Educational and Research Institute Government Departments Closing in 0 days TDR #57505621

Tender For Repair Of Overhead External H.T/L.T Network And Substations At New University C Us, Jammu

Issued by Government Departments · Jammu, Jammu and Kashmir
Tender Value
12.12 Lakhs
Estimated cost
Bid Submission
21 Sep 2026
0 days left
EMD
4998
Bank guarantee accepted
Document Fee
1180
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jammu → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Repair Of Overhead External H.T/L.T Network And Substations At New University C Us, Jammu

BOQ

Name of Work:- Repair of overhead External H.T/L.T Network and Substations at New University C us, Jammu
Sl. No. Item Description
1Earthing with following size of earth plate including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/coke and salt as required.(600X600X6) mm G.I
2P/f of strips on surface/in recess for connections as reqd.6 mm SWG G.I wire
3Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other joining materials for following size of 3 core XLPE AL conductor cable of 11 KV grade as reqd.120 sq mm
470 sq.mm
5Erection of metallic pole of following length in cement concrete 1:3:6 ( 1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling and secured with holding clamps, bolts, nuts etc. as required. a. Above 8 meter upto 11 meter.
6b. Above 6.5 meter upto 8 meter.
7Erection of ACSR conductor of 7/2.11 mm to 7/3.00 mm diameter including binding etc. as required.
8Erection of ACSR conductor of 7/3.35 mm to 7/4.00 mm diameter including binding etc. as required.
9Supply and erection of Stay Set complete(galvanised) with 19/20 mm dia x1.8 meter long stay rod, Anchor plate of size 45 cm x 45 cm x 7.5 mm, thimble, stay clamps, turn buckle (20mmX60mm) 7/3.15 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 1:3:6 (1 cement: 3 corse sand:6 graded stone aggregate 40 mm nomial size) foundation including excavation and refilling etc as reqd.
10Supply and erection of galvanized ‘D’ iron clamps complete with shackle insulator (100 mm x 110 mm), G.I bolts, nuts and washers, coach screws etc. as required.
11Supply and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts washers etc as reqd.
12Supply of swaged type steel tubular pole of following height duly painted with two coats of red oxide and two coats of silver paint made of Mild Steel conforming to IS 2713 part III of 1980 designated as 410 SP 30 HT 9 mtr planted in 1.5 m deep pole pit to be dug for the purpose, welded with (300x300x6) mm base plate at bottom including filling back the pit with cement concrete excavation 1:3:6 (1 cement: 3 corse sand:6 graded stone aggregate 40 mm nomial size) (excluding the cost of CC). The planting depth of the pole shall be 1/6 th 0f pole a) 9 mtr height.
13Non-Schedule Items Supply of swaged type steel tubular pole of following height duly painted with two coats of red oxide and two coats of silver paint made of Mild Steel conforming to IS 2713 part III of 1980 designated as 410 SP12 LT 8 mtr planted in 1.5 m deep pole pit to be dug for the purpose, welded with (300x300x6) mm base plate at bottom including filling back the pit with cement concrete excavation 1:3:6 (1 cement: 3 corse sand:6 graded stone aggregate 40 mm nomial size) (excluding the cost of CC). The planting depth of the pole shall be 1/6 th 0f pole a) 8 mtr height.
14Supply of swaged type steel tubular pole of following height duly painted with two coats of red oxide and two coats of silver paint made of Mild Steel conforming to IS 2713 part III of 1980 designated as 410 SP57 13mtr planted in 1.5 m deep pole pit to be dug for the purpose, welded with (300x300x6) mm base plate at bottom including filling back the pit with cement concrete excavation 1:3:6 (1 cement: 3 corse sand:6 graded stone aggregate 40 mm nomial size) (excluding the cost of CC). The planting depth of the pole shall be 1/6 th 0f pole a) 11 mtr height.
15Providing fixing testing and commissioning of 11KV link set.
16Providing fixing testing and commissioning of 11 KV station type lightening arrestor set of three piece nonlinear resistor, suitable for 3 wire, 11KV overhead lines with rated voltage 9KV (rms) with normal discharge current rating of 5KA complete with G.I clamping arrangement G.I bolts, nuts washers etc as required.
17Supply installation testing and commissioning of post type/ Horn gap type 11KV Triple Pole drop out fuse unit fitted with fuse element. (D.O. Set)
