Tender For Augmentation / Up-Gradation Of Electromechanical Equipments Along-With Allied Works At 17.08 Mld Stp Brari Numbal (Adv. Cost Of Rs. 1183.00 Lacs)
Tender Overview
Project Description
Tender for Augmentation / Up-Gradation Of Electromechanical Equipments Along-With Allied Works At 17.08 Mld Stp Brari Numbal (Adv. Cost Of Rs. 1183.00 Lacs)
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 24-Sep-2026 | Pre-bid Meeting | Other | 07-Oct-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Part-A: Up gradation of Electromechanical machinery: - Dismantling of existing (10 no) surface aerators in aeration tanks, aerobic digester, Carriage scrapper assembly at the bottom of aeration tank and sludge concentrator including all allied accessories like motors, gear boxes, starters ,fans, cabling etc. along dismantling (02 no) mechanical grit removal assemblies. The job also includes dismantling of Civil structure foundation of Aerator bases. The job also includes shifting of old scrap to the divisional store at Alluchibagh. |
| 2 | Supply, Installation, Testing & commissioning of Mechanical Fine screen SS 304 with length : breadth ratio as 1:3 with thickness of bars as 5 mm and spacing between the bars as 6 mm. It shall have minimum submerged area of 0.50m² -1.0 m² |
| 3 | Supply, Installation, Testing & commissioning of conveyer belt system for the disposal of trash removed by the mechanical screen. The size of the conveyer belt shall be as per site requirement. |
| 4 | Supply, Installation, Testing & commissioning of Manual Fine screen SS 304 with length: breadth ratio as 1:3 with thickness of bars as 5 mm and spacing between the bars as 6 mm. It shall have minimum submerged area of 0.50m² -1.0 m² |
| 5 | Supply, Installation, Testing & commissioning of mechanically operated Scrapper assembly in the grit chambers. |
| 6 | Supply, Installation, Testing & commissioning of Submersible pumps for Raw Sewage Sump with following features:-•Discharge=05 cusec•Head=12 M•Efficiency=70%(Min)•Permissible Soft Solid Size (100mm)•Motor ≤50 H.P•RPM=1500(Sync.),•Operation type :continues •Operation conditions: 415V (+/-10%),50Hz (+/-3%),3-Ø, AC•Pump Standard : IS 5600•Motor standard: IEC60034•Motor Cable: Dual PVC Sheathed, Round type, Copper Conductor (Std)•Installation : Auto coupling with Integral Bend in wet Sump, Vertical Disposition....Contd. as per Annexure A. |
| 7 | Supply, Installation, Testing & commissioning of Submersible pumps for Collection water tank with following features:-•Discharge=07 cusec•Head=17 M•Efficiency=70%(Min)•Permissible Soft Solid Size (100mm)•Motor ≤80 H.P•RPM=1000(Sync.),•Operation type :continues •Operation conditions: 415V (+/-10%),50Hz (+/-3%),3-Ø, AC•Pump Standard : IS 5600•Motor standard: IEC60034•Motor Cable: Dual PVC Sheathed, Round type, Copper Conductor (Std)•Installation : Auto coupling with Integral Bend in wet Sump, Vertical Disposition....Contd. as per Annexure A. |
| 8 | Supply, Installation, Testing & commissioning of Horizontal shaft deposition pumping unit for influent pump house (01 no) with following features:-•Discharge=07 cusec•Head=12 M•Efficiency=70%(Min)•Motor ≤65 H.P•RPM=1000(Sync.),•Operation type :continues •Operation conditions: 415V (+/-10%),50Hz (+/-3%),3-Ø, AC•Inbuilt Intelligent Control System:- Motor overload, single phasing etc.•Pump Casing, Motor Casing, : CI•Shaft :AISI410•Flexible coupling between Motor shaft and Pump shaft ....Contd. as per Annexure A. |
| 9 | Supply, Installation, Testing & commissioning of Horizontal shaft deposition pumping unit (03No’s) in Effluent sump /Treated water tank for reuse or Jhelum Disposal with following features:-•Discharge=07 cusec•Head=17 M•Efficiency=70%(Min)•Motor ≤90 H.P•RPM=1000(Sync.),•Operation type :continues •Operation conditions: 415V (+/-10%),50Hz (+/-3%),3-Ø, AC•Inbuilt Intelligent Control System:- Motor overload, single phasing etc.•Pump Casing, Motor Casing : CI•Shaft :AISI410•Flexible coupling between Motor shaft and Pump shaft•Base frame of suitable ISMC channel.....Contd. as per Annexure A. |
| 10 | Supply, Installation, Testing & commissioning of RAS/SAS Pumps Submersible Type Discharge: 42 LPS Head=15M Motor Rating=10-15 H.P. RPM=1440.The pump sets shall be provided with duct foot pedestal, guide rails, Ultrasonic Level Transmitter, Soft Starter Panel, submersible cable (Power cable, control cable, instrumentation cable each 80 meter length each) including providing fitting and grouting of M.S Stool with the base of aeration tank for resting of duct foot pedestal as per the technical specification enclosed. |
| 11 | Supply, Installation, Testing & commissioning of Air Blowers complete with RCC block, M.S base frame, acoustic enclosure, vibration pads, NRV’s, motorized valves , flexible connections, VFDs, pressure gauge 0-1 bar etc. Capacity=3000 cubic meter/Hr Head=4000 mm of water Motor rating =75H.P. or above as per OEM, rpm =1440 synchronous with design rpm of blower as per the technical specification enclosed. |
| 12 | Supply, Installation, Testing & commissioning of diffusers of flow rate 15 cubic meter/hour capacity of length 1Meter and dia 91 mm with winch type clamping arrangement so that two diffusers are fitted simultaneously on circular pipe on both sides as per details below:-Outer circular ring of aeration tanks (100 LSC+100 RSC) with 50 each on either side of the aeration pipe =200 x2=400 no’s Inner circular ring 1 of aeration tanks (66 LSC+66RSC) =132x 2=264 no’s Inner circular ring 2 of aeration tanks (34 LSC+34RSC) =68x 2=136 no’s, |
| 13 | Supply, Installation, Testing & commissioning of SS-304/316 Pipe 250 mm dia. of thickness 3mm confirming to ASTM standards, to be utilized as main header of Air blowers. |
| 14 | Supply, Installation, Testing & commissioning of SS-304/316 Pipe 200 mm dia. of thickness 3mm confirming to ASTM standards, to be utilized for Air blower distribution. |
| 15 | Supply, Installation, Testing & commissioning of SS-304/316 Pipe 150 mm dia. of thickness 3mm confirming to ASTM standards, to be utilized for air blower distribution for submerged portion within tanks and RAS/SAS piping network. |
| 16 | Supply, Installation, Testing & commissioning of ERW, M.S. pipe confirming to IS 3589, dia. & thickness given below. The job includes cutting of the pipe as per site requirement using gas cutter and welding the joints using welding electrodes of adequate strength and consistency. The M.S pipes to be joined in suitable length segments to be fabricated as per site requirements. The exposed part of pipe (not immersed) shall be painted with steel primer followed by two coats of Enamel paint of approved shade. The immersed portion of vertical suction pipe up to maximum water level shall be coated with two coats of bituminous base anticorrosive paint. 450mm Diameter - 5.4mm thickness (min.) for Raw sump pumps |
| 17 | Supply, Installation, Testing & commissioning of ERW, M.S. pipe confirming to IS 3589, dia. & thickness given below. The job includes cutting of the pipe as per site requirement using gas cutter and welding the joints using welding electrodes of adequate strength and consistency. The M.S pipes to be joined in suitable length segments to be fabricated as per site requirements. The exposed part of pipe (not immersed) shall be painted with steel primer followed by two coats of Enamel paint of approved shade. The immersed portion of vertical suction pipe up to maximum water level shall be coated with two coats of bituminous base anticorrosive paint. 400mm Diameter - 5.4mm thickness (min.)From submersible pumps of treated water tank upto Rising main going into river Jhelum& for reuse treated water line |
| 18 | Supply, Installation, Testing & commissioning of ERW, M.S. pipe confirming to IS 3589, dia. & thickness given below. The job includes cutting of the pipe as per site requirement using gas cutter and welding the joints using welding electrodes of adequate strength and consistency. The M.S pipes to be joined in suitable length segments to be fabricated as per site requirements. The exposed part of pipe (not immersed) shall be painted with steel primer followed by two coats of Enamel paint of approved shade. The immersed portion of vertical suction pipe up to maximum water level shall be coated with two coats of bituminous base anticorrosive paint. 250mm Diameter - 5.4mm thickness (min.)For Delivery Manifold |
| 19 | Supply, Installation, Testing & commissioning of UPVC pipe schedule 40 grades of 100 mm dia to be moulded in circular shape as per contour of 02 clarifier/aeration tanks.01 No. peripheral circular pipe headers running along the contour of clarifier tank and 02 no concentric circular headers running along the contour of central aeration tank. |
| 20 | Supply, Installation, Testing & commissioning of DI ,DF Sluice Valves non-rising type confirming to latest IS specifications of 450 mm dia. with fitting gaskets, nuts/bolts etc. |
| 21 | Supply, Installation, Testing & commissioning of DI ,DF Sluice Valves non-rising type confirming to latest IS specifications of 400 mm dia. with fitting gaskets, nuts/bolts etc. |
| 22 | Supply, Installation, Testing & commissioning of DI ,DF Sluice Valves non-rising type confirming to latest IS specifications of 300 mm dia. with fitting gaskets, nuts/bolts etc. |
| 23 | Supply, Installation, Testing & commissioning of DI ,DF Sluice Valves non-rising type confirming to latest IS specifications of 250 mm dia. with fitting gaskets, nuts/bolts etc. |
| 24 | Supply, Installation, Testing & commissioning of DI ,DF Sluice Valves non-rising type confirming to latest IS specifications of 200 mm dia. with fitting gaskets, nuts/bolts etc. |
| 25 | Supply, Installation, Testing & commissioning of DI, DF Motorized Sluice Valves non-rising type confirming to latest IS specifications of 150 mm dia. with allied gaskets, nuts/bolts etc. |
| 26 | Supply, Installation, Testing & commissioning of DI, DF Butterfly Valves non-rising type confirming to latest IS specifications of 150 mm dia. with allied gaskets, nuts/bolts etc. For Air pipeline |
| 27 | Supply, Installation, Testing & commissioning of DI ,DF NRV(Reflux Valve) confirming to latest IS specifications of 250 mm dia. with fitting gaskets, nuts/bolts etc. |
| 28 | Supply, Installation, Testing & commissioning of DI ,DF NRV(Reflux Valve) confirming to latest IS specifications of 150 mm dia. with fitting gaskets, nuts/bolts etc. |
| 29 | DI Dismantling Joint 450 mm Dia of 16 Bar Rating to the individual delivery as per technical specifications prescribed in the Technical annexure |
| 30 | DI Dismantling Joint 300 mm Dia of 16 Bar Rating to the individual delivery as per technical specifications prescribed in the Technical annexure |
| 31 | DI Dismantling Joint 250 mm Dia of 16 Bar Rating to the individual delivery as per technical specifications prescribed in the Technical annexure |
| 32 | DI Dismantling Joint 200 mm Dia of 16 Bar Rating to the individual delivery as per technical specifications prescribed in the Technical annexure |
| 33 | DI Dismantling Joint 150 mm Dia of 16 Bar Rating to the individual delivery as per technical specifications prescribed in the Technical annexure |
| 34 | Supply, install and commission Motorized sluice gates after grit removal chambers to inlet channel of aeration tanks to be operated both through SCADA |
| 35 | Supply, Erection, Testing & Commissioning of EOT Crane of 2 Ton Capacityspan:as persite requirement,lift:15M including power & control cable as per technical specifications prescribed in the Technical annexure, except the structural steellike columns, rail girder, bridge girder etc. |
| 36 | Supply, Erection, Testing & Commissioning of Steel member for errection of EOT Crane of 2Ton Capacity as per technical specifications prescribed in the Technical annexure \\" |
| 37 | Supply, Installation, Testing & commissioning of 01 ton capacity Monorail Electric Hoist with 10M lift complete assembly in aeration tanks, confirming to latest IS specifications. |
| 38 | Supply, fabrication, Installation, fitting, Testing & commissioning of M.S. platform to be fabricated out of M.S chequered plate 6mm thick over ISMB 150 and ISMC 150 M.S frame work for new Raw Sump |
| 39 | Supply, installation, testing and commissioning of Digital(optical) Type Dissolved Oxygen Meter. |
| 40 | Provision for tube settler media to be fitted inside tube settler tanks with volume fill of (1200 m³) |
| 41 | Supply, install and commissioning of automatic gaseous chlorine dozing system with SKID and pressure control valves (1w+1s), dosing range of 0 to 6 ppm (0 to 10 LPH) comprising of chlorine tonners (6 No.), water feed pump, booster pumps, ejectors, lifting device, leak detection and leak absorbing system, safety equipments like canisters, gas mask etc. compatible with SCADA operation in both auto and manual mode as per the technical specification enclosed with the bid document |
| 42 | Up gradation/Augmentation of the existing tertiary treatment plant at 17.08 by way of Supply, installation, testing and commissioning of 24.5 m³ capacity ACF (01 No) and PSF tanks (01 No),in addition to the existing capacity of 73.5 m³, complete with pumping units, piping net work and other allied works in existing tanks and new tanks and synchronous with operation through SCADA. |
| 43 | Supply, installation, testing and commissioning of Electric Actuators with suitable coupling/arrangement complete with power cables, control cables upto the SCADA system, to the existing valves of the tertiary treatment unit. |
| 44 | Supply, fabrication, Installation, fitting, Testing & commissioning of M.S. covering over the treated water tank to be fabricated out of M.S chequered plate 4mm thick over the ISMC channel M.S frame work. The job includes coating of the steel structure with two coats of bituminous base anticorrosive paint on lower side and shall be painted with steel primer followed by two coats of Enamel paint of approved shade over the upper side of structure. |
| 45 | Supply, Installation, Testing & commissioning of D.G. set 320 KVA as captive power back up along with RCC foundation block with CGI enclosure, CPCB-IV compliant (Latest CPCB norm)complete with Earthing, PLC Control system etc. |
| 46 | Supply, Installation, Testing & commissioning of Cables AL armored XLPE single core 630 Sq mm Double layer from HT transformer to main changeover /ATS switch, D.G Sets, Panels etc. (3 Run for three Phases) |
| 47 | Supply, Installation, Testing & commissioning of Cables AL armored XLPE single core 300 Sq mm Double layer from HT transformer to main changeover /ATS switch, D.G Sets, Panels (1 Run for Neutral Phases) |
| 48 | Supply, Installation, Testing & commissioning of Cables AL armored XLPE 3.5 core 500 Sq mm from bus bar to sub panel, D.G sets etc. |
| 49 | Supply, Installation, Testing & commissioning of Cables AL armored XLPE 3.5 core 150 Sq mm from sub panel to Air blowers, Hz. pumps etc. |
| 50 | Supply, Installation, Testing & commissioning of Main Aluminum bus bar Unit of 1500 Amp TPN with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars support at required intervals complete for cross section, size supports & their spacing etc. The unit self resting & self supporting/Wall mounting system as per IS norms, as per Instructions of Engineer. |
| 51 | Supply, Installation, Testing & commissioning of compartmentalize Modular type Sub control panel(CRCA steel sheet of 2mm thickness )with rotary handle type control MCCB’s on the doors with 4pole 50 KA MCCB 630 Amp (01 no), Aluminum bus bar 630 Amp, 630 Amp Changeover Switch,4 pole 35KA 400 Amp MCCB (01 no) for D.G.set,4 pole 25 KA 200 Amp MCCB(10nos), 4 pole 25 KA 100 Ampere MCCB (07 Nos.), 4 pole 10 KA 63 Ampere MCCB (06 Nos.) and enclosure for installation of VFDs of 04 No. Blowers (to be supplied with air blowers), digital multifunctional meters, for operation of all units along with earthing of panel. The panels shall be fitted inside the store room which shall be evacuated prior to installation. The job also dismantling of front wall and laying of cement concrete flooring in the panel room as per the technical specification. All switch gears shall have Icu=Ics., rating at 415V etc. The contractor has to submit the drawing of Panel mentioning all sub-components therein for approval from Department prior to procurement. |
| 52 | Supply, installation, testing and commissioning of PLC panel comprising of PLC, digital input/output, analogue input/output card with 20% spare capacity. The panel shall also comprise accessories like SMOPS/relay cards/fuse tb for IOS with relay cards for digital output, internal wiring, communication cabling and cablings of all sorts from all electromechanical equipments up-to panel for synchronous operation of all electro-mechanical equipments along with earthing of panel as per the technical specification enclosed. |
| 53 | Supply, installation, testing, commissioning and Operation of SCADA System for synchronized operation of all electromechanical equipment’s along with requisite licensed software(both engineering and operating license) valid for life time with minimum 512 power tags( industrial GRADE PC SCADA system with console desk) ,PC of I-12 processor 256 GB ram, 2-Terabite hard disc, laser jet printer, 5 G internet connectivity, 200AH double battery and 2500 VA Inverter and shall modify operation of electromechanical equipments as per input data. The SCADA System shall be synchronized with raw sewage pumps in both sumps, mechanical fine screen (02 no’s), blowers, RAS/SAS pumps, Effluent transfer pumps, tertiary treatment system, dosing pumps, clear water pumps, effluent transfer pumps, treated water pumps, D.O meters, inlet and out let flow meters and OCEMS so that self-corrective action is generated if there is any deviation of parameters of treated water. The SCADA System shall have bump less UPS backup facility with minimum back up period of 60 minutes. Further the SCADA system shall generate Web -based MIS report and RTU system for transmitting data to PCB website. |
| 54 | 1.1 KV LT TRANSFORMER SUPPLY CONTROL AND CHANGEOVER PANEL: Electric Control Panel: Supplying, installation, testing & commissioning of cubical type floor mounted power distribution panels suitable for 415V, 3 Phase, 4Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, 3 mm thick for gland plates including cleaning & finishing complete with 7 tank process for powder coating in approved shade (RAL 7032), having suitable capacity extensible type FP Aluminum Alloy bus bars of high conductivity aluminum colour coded bus bar sleeves, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MV A for I Sec. with 2 Nos. earth stud, solid connections from main breaker to bus bar to switch gears with required size as per proper calculations of Al. bus bars and control wiring with 1.5 sq.mm....Contd as per Annexure A. |
| 55 | Illumination of the STP premises by way of Supply, installation, testing and commissioning of Aluminum modular solar street light poles 6 meters high along with luminary lights 20 watts (06 nos) with solar panel (75 watt) and lithium-ion batteries(25AH) |
| 56 | Supply, installation, testing and commissioning of 1 MVA Servo stabilizer as per the technical specification enclosed. |
| 57 | Supply, installation, testing and commissioning of Soft Starters 150HP rating (04 Nos) to the existing units as replacement to the old starters. These starters shall be complete in all respects including control cables auxiliary wiring etc. |
| 58 | Rubber Insulation matting :- Supply & Laying of high voltge rubber matting Indian Standard IS 15652, IEC/BS EN 61111:2009, ISI Marked as per the technical specification prescribed in the Technical annexure |
| 59 | Earthing System :- Supply & installation of Chemical Earthing System as per the technical specification prescribed in the Technical annexure |
| 60 | Providing of spares to Elelctromecahnical equipement,Toolkit & PPE kit as per the list given in the Technical annexure |
| 61 | (Part-B Civil): Earth work in excavation by mechanical means (hydraulic excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts,wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth anddisposal of surplus excavated earth as directed, within a lead of 50 metres (All kinds of soil). |
| 62 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth asdirected: (All kinds of soil). |
| 63 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50 m and lift upto 1.5m. |
| 64 | Supply and Laying of dry sotne soling in horizontal on level. |
| 65 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with: |
| 66 | 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 67 | Providing and laying in position specified grade of reinforced cement concrete including curing but excluding the cost of centering, shuttering, finishing and reinforcement. All works upto plinth level. |
| 68 | (1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 69 | 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 70 | Reinforcement for RCC work incl. Straightening cutting, bending, placing in position and binding all complete (Thermo Mechanically Treated Bars). |
| 71 | Centering and shuttering incl. Strutting, propping etc and removal of form work for:- |
| 72 | Foundation, footings, basis of columns etc, mass concrete. |
| 73 | Walls (any thickness) incl. Attached pilasters buttresses, plinth and string courses. |
| 74 | 15mm Cement plaster on the rough side of single or half brick wall of mix 1 : 6 ( 1 cement : 6 fine sand) |
| 75 | Providing corrugated G. S. sheet roofing including vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and G.I limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/vertical or curved surface)excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required (0.80 mm thick with zinc coating not less than 275 gram/m2). |
| 76 | Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.(In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works) |
| 77 | Provision for Painting for Civil Structures as per Directions of Engineer-In-Charge (Complete Job). |
| 78 | Carriage of Materials by Mechanical Transport from Source to site of work: - |
| 79 | Stone soling from Athwajan Avg. 12kms |
| 80 | Stone Agg. 40mm & above from Athwajan Avg. 12kms. |
| 81 | Stone Agg. Below 40mm from Athwajan Avg. 12kms. |
| 82 | Sand from Ganderbal Avg. 18kms |
| 83 | Cement and Steel from Source Avg. 6kms |
| 84 | Bricks from Budgam Avg. 20 Kms. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 1 dayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender