Tender For special Repair To Ceiling Fans, Exhaust Fans, Geyser And Cooling Appliances Against Ber For Otm And Md Accn At Other Than Mh Secbad Under Age E/M Of Ge (South) Secunderabad Under Age E/M (S) Of Ge (S) Secunderabad
Tender Overview
Project Description
Tender for special Repair To Ceiling Fans, Exhaust Fans, Geyser And Cooling Appliances Against Ber For Otm And Md Accn At Other Than Mh Secbad Under Age E/M Of Ge (South) Secunderabad Under Age E/M (S) Of Ge (S) Secunderabad
BOQ
| Sl. No. | Item Description |
| 1 | Supply, install, testing and commissioning of energy efficient split type air conditioner indoor/outdoor units complete all as specified and directedISEER : 5 Star Tonnage rating : 1.5TR Compressor: Inverter type Condenser material : CopperBlower motor winding : Copper Condenser fan motor winding : Copper Operation sound : Not more than 60 dbRefrigerant : R32/R-410/R-407 Indoor unit and out door unit connection pipe material: CopperAir flow rate : Not less than 700 CFM Swing : 2 way Maximum cooling capacity: Not less than 5000 Watts at 100 % LoadMinimum cooling capacity: 1500 Watts Power supply: Single phase 230 V, 50 Hz Evaporative fins : Hydrophilic finsFilters : Anti dust with anti Microbial Remote: LCD Display wire lwss Temperature setting range: 16 to 30 degree Celsius Maximum ambient tperature:52 degrees celsius Maximum piping capability: 3 Mtrs Thermostat : Anti freeze typeDrain pipe: 15 mm dia flexible type up to 15 Mtr |
| 2 | Supply, install, testing and commissioning of energy efficient split type air conditioner indoor/outdoor units complete all as specified and directedISEER : 5 Star Tonnage rating : 2TR Compressor: Inverter type Condenser material : CopperBlower motor winding : Copper Condenser fan motor winding : Copper Operation sound : Not more than 60 dbRefrigerant : R32/R-410/R-407 Indoor unit and out door unit connection pipe material: CopperAir flow rate : Not less than 700 CFM Swing : 2 way Maximum cooling capacity: Not less than 6000 Watts at 100% loadMinimum cooling capacity: 1500 Watts Power supply: Single phase 230 V, 50 Hz, copper cable 3 core 4 Sq.MmEvaporative fins : Hydrophilic fins Filters : Anti dust with anti Microbial Remote: LCD Display wire lessTemperature setting range: 16 to 30 degree Celsius Maximum ambient tperature:52 degrees celsiusMaximum piping capability: 3 Mtrs Thermostat : Anti freeze type Drain pipe: 15 mm dia flexible type up to 15 Mtr |
| 3 | S&F Desert cooler ISI marked of following specifications complete all as specified and directed.(i)Air drluvery Capacity: Not less than 5000 CMH (ii)Cooling media : Honey comb(iii)Speed control: 3 step speed control Knob for power ful motor (iv)Water tank capacity: 100 Ltrs(v)Material: PVC body/Metal as per OEM (vi)Air through distance: Not less than 20 Mtrs(vii)Power : Single phase,230 V & 50 Hz (viii)Mounting: Lockable castor Wheel (ix)Float valve: Yes(x)Vertical swing: As per OEM (xi)Water level indicator: Yes (xii)Submersible pump: Yes(xiii)Auto drain vent: Yes (xiv)Motor speed : As per OEM |
| 4 | S&F water cooler ISI marked of following specifications complete all as specified and directed.(i) Storage capacity : Not less than 120 Ltrs (ii) Cooling capacity : Not less than 60 Ltrs/Hr(iii) Refrigerant : R134a (iv) Number of faucet :2 (v)Cabinet material : Food grade Stain less steel tank(vi)power :single phase, 230 Volts,50Hz, AC (vii)Doors Locking system : yes (viii)Compressor: As per OEM(ix)Drain water tray : Yes (x) Warranty : Not less than one year on product |
| 5 | S&F Refrigerator of capacity not less than 300 Ltrs of following specifications complete all as specified and directed.(i) Compressor type: Inverter (ii) Shelf type:Toughened glass/tempered glass (iii) Number of glass shelves : Not less than 03(iv) Star rating : Not less than 2 (v)Freezer : Covertible (vi) Refrigerant : R600a (vii) Number of doors : Double door (viii) Indoor Cabin light : LED (ix) Power : single phase, 230 Volts,50Hz, AC (x) Colour : As decided by E-In-Charge(xi)Type : Frost free (xii) Warranty : Not less than one year on product & 10 years on Compressor |
| 6 | M & L for Surface Conduit Point wiring with 2.5 Sq mm copper conductor single core PVC insulated cable FRLSH type 1100 V multistranded drawn through conduit and including rigid PVC conduit and conduit accessories of suitable dia medium grade and pressed steel terminal boxes of 1.6 mm thick MS duly painted with red oxide metal primer including fixing/grouting sunken/ surface as per site requirement covered with 3 mm thick laminated hylam sheet including running up of 2.5 Sq mm copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly for fixing the switches/ sockets/ regulators etc complete all as specified and as directed. |
| 7 | S & F in repair switch socket combination flush type multipurpose 5 in 1, 5/16 Amps, 230 Volts complete all as specified and as directed. |
| 8 | M & L for Submain wiring with two single core 4 Sq mm PVC insulated cable FRLSH type copper conductor multistranded 1100 Volts grade drawn through and including rigid PVC conduit and conduit accessories of 25 mm dia medium grade including running up of 4 Sq mm copper conductor multistranded PVC insulated cable as earth continuity conductor along the wiring and connected to the common earth dolly complete including removing and taking down the existing unserviceable sub main wiring and making good the disturbed surface to match with the existing all as specified. Note:-two runs of cable, one run of earth contuinity conductor and one run of conduit shall be measured and paid as one unit length. |
| 9 | S & F in repair single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one double pole MCB 20 Amp complete all as specified and as directed |
| 10 | Taking down existing unserviceable point wiring of any description/type/ size of light/fan/power/two way/bell etc on TW batten/conduit including removal of batten / conduit / gutties / wooden boards / switches / sockets / regulators/ light fittings etc and removal of unserviceable material out of site area and making good the disturbed surfaces of wall/ceiling so as to match with the existing finishes complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender