Tender For Repair / Maintenance Of External Electrical Networks Feeder Pillars, Lt Switch Gears At Sector- Iii & Iv At Ge Deolali.

Issued by Statutory Bodies & Commissions/Committees · Nashik, Maharashtra
Tender Value
49 Lakhs
Estimated cost
Bid Submission
06 Oct 2026
19 days left
EMD
98000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Nashik → Maharashtra
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair / Maintenance Of External Electrical Networks Feeder Pillars, Lt Switch Gears At Sector- Iii & Iv At Ge Deolali.

BOQ

Name of Work:- REPAIR / MAINTENANCE OF EXTERNAL ELECTRICAL NETWORKS FEEDER PILLARS, LT SWITCH GEARS AT SECTOR- III & IV AT GE DEOLALI.
Sl. No. Item Description
1Taking down existing defective LT under ground cable of any size from trenches complete all as directed.
2S&F tubing 'light grade' galvanised iron with all fittings and fixed to poles, walls etc. with flat iron clamps/bolts/nuts/washers or laid in floors/under roads complete all as specified and directed .
380 mm bore
450 mm bore
540 mm bore
6Supply, Laying , jointing and testing in replacement of LT underground cable, heavy duty, 1100 Volts, XLPE insulated and sheathed, armoured with multi-stranded aluminium conductor cable , laid in trenches/ducts or fixed to poles/walls or laid under roads/paths/drains/culverts duly encased in galvanised steel pipe of suitable sizes including cable gland of suitable sizes and aluminium lugs for connection complete all as specified and directed of following size:-
73.5 core150 sqmm
83.5 core120 sqmm
93.5 core 70 sqmm
103.5 core 50 sqmm
113.5 core 35 sqmm
123.5 core 25 sqmm
134 core 16 sqmm
142 core 16 sqmm
15Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil complete all as specified and directed.
16Excavating in post hole size 0.6 Mtr X 0.6 Mtr X 1.65 Mtr depth for installation of LT pole 9 mtr long ,in any type of soil and getting out, returning filling in and ramming earth or broken rubble mixed with earth around in layers not exceeding 25 cm.
17Supply & lay in trenches double walled corugated HDPE pipe 75 mm dia high density for protection of under ground cables( Note: pipe couplers with seal, bends, end covers etc are deemed to be included in rate quoted)
18Supply & lay in trenches double walled corugated HDPE pipe 50 mm dia high density for protection of under ground cables( Note: pipe couplers with seal, bends, end covers etc are deemed to be included in rate quoted)
19Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed
20Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
21Supply and fix , test , commissioning of LT weather proof panel board powder coated out door type double door shutter type made out of CRCA 3.15 mm thick outer and 1.6 mm thick for inner door confirming to IS 8623 with angle iron 50x50x6 mm outdoor, floor mounting type with closed bus bar , chamber and with aluminium bus bar with necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supply as per CPRI approved including provn of digital ammeter 0-500A, digital voltmeter 0-500Volts, CT's of suitable ratio, indicator lamps R-Y-B,selector switches and internal wiring including making PCC block type 0.6 Mtr above ground level grouting etc all as specified and directed with the following Work also includes provision of suitable size of cable glands, cable lugs, nut, bolts, washers etc (The bottom portion of enclosure shall be minimum 40 cm above ground level. legs & depth of the panel should not be less than 45cm).Legs of angle iron should be 100 cm lenth (60 cm below ground and 40 cm above the eground) a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA , 250 Amp - 1 No (I/C) c) MCCB 4 Pole 30 KA, 63 Amp - 5 Nos
22All as item NO 10 above but with following accessories:- a) Aluminium bus bar of capacity 200 Amps for Phase-R-Y-B & 100 Amps for neutral -1 No b) MCCB 4 Pole 36 KA , 160 Amp - 1 No (I/C)c) MCB TPN 63 Amp ,10 KA - 4 Nos (O/G) d) MCB SPN 32 Amps-02 (O/G)
23All as item NO 10 above but with following accessories:- a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 250 Amp - 1 No (I/C)c) MCCB 4 Pole 36 KA 160 Amp - 1 No (O/G)d) MCCB 4 Pole 25 KA 63 Amp - 4 Nos (O/G)
24All as item NO 10 above but with following accessories:- a) Aluminium bus bar of capacity 300 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 200 Amp - 1 No (I/C)c) MCCB 4 Pole 36 KA 100 Amp - 1 No (O/G)d) MCCB 4 Pole 25 KA 63 Amp - 2 Nos (O/G)
25All as item NO 10 above but with following accessories:- a) Aluminium bus bar of capacity 200 Amps for Phase-R-Y-B & 100 Amps for neutral -1 No b) MCCB 4 Pole 36 KA , 160 Amp - 1 No (I/C)c) MCCB TPN 63 Amp ,10 KA - 1 Nos d) MCB TPN 63 Amps-04 e) Astro time switch ( AUTS02AST00 of L&T) suitable for street light control and with 40 Amps ,440 volt coil voltage MNX- 40 contactor ( L&T) 3Ph phase- 0 1 Set
26All as item NO 10 above but with following accessories:- a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA , 250 Amp - 1 No (I/C)c) MCCB 4 Pole 36 KA , 250 Amp - 1 No (O/G) d) MCCB 4 Pole 30 KA 63 Amps - 1 No (O/G)