18Supply of following size ACSR conductor of required aluminum and steel strands including binding etc. as required as per IS O 398 part 2a) 7/2.11 mm to 7/4mm
19Providing & fixing lock type clamps /thimbles made of brass or copper of required size for L.T/H.T bushings of 250 to 630 KVA transformers.
20Painting of previously painted swaged type Tubular poles of following size with silver paint (One or more coat) of approved brand and manufacture.Make (Asian/Nerolac)a) 4.0 mtr height
21Painting of previously painted swaged type Tubular poles of following size with silver paint (One or more coat) of approved brand and manufacture.Make (Asian/Nerolac)a) 8.0 mtr height
22Painting of previously painted swaged type Tubular poles of following size with silver paint (One or more coat) of approved brand and manufacture.Make (Asian/Nerolac)a) 9.0 mtr height
23Reconditioning of the coils of Al. Wound Distribution Transformer of following rating including painting with suitable coat of enamaled paint.a. 250 KVA To 630 KVA
24Reconditioning of the coils of Copper wound Distribution Transformer of following rating including painting with suitable coat of enamaled paint.a. 250 KVA To 630 KVA
25Rewinding of 250 to 630 KVA rating of Distribution transformers with suitable size HV/LV leg new coil made of Aluminium Super Enamel Coil/DPC as per the requirement of original existing winding including painting the transformer with weather proof paint of approved brand as per IS code.
26Rewinding of 250 to 630 KVA rating of Distribution transformers with suitable size HV/LV New leg coil made of Copper Super Enamel Coil/DPC as per the requirement of original existing winding including painting the transformer with weather proof paint of approved brand as per IS code.
27S/F of HV bushing of following rating Distribution Transformer.a. 250 KVA
28S/F of HV bushing of following rating Distribution Transformer.a. 400 KVA
29S/F of HV bushing of following rating Distribution Transformer.a. 630 KVA
30S/F of LV bushing of following rating Distribution Transformer.a. 250 KVA
31S/F of LV bushing of following rating Distribution Transformer.a. 400 KVA
32S/F of LV bushing of following rating Distribution Transformer.a. 630 KVA
33S/F of HV bush Rod of following rating Distribution Transformer.a. 250 KVA
34S/F of HV bush Rod of following rating Distribution Transformer.a. 400 KVA
35S/F of HV bush Rod of following rating Distribution Transformer.a. 630 KVA
36S/F of LV bush Rod of following rating Distribution Transformer.a. 250 KVA
37S/F of LV bush Rod of following rating Distribution Transformer.a. 400 KVA
38S/F of LV bush Rod of following rating Distribution Transformer.a. 630 KVA
39S/Filling of Filtered Dehydrated Transformer oil.
40S/F of Transparent Silica gel breather for following rating Distribution Transformer.a. 250 KVA TO 630 KVA
41S/F of Phase Separator with insulation between coils for the following rating Distribution Transformer.a. 250 KVA To 630 KVA
42P/F of Arching horn assembly for 11 KV bushing of following rating Distribution Transformer.a. 250 KVA TO 630 KVA
43P/F of suitable rating Al bus bars for L.V connections of following rating Transformer.a. 250 KVA TO 630 KVA
44Shifting of following rating Distribution Transformer from one site to another site with in the 3 KM Campus including Crane Charges for loading and unloading.a. 250 KVA TO 630 KVA
45Shifting of following rating Distribution Transformer from one site to the workshop and Vice-Versa including Crane Charges for loading and unloading at site as well as at Workshop.a. 250 KVA TO 630 KVA
46Filtration and Dehydration of the existing Transformer Oil including filling in the repaired transformer
47Supply, fabrication of following sizes of channels, angles and flat iron including drilling holes for insulators and painting with primer and silver paint.A)Channel (75x40x6)mm
48….do…. Angle (50x50x6)mm
49….do…. Flat iron clamps suitable for LT/HT poles (50x6)mm.
50Supply and installation of Copper Maintenance free Chemical Earthing System. Electrode size length 3000x dia 50mm with CU pipe Thickness 2.10mm. CU inner and terminal strip size 32x6mm with GSI backfill compound 2 No’s Bag (40-45kg) per Earthing. The Chemical Earthing system tested and certify/ recommended resistance value in normal soil 00.95 ohms max. decaying -0.02 per year, Conductivity as per IS 3043 Code including cost of 5 Rmt copper Strip.
51Construction of Platform of size 8’-0”x5’-0”x4’-0” (ht) for electric substation with cement concrete 1:4:8 (1cement:4sand :8crushed stone aggregate 20mm nominal size) with 50% stone boulders including cost of formwork, curing, earthwork in excavation(1’-0”)depth, laying of 6” thick layer of cement concrete 1:4:8 in foundation, consolidation, plastering the exposed vertical surface of platform with cement mortar1:4(1 cement:4 sand) P&L of 75 mm thick cement concrete with 1:2:4(1cement:2 sand:4 graded stone aggregate 20mm nominal size) at top of the platform. Note:- Total height of the platform shall be 4”-0” which would include 1’-0” below the ground and 75 mm thick cement concrete laid at top of platform..
52Cleaning of the sub stations by the way of removing of jungle grass/bushes or any other unwanted vegetation/plants
53Pruning/Branch cutting of trees on emergency basis for clearing of electric line (HT/LT) network near the sub stations and near main 11 KV VCB control panel for rectification of faults and restoration of power supply as and during the contract period by providing the services for Fitter/Lineman.
54Providing and making bottoming for steel/PCC pole with cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 stone aggregate 20mm) of 18’ dia and 18” height for round shape or 18” side and 18’ height for square shape above the ground level including formwork, plastering if required and curing etc. as required.
55Supply/laying of following size of 3-core 11 KV graded HT XLPE insulated inner sheath of PVC,Galvanised steel flat strip or round/ Armoured (U.E) cable confirming to IS 7089Part-2.2011 with upto date amendments (Havells/polycab/gloster/General Equivalent make of required specification to be approved by the Engineer In charge)120 sqmm 3 core
5670Sqmm 3 core
57Supply,Laying, testing and commissioning of PVC sheathed Aluminum conductor 1100 volts graded PVC AA Armoured/unarmoured XLPE Cable including end termination, crimping, cost of thimbles, nuts bolts, glands, connection, testing and commissioning complete job. (Make: Havells / General/Polycab / Gloster) Equivalent make of required specification to be approved by the Engineer In charge) 300 sq mm armoured cable single core
58Dismantling of L.T cable connection from the L.T line pole including end termination,fixing the insulating tape,cleaning the carbon accomolated and reinstallation the same at various service line connection wherever required.
59Dismentling of pole/street light standard /trut embedded in brick ballast foundation etc. as required
60Dismantling/Disconnection of Electrical Sub Station including disconnection of the L.T & HT cable of Distribution Transformer and reconnection of the Distribution Transformer after repair with LT&HT cable complete job. The Job includes the Disconnection of the earthing system and refixing after the transformer is repaired.
61P/F M.V danger notice plate of (200x150) mm made of mild steel at least 2mm thick and vitreous enameled white on both side and with inscription in single red colour on front side as reqd.
62Cement concrete Flooring 1:2:4 (1 Cement 2 coarse sand : 4 graded stone aggregate) finshed with afloating coat of neat cement including cement slurry and curing complete, 40mm thick with 20 mm nominal size stone aggregate
63Supply and Installation Three Phase 5 wire spacer for L.T Line
64LT fuse switch made of angle iron with 50X50X6mm, with Aluminium busbar strip 50X6mm fuse on busbar insulator including clamps for sixing of switches
65Providing the and laying in position cement concrete of specified grade including curing Excuvation. Shuttering. 1:5:10(1 cement : 5coarse sand : 10 graded stone aggregate 40 mm nominal size) Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57505621
AUTHORITY Government Departments
TENDER VALUE 12.12 Lakhs
LAST DATE 21-09-2026
Authority
Authority Name Government University
Work Description Tender for Repair Of Overhead External H.T/L.T Network And Substations At New University C Us, Jammu
Basic Detail
Tender No enit 240 dated 11-9-2026
Bidding Type Tender
Location
City Jammu
State Jammu and Kashmir
Key Dates
Publish Date 14 Sep 2026
Submission Date 21 Sep 2026
Open Date 24 Sep 2026
Finance
Tender Value 12.12 Lakhs
Tender Fee 1180
EMD 4998
Exemption Not Available
Document List
bdfdc124-0cde-40dc-a4e8-cd97890e12a4.html
BOQ_1094945.xls
Tendernotice_1 (20).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 14, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 21, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Sep 24, 2026

Bid Opening Date

Technical bids will be opened and evaluated.