Tender For Replacement Of Lt Panel With All Other Allied Work At C Block Eok Bps In Kalkaji Constituency Ac-51.
Tender Overview
Project Description
Tender for Replacement Of Lt Panel With All Other Allied Work At C Block Eok Bps In Kalkaji Constituency Ac-51. , Dismantling Of Old Damaged Panel, Removing Of Cable Connection, & Shifting The Same By Heavy Labour At Djb Store , Lt Distribution Panel Sheet Steel Enclosure Made Out Of 2Mm Crca Sheet Totally Enclosed, Powder Coated Free Standing, Floor Mounted Type, Dust& Vermin Proof, Outward Opening, Lockable Doors Having Hidden Hinges And A Bolted Back Cover Both Using Non-Deteriorating Neoprene Rubber Gaskets To Provide Ip-54 Protection. Each Part Of The Fabricated Panel Will Be Strictly Subjected To Seven Tank Treatment. The Various Components, Assemblies And Sub EquipmentS Of The Panel Will Be As Per Standard Given In Relevant Is. The Bus Bar Of The Panel Will Be Shaped Out Of High Conductivity, Electrolytic Conductor And Shall Be Liberal Sized In Aluminum. The Control Wiring Of The Panel Will Be Done With Pvc Flexible Copper Wires Of 1.5Mm Cross Section. Each Wire Will Be Terminating With A Ferule Crimped To The Wire, Size 1200Mm X1000x400mm. Having Following Components Of Approved Make. , Mccb 415V, Four Pole High Breaking Capacity 36Ka 50Hz,200Amp With Spreader - Make L&T/Siemens/ Djb Approved Make. , Mccb 415V, Tp 3Phase High Breaking Capacity 36Ka 50Hz,63Amp With Spreader - Make L&T/Siemens/ Djb Approved Make. , Mcb Single Pole 6Amp. Make L&T/Siemens/ Djb Approved Make. , Mcb Triple Pole 63Amp. Make L&T/Siemens/ Djb Approved Make. , Mcb Triple Pole 32Amp. Make L&T/Siemens/ Djb Approved Make. , Over Load Relay 30-50 annual periodical maintenance Make: L&T/Siemens/ Djb Approved Make. , Over Load Relay 4.5 -7.5 annual periodical maintenance Make: L&T/Siemens/ Djb Approved Make. , Digital Amp. Meter Make Ae/L&T/ Djb Approved Make. , Digital Volt Meter-Make Ae/L&T/ Djb Approved Make. , Motor Protection Relay Make: L&T/Siemens/ Djb Approved Make. , Power Contactor 220V 3Phase 50Amp. Make L&T/Siemens/ Djb Approved Make. , Power Contactor 220V 3Phase 32Amp. Make L&T/Siemens/ Djb Approved Make. , Power Contactor 220V 3Phase18amp. Make L&T/Siemens/ Djb Approved Make. , Star Delta Timer On Delay Make: L&T/Siemens/ Djb Approved Make. , Indicating Lights Led Type Ryb & On/Off Make: L&T /Siemens/ Djb Approved Make. , Current Transformer200/5 Make: L&T/ Djb Approved Make. , Current Transformer 60/5 Make L&T/ Djb Approved Make. , Fitting Of The Above Components In Panel Enclosure With Terminal Blocks, Channels, Ferrules, Thimble, Support Insulator On Bus Bar, Required Hard Wares Complete In All Respect., , Loading, Unloading By Crane Or Heavy Labor And Cartage Up To Site Cleaning & Dressing The Surface For , Installation Of The Panel At Site On Base Frame, Laying Of Cable, Termination Of Cable Both Incoming &Out Going Side , Testing & Commissioning Of Panel, As Per Required Parameters With Relevant Is. Testing Of The Panel Prior To Switching On As Follow : I) Continuity And Earth Testing Ii) Meagering Of All EquipmentS For Phase To Phase, Neutral To Body, Neutral To Earth And Phase To Earth. Iii) Checking For All Tightness Of Nut And Bolts Iv) Alignments Of Doors Etc. Interlocking Tests. All Function Tests
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling of old damaged panel, removing of cable connection, & shifting the same by heavy labour at DJB store |
| 2 | LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection. Each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipment’s of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1200MM x1000x400mm. Having following components of approved make. |
| 3 | MCCB 415V, Four Pole High breaking capacity 36KA 50Hz,200Amp with spreader - Make L&T/Siemens/ DJB approved make. |
| 4 | MCCB 415V, TP 3phase High breaking capacity 36KA 50Hz,63Amp with spreader - Make L&T/Siemens/ DJB approved make. |
| 5 | MCB Single pole 6Amp. Make L&T/Siemens/ DJB approved make. |
| 6 | MCB Triple pole 63Amp. Make L&T/Siemens/ DJB approved make. |
| 7 | MCB Triple pole 32Amp. Make L&T/Siemens/ DJB approved make. |
| 8 | Over load relay 30-50 amp Make: L&T/Siemens/ DJB approved make. |
| 9 | Over load relay 4.5 -7.5 amp Make: L&T/Siemens/ DJB approved make. |
| 10 | Digital Amp. Meter Make AE/L&T/ DJB approved make. |
| 11 | Digital Volt Meter-Make AE/L&T/ DJB approved make. |
| 12 | Motor protection Relay Make: L&T/Siemens/ DJB approved make. |
| 13 | Power contactor 220V 3phase 50Amp. Make L&T/Siemens/ DJB approved make. |
| 14 | Power contactor 220V 3phase 32Amp. Make L&T/Siemens/ DJB approved make. |
| 15 | Power contactor 220V 3phase18Amp. Make L&T/Siemens/ DJB approved make. |
| 16 | Star delta timer on delay make: L&T/Siemens/ DJB approved make. |
| 17 | Indicating lights LED type RYB & On/OFF Make: L&T /Siemens/ DJB approved make. |
| 18 | Current Transformer200/5 Make: L&T/ DJB approved make. |
| 19 | Current Transformer 60/5 Make L&T/ DJB approved make. |
| 20 | Fitting of the above components in panel enclosure with terminal blocks, channels, ferrules, thimble, support insulator on bus bar, required hard wares complete in all respect., |
| 21 | Loading, unloading by crane or heavy labor and cartage up to site cleaning & dressing the surface for |
| 22 | Installation of the panel at site on base frame, laying of cable, termination of cable both incoming &out going side |
| 23 | Testing & commissioning of panel, as per required parameters with relevant IS. testing of the panel prior to switching on as follow :i) Continuity and earth testing ii) Meagering of all equipment’s for phase to phase, neutral to body, neutral to earth and phase to earth. iii) Checking for all tightness of nut and bolts iv) Alignments of doors etc. Interlocking tests. All function tests Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender