Tender For Rki , Kaippad Project- Electrification Works Of Organic Input Unit, Organic Marketing Unit And Agro Service Centre Building At Pattuvam, Kannur
Tender Value
24.24 Lakhs
Estimated cost
Bid Submission
24 Sep 2026
8 days left
EMD
50000
Bank guarantee accepted
Document Fee
2500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kannur → Kerala
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Rki , Kaippad Project- Electrification Works Of Organic Input Unit, Organic Marketing Unit And Agro Service Centre Building At Pattuvam, Kannur
BOQ
| Sl. No. | Item Description |
| 1 | WIRING |
| 2 | 1.10.1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVCconduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group A |
| 3 | 1.10.2Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVCconduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B |
| 4 | 1.10.3Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 5 | 1.14.1Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire |
| 6 | 1.14.2Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | 1.14.3Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 8 | 1.21.1Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 9 | 1.21.2Supplying and fixing of following sizes of medium class PVC conduit along withaccessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.25 mm |
| 10 | 1.21.3Supplying and fixing of following sizes of medium class PVC conduit along withaccessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.32 mm |
| 11 | 1.21.4Supplying and fixing of following sizes of medium class PVC conduit along withaccessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.40 mm |
| 12 | 1.24.1Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 13 | 1.24.4Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 14 | 1.26Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required |
| 15 | 1.27.1Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 16 | 1.27.2Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 17 | 1.27.3Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm) |
| 18 | 1.31Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 19 | 1.32Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 20 | 90.4.5.4Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper windingsuitable for 230V/240V single phase AC supply |
| 21 | 1.25Supplying and fixing two module stepped type electronic fan regulator on the existingmodular plate switch box including connections but excluding modular plate etc. asrequired. |
| 22 | OD91000/2026-2027Supply, conveyance, installation, testing and commissioning of the following sizesof exhaust fans in the existing opening,fixing necessary bolt and nuts, makinggood the damages etc. as required including giving connections with requiredlength of 24/0.20mm PVC insulated and PVC sheathed 3 core round copperconductor flex wire conforming to relevant ISS. 200 mm sweep Light Duty Exhaust fan in plastic body with self opening lowers working on 230V single phase A/C. |
| 23 | 1.55.1Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bellpoint ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copperconductor single core cable in surface/ recessed PVC conduit, and earthing the pointwith 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group A |
| 24 | 1.55.2Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bellpoint ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copperconductor single core cable in surface/ recessed PVC conduit, and earthing the pointwith 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required . Group B |
| 25 | 1.55.3Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bellpoint ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copperconductor single core cable in surface/ recessed PVC conduit, and earthing the pointwith 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 26 | 1.57Supplying & fixing suitable size Gl box wih modular plate and cover in front onsurface or in recess including providing and fixing 25 A modular socket outlet and 25A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. lCD |
| 27 | OD130869/2026-2027Supplying and angle /straight brasslined modular Bakelite batten holder with 7WLED lamp and giving connection etc as required |
| 28 | 90.3.19.3Supply conveyance, installation, testing and commissioning the light fittings offollowing types made from CRCA sheet 0.5mm thickness with all accessories andlamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulatedand sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture |
| 29 | 90.15.3.1Supply installation testing commissioning of Octogaonal Pole made of hot dipgalvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mmbase plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 PartIII single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters |
| 30 | 90.15.4.2Supply Conveyance, installation, testing and commissioning of 36/40W LED streetlight output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chipmake Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internalsurge protection up to 8 KV,and Aluminium pressure die-cast Powder coatedhousing,acrylic cover complete with THD less than 10%, power factor greater than0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chipmanufacturer) |
| 31 | 90.15.4.3Supply Conveyance, installation, testing and commissioning of 70W LED street lightoutput greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip makeCree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surgeprotection up to 8 KV,and Aluminium pressure die-cast Powder coatedhousing,acrylic cover complete with THD Less than 10%, power factor greater than0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chipmanufacturer) |
| 32 | 90.15.4.5Supply Conveyance, installation, testing and commissioning of 40W LED Flood lightoutput greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip makeCree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surgeprotection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHScompliant, duly wired up for use on 230 V AC supply. Driver compartment should beseperatly accessible for maintenance (LM 79&80 certificates from NABLaccredited Third party lab to be produced mentioning chip manufacturer) |
| 33 | 90.15.4.6Supply Conveyance, installation, testing and commissioning of 70W LED Flood lightoutput greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip makeCree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surgeprotection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates fromNABL accredited Third party lab to be produced mentioning chip manufacturer ) |
| 34 | 1.14.4Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire |
| 35 | DB AND DB ACCESSORIES |
| 36 | 2.4.1Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 Way (4+12) Double door |
| 37 | 2.4.2Supplying and fixing following way, horizontal type three pole and neutral, sheetsteel, MCB distribution board, 415 volts, on surface / recess, complete with tinnedcopper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)6 Way (4+18), Double door |
| 38 | 2.4.3Supplying and fixing following way, horizontal type three pole and neutral, sheetsteel, MCB distribution board, 415 volts, on surface / recess, complete with tinnedcopper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)8 way(4+24), Double door |
| 39 | 2.5.1Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (butwithout MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 WAY(4+12), DOUBLE DOOR |
| 40 | 2.5.2Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (butwithout MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 Way(4+24), Double door |
| 41 | 2.5.3Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (butwithout MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)12 WAY(4+36),Double door |
| 42 | 2.10.1Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 43 | 2.10.4Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 44 | 2.11Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 45 | 2.12.1Supplying and fixing following rating, double pole, 240 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 46 | 2.12.2Supplying and fixing following rating, double pole, 240 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 47 | 2.13.1Supplying and fixing following rating, four pole, 415 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 48 | 2.13.2Supplying and fixing following rating, four pole, 415 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 49 | 2.14.1Supplying and fixing following rating, double pole, (single phase and neutral),240volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps |
| 50 | 2.14.2Supplying and fixing following rating, double pole, (single phase and neutral),240volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps |
| 51 | 2.15.1Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 52 | 2.15.2Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 53 | 2.15.3Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 54 | 2.18Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2pole and earth,metal enclosed plug top along with 20 amps \\"C\\" curve, SP, MCB, insheet steel enclosure, on surface or in recess, with chained metal cover for the socketout let and complete with connections, testing and commissioning etc. as required. |
| 55 | 2.19Supplying and fixing 20 A,415volts, TPN industrial type, socket outlet, with 4 poleand earth, metal enclosed plug top along with 20 amps \\"C\\" curve, TPMCB, in sheetsteel enclosure, on surface or in recess, with chained metal cover for the socket out letand complete with connections, testing and commissioning etc. as required. |
| 56 | 90.14.28.1S & F Motor starters of the following ratingsSingle phase DOL starters for 0.25HP to3HP motor |
| 57 | 90.14.28.4S & F Motor starters of the following ratingsSemiautomatic star delta starter for 5 to7.5HP motor |
| 58 | OD129224/2026-2027Supply and installation of FP metal MCB enclosure |
| 59 | 2.14.3Supplying and fixing following rating, double pole, (single phase and neutral),240volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps |
| 60 | CABLE TRAYS |
| 61 | 4.6.1Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 100 mm width X 50mm depth X 1.6 mm thickness |
| 62 | 4.6.2Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I.suspenders including G.I. bolts & nuts, etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 63 | 4.6.4 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I.suspenders including G.I. bolts & nuts, etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 64 | 4.7.1Supplying and installing following size of perforated Hot Dipped Galvanized Ironcable tray \\"bends\\" (galvanization not less than 50 microns) with perforation not morethan 17.5%, in convenient sections, joined with connectors, suspended from theceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100mmwidth X 50 mm depth X 1.6mm thickness |
| 65 | 4.7.2Supplying and installing following size of perforated Hot Dipped Galvanized Ironcable tray \\"bends\\" (galvanization not less than 50 microns) with perforation not morethan 17.5%, in convenient sections, joined with connectors, suspended from theceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150mmwidth X 50mm depth X 1.6mm thickness |
| 66 | 4.7.4Supplying and installing following size of perforated Hot Dipped Galvanized Ironcable tray \\"bends\\" (galvanization not less than 50 microns) with perforation not morethan 17.5%, in convenient sections, joined with connectors, suspended from theceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.300mmwidth X 50mm depth X 1.6mm thickness |
| 67 | 4.8.1Supplying and installing following size of perforated Hot Dipped Galvanized Ironcable tray \\"Tee\\" (galvanization not less than 50 microns) with perforation not morethan 17.5%, in convenient sections, joined with connectors, suspended from theceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100 mmwidth X 50 mm depth X 1.6 mm thickness |
| 68 | 4.8.2Supplying and installing following size of perforated Hot Dipped Galvanized Ironcable tray \\"Tee\\" (galvanization not less than 50 microns) with perforation not morethan 17.5%, in convenient sections, joined with connectors, suspended from theceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mmwidth X 50 mm depth X 1.6 mm thickness |
| 69 | 4.8.4Supplying and installing following size of perforated Hot Dipped Galvanized Ironcable tray \\"Tee\\" (galvanization not less than 50 microns) with perforation not morethan 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 70 | 4.10.1Supplying and installing following size of perforated Hot Dipped Galvanised Ironcable tray \\"Reducer\\" (galvanisation not less than 50 microns) with perforation notmore than 17.5%, in convenient sections, joined with connectors, suspended from theceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mmwidth x 50 mm depth x 1.6 mm thickness |
| 71 | 4.10.2Supplying and installing following size of perforated Hot Dipped Galvanised Ironcable tray \\"Reducer\\" (galvanisation not less than 50 microns) with perforation notmore than 17.5%, in convenient sections, joined with connectors, suspended from theceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mmwidth x 50 mm depth x 1.6 mm thickness |
| 72 | 4.10.4Supplying and installing following size of perforated Hot Dipped Galvanised Ironcable tray \\"Reducer\\" (galvanisation not less than 50 microns) with perforation notmore than 17.5%, in convenient sections, joined with connectors, suspended from theceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 mmwidth x 50 mm depth x 1.6 mm thickness |
| 73 | OD129227/2026-2027Supply, installation, testing and commissioning of UnPerforated Cable tray withcover/Ceiling Raceway closed with snap fit lid confirming to IEC-61537. The Trayshall be galvanized for corrosion protection confirming to DIN EN 10346 / ISO 1461.The Ceiling Raceway shall be supplied with cover with the standard length of 3 Mtr .100 mm x 60 mm |
| 74 | EARTHING |
| 75 | 5.4Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 76 | OD129228/2026-2027Supply of all materials and providing Rod Earthing using 20mm Dia 3 mtr longcopper coated steel electrode with all required accessories and adding earthconductivity enhancing mineral compound(25kg), construction of RCC earth chamber and covering with Heavy duty RCC Chamber Cover of size 450 x 450mm including excavation of earth pit. Rod Earth Station |
| 77 | 90.16.1.3Supply and drawing bare earthing conductors of the following sizes along withwiring/ cables and giving connection as required3.15 mm copper conductor ( 10SWG) |
| 78 | 90.16.1.4Supply and drawing bare earthing conductors of the following sizes along withwiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 79 | 90.16.3.3Supply and clamping the following size of strips on surface of wall/ parapet/ existingcable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy dutyGI spacer saddles spacing of clamps not exceeding 1 m, making good the damages,colour washing etc. as required ( for horizontal run)25 x 6 mm GI strip |
| 80 | 90.16.4.3Supply and clamping the following sizes of strips on surface of wall / parapet/existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted orheavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good thedamages, colour washing etc. as required ( for vertical run).25 x 6 mm GI strip |
| 81 | 90.16.3.5Supply and clamping the following size of strips on surface of wall/ parapet/ existingcable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy dutyGI spacer saddles spacing of clamps not exceeding 1 m, making good the damages,colour washing etc. as required ( for horizontal run)32 x 6 mm GI strip |
| 82 | 90.16.4.5Supply and clamping the following sizes of strips on surface of wall / parapet/existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted orheavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good thedamages, colour washing etc. as required ( for vertical run).32 x 6 mm GI strip |
| 83 | 90.16.3.9Supply and clamping the following size of strips on surface of wall/ parapet/ existingcable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy dutyGI spacer saddles spacing of clamps not exceeding 1 m, making good the damages,colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip |
| 84 | 90.16.4.8Supply and clamping the following sizes of strips on surface of wall / parapet/existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted orheavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good thedamages, colour washing etc. as required ( for vertical run).25 x 3 mm copper strip |
| 85 | 90.16.3.10Supply and clamping the following size of strips on surface of wall/ parapet/ existingcable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy dutyGI spacer saddles spacing of clamps not exceeding 1 m, making good the damages,colour washing etc. as required ( for horizontal run)25 x 6 mm copper strip |
| 86 | 90.16.4.9Supply and clamping the following sizes of strips on surface of wall / parapet/existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted orheavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good thedamages, colour washing etc. as required ( for vertical run).25 x 6 mm copper strip |
| 87 | 5.19Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 88 | CABLING AND TERMINATION |
| 89 | 90.12.37.21Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 35 sq mm |
| 90 | 90.12.37.22Supply & laying of one number PVC insulated and PVC sheathed armoured copperpower cable of 1.1KV grade of the following sizes in ground including excavation oftrench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 50 sq mm |
| 91 | 90.12.37.24Supply & laying of one number PVC insulated and PVC sheathed armoured copperpower cable of 1.1KV grade of the following sizes in ground including excavation oftrench of size 35 x 75 cm, refilling the trench etc. as required but excluding sandcushioning and protective covering (in ordinary soil).3.5 core 95 sq mm |
| 92 | 90.12.41.21Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredcopper power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.3.5 core 35 sq mm with factory made clamp |
| 93 | 90.12.41.35Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredcopper power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.4 core 25 sq mm with factory made clamp |
| 94 | 90.12.41.34Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredcopper power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 95 | 90.12.41.33Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredcopper power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 96 | 90.12.41.32Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredcopper power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.4 core 6 sq mm with factory made clamp |
| 97 | 90.12.41.3Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredcopper power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.2 core 10 sq mm with factory made clamp |
| 98 | 90.12.38.5Supply and Laying of one number additional PVC insulated and PVC sheathedarmoured copper power cable of 1.1KV grade of the following sizes in ground in thesame trench in one tier horizontal formation including widening the trench by 20 cm,refilling the trench etc. as required but excluding sand cushioning and protectivecovering (in ordinary soil)3 core 4 sq mm |
| 99 | 90.12.41.2Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredcopper power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.2 core 6 sq mm with factory made clamp |
| 100 | 90.12.41.1Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredcopper power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.2 core 4 sq mm with factory made clamp |
| 101 | 90.12.40.5Supply & laying of one No. PVC insulated and PVC sheathed armoured copperpower cable of 1.1 KV grade of the following sizes in the existing masonry open ductas required.3 core 4 sq mm |
| 102 | 9.1.24Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm) |
| 103 | 9.1.22Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 104 | 9.1.21Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 105 | 9.1.34Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.4 X 25 sq. mm (28mm) |
| 106 | 9.1.33Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 107 | 9.1.32Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 108 | 9.1.2Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.2 X 10 sq. mm (19mm) |
| 109 | 9.1.1Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.2 X 6 sq. mm (19mm) |
| 110 | 90.6.6.4Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 corecopper conductor flat cable for submersible pump motor conforming to IS 694 part I1990 as required including giving necessary connections of the following sizes.6 sqmm |
| 111 | SWITCH BOARD |
| 112 | OD130085/2026-2027Supply, erection, testing and commissioning of the following cubicle type dust andvermin proof free standing, floor mounting panel boards with top /bottom entry forcables and complete with all interconnections, powder coating, control wiring etc. asper approved drawings, IS, CEA Regulations and General conditions/ Technicalspecifications.Incomer- RYB Indication lamp - 1 set.150/5A 0.5s 5VA CT operated 3ph KWh meter-1.150A cut out fuse unit - 3 nos with neutral link.Outgoings - 160A 25kA 4P thermal magnetic release MCCB - 1 no. |
| 113 | OD130095/2026-2027Supply erection, testing and commissioning of the following cubicle type dust and vermin proof free standing, floor mounting panel boards with top /bottom entry for cables and complete with all interconnections, powder coating, control wiring etc. as per approved drawings, IS, CEA Regulations and General conditions/ Technicalspecifications.MSBa) Incomer -160A FP 18kA Microprocessor based 3 o/c+ IE/F release MCCB- 1 No.Provision for 160A FP Isolator for future - 1 No.b) Outgoing -125A TP+N TM MCCB, 18kA - 1 No.100A TP+N TM MCCB, 18kA - 3 Nos.80A TP+N TM MCCB, 18kA - 1 No.63A TP+N TM MCCB, 18kA - 2 Nos.c) Busbar System -160A TPN Aluminium Bus Bars of suitable length. Bus bars shall be colour codedand insulated by heat shrinkable sleaves & clip on shrouds for joints. The currentdensity of Bus bar shall be 0.8 sq.mm. / amp. |
| 114 | OD130097/2026-2027Supply erection, testing and commissioning of the following cubicle type dust andvermin proof free standing, floor mounting panel boards with top /bottom entry forcables and complete with all interconnections, powder coating, control wiring etc. asper approved drawings, IS, CEA Regulations and General conditions/ Technicalspecifications.SSB -A) Incomer:100A FP Isolator -1 No.B) Metering & Indications:R-Y-B Indication Lamps - 1 Set suitable for 230 V AC fittings with back upMCB/Fuse.C) Outgoing 1:63A FP MCB, 10kA - 2 Nos.32A FP MCB, 10kA - 2 Nos.25A FP MCB, 10kA - 1 No.D) Busbar System:100A TPN Aluminium Bus Bars of suitable length. Bus bars shall be colour codedand insulated by heat shrinkable sleaves & clip on shrouds for joints. The currentdensity of Bus bar shall be 0.8 sq.mm. / amp |
| 115 | OD130098/2026-2027Supply erection, testing and commissioning of the following cubicle type dust andvermin proof free standing, floor mounting panel boards with top /bottom entry forcables and complete with all interconnections, powder coating, control wiring etc. asper approved drawings, IS, CEA Regulations and General conditions/ Technicalspecifications.SSBA) Incomer:125A FP Isolator -1 No.B) Metering & Indications: R-Y-B Indication Lamps - 1 Set suitable for 230 V AC fittings with back up MCB/Fuse.C) Outgoing 1:63A FP MCB, 10kA - 2 Nos.32A FP MCB, 10kA - 2 Nos.25A FP MCB, 10kA - 1 No.D) Busbar System:125A TPN Aluminium Bus Bars of suitable length. Bus bars shall be colour codedand insulated by heat shrinkable sleaves & clip on shrouds for joints. The currentdensity of Bus bar shall be 0.8 sq.mm. / amp |
| 116 | OD130100/2026-2027Supply erection, testing and commissioning of the following cubicle type dust and vermin proof free standing, floor mounting 40kVAr APFC panel boards with top /bottom entry for cables and complete with all interconnections, powder coating, control wiring etc. as per approved drawings, IS, CEA Regulations and General conditions/ Technical specifications.a) Incomer: 100A TPN Isolator -1 No.MFDM with suitable CTs-1 Set.R-Y-B Indication Lamps - 1 Set suitable for 230 V AC fittings with back up MCB/Fuse. 8 stage automatic power factor controller relay with Auto manual selector switch.b) Outgoing:2 kVAR MPP type capacitor banks with 16A TP MCB- 1Nos.3 kVAR MPP type capacitor banks with 16A TP MCB - 1Nos.5 kVAR MPP type capacitor banks with 25 A TP MCB - 2Nos.10 kVAR MPP type capacitor banks with 32 A TP MCcB - 1Nos.15 kVAR MPP type capacitor banks with 32 A TP MCcB - 1Nos.Indicating lamp in each capacitor chamber unit to indicate \\"ON\\"/\\"OFF\\" status of capacitor unit.c) Busbar System : 100A TPN Aluminium Bus Bars of suitable length. Bus bars shall be colour coded and insulated by heat shrinkable sleaves & clip on shrouds for joints. The current Ndensity of Bus bar shall be 0.8 sq.mm. / amp |
| 117 | MISCELLANEOUS |
| 118 | 2.21Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mildsteel, at least 2 mm thick, and vitreous enameled white on both sides, and withinscription in single red colour on front side as required. |
| 119 | OD129230/2026-2027Supply and fixing of IP65 junction box with terminals and PG Gland 88mm x 88mmx 53mm |
| 120 | OD129231/2026-2027Supply and fixing of shock treatment chart laminated in suitable frame |
| 121 | OD129232/2026-2027Supply and laying of 440V grade Synthetic Insulated mat 2 meter x 1 meter conforming to IS:15652:2006 |
| 122 | OD129233/2026-2027Supply and laying of DCP type fire extinguisher 5 Kg. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 14, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 24, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.