Tender For Electrical & Allied Work For Cca Block Building At Ssj University, Almora.
Tender Value
1.90 Crore
Estimated cost
Bid Submission
29 Sep 2026
13 days left
EMD
3.80 Lakhs
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Nainital → Uttarakhand
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Electrical & Allied Work For Cca Block Building At Ssj University, Almora.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loopearthing as required. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire (For Circuit Wiring & Light Plug Wiring) |
| 6 | 2 X 6 sq. mm + 1 X 6 sq. mm (For Single Phase DB. From Sub Panel to DB) |
| 7 | 4 X 10 sq. mm + 2 X 6 sq. mm (For Three Phase DB. From Sub Panel to DB) |
| 8 | 4 X 16 sq. mm + 2 X 16 sq. mm (For Three Phase DB. From Sub Panel to DB) |
| 9 | Supplying and fixing following Modular base & cover plate one existing modular metal boxes etc. as required |
| 10 | 6 Module |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required |
| 12 | 5/6 A switch |
| 13 | 3 pin 5/6 A socket outlet |
| 14 | 15/16 A Switch |
| 15 | 6 pin 15/16 A Socket outlet |
| 16 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 17 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 18 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 19 | Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 20 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 21 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 22 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 23 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 24 | 1 or 2 Module (75mmX75mm) |
| 25 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 26 | Telephone socket outlet |
| 27 | TV antenna socket outlet |
| 28 | Bell push |
| 29 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 30 | 20 mm |
| 31 | 25 mm |
| 32 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, Unarmored Telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 33 | 2 Pair |
| 34 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 35 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 36 | 1 run of cable |
| 37 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 38 | 25 mm |
| 39 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 40 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 41 | Upto 450 mm sweep |
| 42 | Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes. |
| 43 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 44 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 45 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 46 | Single pole |
| 47 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 48 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 49 | 8 way , Double door |
| 50 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required. |
| 51 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 52 | Above 35 sq. mm and upto 95 sq. mm |
| 53 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 54 | 3 X 95 sq. mm (38mm) |
| 55 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 56 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 57 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 58 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 59 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 60 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 61 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 62 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 63 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 64 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 65 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 66 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 67 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 68 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 69 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 70 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. |
| 71 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 72 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 73 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 74 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 75 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Reducer\\" (galvanisation not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. |
| 76 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 77 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 78 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 79 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 80 | FLOORS PANEL |
| 81 | Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. |
| 82 | INCOMER : 150 AMP |
| 83 | BUS BAR : 150 AMP, 440 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp. |
| 84 | OUT GOINGS : |
| 85 | 1 No 40 AMP 4P MCB (Light DB 1) |
| 86 | 1 No 40 AMP 4P MCB (Light DB 2) |
| 87 | 1 No 63 AMP 4P MCB (Power DB 1) |
| 88 | 1 No 63 AMP 4P MCB (Power DB 2) |
| 89 | 4 No 63 AMP 4P MCB (Spare) |
| 90 | Complete panel as above and complete |
| 91 | Providing and Supplying of LED Batten 20 Watts 1150 mm |
| 92 | Providing and Supplying of 9W Led Bulb With Battery-Is:16102, Warranty for free replacement 1 year |
| 93 | Providing and Supplying of 12W Warm White Ceramic Circular LED Surface Ceiling Light |
| 94 | Providing and Supplying of Aluminium Wall Fan 2 year Warranty |
| 95 | Providing and Supplying of Exhaust Fan 300 mm |
| 96 | Providing and Supplying of 2 Ton 5 Star, Inverter AC Wall Mount Split AC |
| 97 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 98 | 25 mm dia |
| 99 | 50 mm dia |
| 100 | 100 mm dia |
| 101 | 150 mm dia |
| 102 | Excavating trenches of required width for pipes, cables, etc, including excavation for sockets, depth upto 1.5 m, including getting out the excavated materials, returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, within a lead of 50 m : 2.13.1 Ordinary rock 2.13.1.2 Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 103 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 104 | 100 mm dia |
| 105 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 106 | 100 mm dia |
| 107 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
| 108 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : 150mm dia |
| 109 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 40 m |
| 110 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel (Grade 304) |
| 111 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Stainless Steel (Grade 304) |
| 112 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 4 way - 150 mm dia M.S. Pipe |
| 113 | 2 way-100 mm dia M.S. Pipe |
| 114 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 100mm dia |
| 115 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel |
| 116 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 117 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1000mm |
| 118 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 150mm dia |
| 119 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : |
| 120 | Pendent Sprinkler |
| 121 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. |
| 122 | 100mm dia |
| 123 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (d) Suitable cement concrete foundation duly plastered and with anti vibration pads.900 lpm at 35 m Head |
| 124 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 125 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
| 126 | 150mm dia |
| 127 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter_x0002_connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required : |
| 128 | INCOMING |
| 129 | 800A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-800 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 1000Amps |
| 130 | OUTGOING |
| 131 | ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
| 132 | MAIN FIRE PUMP |
| 133 | 250 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets |
| 134 | JOCKEY PUMP |
| 135 | 125 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets |
| 136 | DIESEL ENGINE CONTROL |
| 137 | Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 138 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 139 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 140 | Providing & fixing 25mm x 5mm G.I. strip on surface or in recess for connections etc. as required. |
| 141 | Providing and Fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing alongwith existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 142 | Supplying, fabricating and installing following size of perforated painted with powder coating M.S. cable trays,with perforation not more than 17.5%, in covenient section, joined with connectors, suspended from the ceiling with MS suspenders including bolts & nuts, painting suspenders etc. as required. |
| 143 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 144 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 145 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 146 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 147 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 148 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 149 | 4x16 sqm mm (28mm) |
| 150 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 151 | 4 x 1.5 Sq. mm |
| 152 | Providing & Supplying Extinguisher Fire Carbondioxide 4.5 kg,duly charged, Portable and complete as per defence specification |
| 153 | Providing & Supplying ceasefire Wall Mounted Automatic Fire Extinguisher Powder Based (as per IS 4308 ) Automatic |
| 154 | Providing & Supplying FIREMAN'S AXE 3 kg (Fire suppression hand tools) |
| 155 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
| 156 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 157 | Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 158 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. |
| 159 | Supplying and fixing of following sizes of PVC conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25mm |
| 160 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/recessed Steel/PVC conduit as required 1 run of cable. |
| 161 | Supplying and fixing of GI box of following size modules, along with modular base & cover plate for modular switches in recess etc as required. |
| 162 | 1 or 2 Module (75mmx75mm) |
| 163 | Supply, installation, testing and commissioning of following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. RJ 45 Socket |
| 164 | Supply, installation, testing and commissioning of 9U rack complete with all accessories etc complete as per specifications and as required. |
| 165 | Supply, installation, testing and commissioning of 42U rack complete with all accessories etc complete as per specifications and as required. |
| 166 | Supply, installation, testing and commissioning of 12 port unmanaged ethernet switch. |
| 167 | Supply, installation, testing and commissioning of 24 port managed ethernet switch with 2 nos fiber ports. |
| 168 | Supply, installation, testing and commissioning of Cat-6 shuttered 12 port fully loaded patch panel. |
| 169 | Supply, installation, testing and commissioning of 24 port Patch panel fully loaded patch panel. Cat-6 UTP |
| 170 | Supply, installation, testing and commissioning of Cat-6 UTP 24AWG patch cord, 1 meter, Plug 30U, snaglless etc as required. |
| 171 | Supplying and Fixing of following sizes of PVC conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 172 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/recessed Steel/PVC conduit as required 1 run of cable. |
| 173 | Supply, installation, testing and commissioning of IP Camera Indoor 4MP with RJ 45 connector/jack. |
| 174 | Supply, installation, testing and commissioning of IP Camera Outdoor 4MP with RJ 45 connector/jack. |
| 175 | Supply, installation, testing and commissioning of NVR 32 channel complete with all respect accessories and suitable for minimum 4 slot harddisk. |
| 176 | Supply, installation, testing and commissioning of hard disk 4TB per NVR. |
| 177 | Supply, installation, testing and commissioning of Switch 16 port POE. |
| 178 | Supply, installation, testing and commissioning of Switch 24 port POE. |
| 179 | Supply, installation, testing and commissioning of Back Box. |
| 180 | Supply, installation, testing and commissioning of 48\\" LED Screen for Observation and reviewing. |
| 181 | Supply and fixing of 2 meter patch cord with complete connectors. |
| 182 | Supply, installation, testing and commissioning of 42U RACK with PDU and respected accessories. |
| 183 | Supply, installation, testing and commissioning of 9U RACK with PDU and respected accessories. |
| 184 | Supply, installation, testing & commissioning of Numeric 5 KVA Online Ups with inbuilt isolation transformer. |
| 185 | Supply, installation, testing & commissioning of SMF 12V*26 AH X 16 NOS. BATTERY, RACK & LINKS . |
| 186 | Supply, installation, testing and commissioning of Power Generator- DG set of 250 KVA Power Generator installation configurations as defined in CPWD General Specifications for Electrical works - Part VII (DG Set) Fixed (Power Generators are permanently installed) 1500 RPM Engine, VG 3 Voltage Regulation Grade, AMF Control Panel, with installation - inclusive in the scope of supply with 24 month warranty on complete power genertor/DG Set. |
| 187 | Supplying, installation, testing and commissioning of LED street/compound/ high mast/ pathway/ landscape lighting for the entire campus (Rate applicable on total plot area). Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 15, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 13 daysSep 29, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 13 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender