hardware for longer life, -Insulation material meets exacting IS 8183 specifications for better sound attenuation, -Flush styling - no projections, -Fluid drains for lube oil and fuel, -Fuel filling point. The following tools are requried for maintenence of DG Set and to be handed over to Engr-in-Charge. |
| 60 | Tools (As per manufacturers instructions |
| 61 | (a) 'D' spanners - 01 Set |
| 62 | (b) Ring spanners - 01 Set |
| 63 | (c) Screw driver 5\\" to 12\\" - 01 Set |
| 64 | (d) Cutting plier 9\\" - 01 No |
| 65 | (e) Hammer 2 LBS - 01 No Please Enable Macros to View BoQ information |
| 66 | (e) Hammer 2 LBS - 01 No Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 16, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 07, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysOct 09, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