27All as item NO 10 above but with following accessories:- a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA , 250 Amp - 1 No (I/C)c) MCCB 4 Pole 36 KA , 125 Amp - 2 No (O/G) d) MCCB 4 Pole 30 KA 63 Amps - 1 No (O/G)
28All as item NO 10 above but indoor type with following accessories:- a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA , 400 Amp - 1 No (I/C)c) MCCB 4 Pole 36 KA , 250Amp - 3 No (O/G) d) MCCB 4 Pole 30 KA 100 Amps - 1 No (O/G) e) MCB SPN 10 KA 32 Amps -2 No (O/G)
29M&L for out door type bus bar chamber fabricated by MS sheet of size 3mm and mounted on MS angle iron frame suitable for 415 Volt 3 phase 4 wire AC supply comprising of Aluminium bus bar of capacity 200Amps installed on epoxy insulators consisting of MCB TPN 63 Amps-01 No & MCB SPN-32 Amps-06 Nos. the bus bar chamber should be dust proof, vermi proof and made out of 3 mm CRCA sheet and mounted on 40x40x6mm angle iron,.door is front opening with locking arrange ment. duly powder coated.including MS stand, making PCC block type 0.6 Mtr above ground level grouting etc all as specified and directed.
30Supplying, install and errect in true vertical position steel tubular swaged welded pole in replacement complete with cast iron/MS base plate 6mm thick and of size 300x300mm, final taper, pole cap, bolts, nuts, washers & screws etc. pole made out of ERW M.S. tubing conforming to IS-2713 part-II type 410 SP-531 (9.0 metre long) LT including of holes of reqd Nos and size for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embedded in concrete, painting three signal red colour bends at lower portion of exposed pole starting from plinth block , each band of 300mm height at 300mm spacing, painting pole No the black paint by stenciled letters/figures of 8 cm height complete all as specified and directed. (Note:1. Excavation and PCC works will be measured and paid separatly in respected items.)
31M&L for cement concrete 1 : 2 : 4 type B-1 using 20 mm graded aggregate as in foundation , filling and mass concrete necessary form work all as specified and directed. (for transformer platform)
32M&L for cement concrete 1 : 4 : 8 type D-2 using 40 mm graded aggregate as in foundation for pole including necessary form work all as specified and directed.
33M&L Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts,bolts,washers, welding , bending cold or hot, drilling holes for bolts,in any shape or sizes as indicated or directed and Including one coat of primer and two coats of alluminium paint complete all as specified and directed.
34M&L for scrubbing out old paint, rust etc from 9 mtr steel tubular pole of any size and making smooth and even surface then painting with one coat of anti rust paint and two coat of superior quality aluminium paint on entire exposed portion of pole structure and writing Abbreviated feeder name in 2 \\" size with white paint on black base all as directed at site(work shall be completed in the stipulated period as directed.
35M&L in replacement of u/s MCCB of 4 pole 63 Amps 415 Volts with breking capacity 35 KA includind spreader link complete all as specified and directed .
36M&L in replacement of u/s MCCB of 4 pole 100 Amps 415 Volts with breking capacity 35 KA includind spreader link complete all as specified and directed .
37M&L in replacement of u/s MCCB of 4 pole 125 Amps 415 Volts with breking capacity 35 KA includind spreader link complete all as specified and directed .
38M&L in replacement of u/s MCCB of 4 pole 160 Amps, 415 Volts, with breking capacity 35 KA includind spreader link complete all as specified and directed .
39M&L in replacement of u/s MCCB of 4 pole 200 Amps 415 Volts, with breking capacity 35/36 KA , adjustable type includind spreader link complete all as specified and directed .
40M&L in replacement of u/s MCCB of 4 pole 250 Amps 415 Volts, with breking capacity 35/36 KA fixed type includind spreader link complete all as specified and directed.
41M&L in replacement of u/s MCCB of 4 pole 400 Amps adjustable type, 415 Volts, with breking capacity 50KA includind spreader link complete all as specified and directed .
42Supply and fix in repair MCB 4 Pole 63 Amps, 415 volts complete all as specified and as directed.
43Supply and fix in replacement MCB TP 63 Amps, 415 volts complete all as specified and as directed.
44Supply and fix inreplacement MCB TPN 32 Amps, 415 volts complete all as specified and as directed.
45Supply and fix in replacement MCB TP 63 Amps, 415 volts complete all as specified and as directed.
46Supply and fix in replacement MCB TP 32 Amps, 415 volts complete all as specified and as directed.
47Supplying, fixing, jointing and testing heat shrinkable Straight through joint, with including jointing materials suitable for 1100 V , XLPE LT cable of size 25-50 sqmm , 3.5 core , Incl excavation upto 7 mtrs and returning fillin in after jointing of cable complete all as specified and directed.
48Supplying, fixing, jointing and testing heat shrinkable Straight through joint, with including jointing materials suitable for 1100 V , XLPE LT cable of size 70-120 sqmm , 3.5 core , Incl excavation upto 7 mtrs and returning fillin in after jointing of cable complete all as specified and directed.
49Supplying, fixing, jointing and testing heat shrinkable Straight through joint with including jointing materials suitable for 1100 V, XLPE LT cable of size 150-185 sqmm , 3.5 core , complete all as specified and directed .
50Supplying, fixing, jointing and testing heat shrinkable Straight through joint , with including jointing materials suitable for 1100 V, XLPE LT cable of size 240-300 sqmm , 3.5 core , Incl excavation upto 7 mtrs and returning fillin in after jointing of cable complete all as specified and directed.
51Trimming of tree branches up to the extent to obtain clearence all around the LT over head lines conductor up to 3 mtr from the conductor on pole including removing of cut branches and clearing the site. Note: tools and cutting equipment to by provided by contractor only.
52Cutting through existing bituminous road /PCC/floor/approx size width 50cm X 60cm depth along cross section of the road for laying of GI tubing/RCC pipe for encasing of cable and repairing the road to match with the original finish complete all as specified.
53\\"M&L earthing GI Strip complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32 x 6 mm size by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of strata, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete all as specified.
54M&L for servicing of 1.1 KV LT ACB of 415 Volts 630 Amps by removing from LT panel, dismantling checking the serviceability of parts & replacing the unserviceable parts ,oiling/ greasing the moving parts, reassembling, testing and installing to the original position and cheking for correct fuctioning. all as specified and directed .
55M&L for making underground boaring (Manually/Mech) through existing bituminous road/PCC/Floor along cross section approx 10 mtr of the road at a depth approx 1.0 mtr for laying of GI tubing of dia 80/100 mm for encasing of cable all as specified.
56Supply,install, testing & commissioning of factory made LT panel wall mounted board made out of CRCA sheet 2 mm thick indoor type toltally enclosed weather,dust and vermin proof compartment type with front hinged door and locking arrengement mounted on M S flat iron clamp welded to panel body duly grouted on wall 415 V, 3 phase, 4 wire AC, 50 Hz having aluminium bus bar 160 Amps for pfase-03 Nos & neutral- 01 No with 02 Nos Earth Terminals. insulated with PVC sleeves, space for fixing single phse KWH Emergy meter 04 Nos 40x40x6 mm size angle iron hold fast, fastener bolts, copper lugs, spacers channels,rubber gaskets, locking knob, hylem sheet piece,PVC shrinkable sleeves, nut and bolts, washers etc suitable single core copper wire connectors, suitable compartments and epoxy power spray paint with primer complete all as specified including the following accessories including taking down old unservicable LT panel board INCOMING- a) MCCB 415 V 4 POLE 18 KA breaking capacity of 63 Amps- 01 No b) R-Y-B phase LED indicating lamp-03 Nos OUTGOING- a) MCB SPN 32Amps, 230V, 10 KA, C curve - 05 Nos b) Providing space for and refixing existing single phase KWH electric enery meter-04 Ns c) Copper wire 6 Sqmm wire and open terminals for all meters totaly pre wired. d) Glass windows for all meter for taking meter reading Note:- 1. Cost of taking down electric meters from old unserviceable penel board keeping in safe custody, and refixing the same electric meters in new panel is deemed to be includede in rate quoted. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57535076
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 49 Lakhs
LAST DATE 06-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair / Maintenance Of External Electrical Networks Feeder Pillars, Lt Switch Gears At Sector- Iii & Iv At Ge Deolali.
Basic Detail
Tender No 8229/E8
Bidding Type Tender
Location
City Nashik
State Maharashtra
Key Dates
Publish Date 15 Sep 2026
Submission Date 06 Oct 2026
Open Date 12 Oct 2026
Finance
Tender Value 49 Lakhs
Tender Fee 500
EMD 98000
Exemption Available
Document List
3e820c6d-753c-4332-bad9-a4c80c4ab5a0.html
BOQ_885018.xls
gnlpgs.pdf
ps.pdf
Tendernotice_1 (10).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 15, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 06, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 19 days
Oct 12, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 25 days

Tender Documents

Download All (ZIP) ↓
html

3e820c6d-753c-4332-bad9-a4c80c4ab5a0.html

xls

BOQ_885018.xls

pdf

gnlpgs.pdf

pdf

ps.pdf

pdf

Tendernotice_1 (10).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders