Tender For Special Repair Of Lighting Conductor/Arrester And Allied Work At 2Asd (23Fad) At Mil Stn Beas Under Ge Kapurthala
Tender Value
28.88 Lakhs
Estimated cost
Bid Submission
03 Oct 2026
18 days left
EMD
57760
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kapurthala → Punjab
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Special Repair Of Lighting Conductor/Arrester And Allied Work At 2Asd (23Fad) At Mil Stn Beas Under Ge Kapurthala
BOQ
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : Garrison Engineer Kapurthala Name of Work : Special repair of lighting conductor/arrester and allied work at 2ASD (23FAD) at Mil Stn Beas under GE Kapurthala Contract No : GE KPT- /2026-27 Bidder Name : SCHEDULE OF WORKS(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # S.No Description of work Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Repair to the existing earthing (GI/copper plate earthig) with provision of new layers of back filling compound (BFC) and salt all as specified in electrical plate No 3 of SSR Part-I, including cleaning of existing GI/Copper earth plate, conductors etc, connecting with new bolts, nuts and washers including replacement of watering pipe, funnel with wire mesh, earth lead and protection pipe including necessary testing on complete all as specified and directed.Note:- (i) Excavation will be measured & paid under relevent item No.(ii) Watering pipe, funnel with wire mesh will be measured & paid under relevent item No. |
| 3 | Supply only funnel made out of aluminium sheet in conical shape, dia of the funnel should be similar to existing funnel complete all as specified and as diirected. |
| 4 | Supply only light grade GI pipe 20 mm dia for watering in earthing pit complete all as specified and directed. |
| 5 | Supply only light grade GI pipe 40 mm dia for protection of earthing lead, water piping complete all as specified and directed. |
| 6 | Supply only salt suitable for earthing pit complete all as specified and directed. |
| 7 | M&L for providing BFC (Back filling compound chemical) in 25 kg of bag, earth conductivity enhancing compound to level chemical the existing chemical earth pit including taking out mud from existing earth pit and cleaning complete all as specified and directed. |
| 8 | M&L in repair for PCC earth pit cover and supply and fixing/laying of prefabricated RCC earth pit cover of size 60cm x 60cm X 50mm made using RCC 1:2:4 type B0 (using 12.5mm graded stone aggregate) and 8mm dia Fe-500 grade TMT reinforcement bars @ 140mm center to center on both ways, including two nos 8mm dia TMT bar handles embedded into pit cover complete all as specified and directed. |
| 9 | M&L for repair of earth pits of internal dimensions 60cm x 60 cm x 60 cm making good disturbed/dismantled brick work in cement mortar (1:4) plastering surfaces in cement mortar 1:6, 15mm thick and PCC coping in cement concrete 1:2:4 type B-1 (a) M&L for brick work using sub class 'B' (old size bricks) in cement mortar 1:4 (b) M&L for rendering 15 mm thick including plastering inside and outside of earthpit (c) Excavation in any type of soil, Returning, Filling in and Removal of surplus Spoil disposal to out side MoD landcomplete all as specified and directed. |
| 10 | M&L in replacement for \\"Test Point Terminal Block\\" made of gun metal or phosphorus bronze of having size 75 X 75 X 25 mm drilled and screwed by providing 3 nos 8 mm dia 25 mm long hexazonal head screw and connected to Copper/ Aluminium / GI strips complete housed in a PVC junction box after taking down old one complete all as specified and directed.Note:- (i) The test points will be properly fixed on epoxy insulators. Cost of epoxy insulators are inclusive of unit rate quoted by the contractor.(ii) PVC junction box will be paid and measured separately under item . |
| 11 | S&F of 4 digit electromechanical lightning event counter in weather proof enclosure. The counter should give the number of strikes intercepted by lightning arrestercomplete all as specified and directed. |
| 12 | S&F in repair air termination single pointed aluminium rod not less than 12mm dia and 300mm long end threaded all as specified and as directed. |
| 13 | S&F in repair air termination single pointed copper rod not less than 12mm dia and 300mm long end threaded after taking down old one complete all as specified and directed. |
| 14 | S&F in repair post insulator epoxy LV type suitable for copper/aluminium/ GI strip 25 x 4 mm lightening conductor fixed on wall/roof/pole including screw after taking down old one complete all as specified and directed. |
| 15 | S&F in repair post insulator cetrally threaded epoxy LV type suitable for holding threaded aluminium/ copper AT rod 12 mm dia fixed on stand post including screw after taking down old one complete all as specified and directed. |
| 16 | Taking down old defective conductor strips of any type/description (i.e GI, Aluminium & copper strip) from wall/ roof and making good to the disturbed surfaces to match the existing surface complete all as specified & directed. |
| 17 | S&F in repairs aluminium strip of size 25 x 3 mm fixed to wall/ pole with aluminium saddles and screws for roof/ down conductor above ground/ buried in ground/ drawn in conduit/ fixed to poles or any other indicated situation for loop earthing including connected upto test terminal point complete all as specified and directed.Note:- Insulators/conduit/pipe shall be measured and paid separately under appropriate items here in after |
| 18 | S&F in repairs copper strip of size 20 x 3 mm fixed to wall with copper saddles and screws drawn in conduit/ fixed to poles or any other indicated situation for loop earthing including connected upto test terminal point complete all as specified and directed.Note:- Insulators/conduit shall be measured and paid separately under appropriate items here in after |
| 19 | S&F in repairs fixing Galvanised iron strip of size 32 x 6 mm fixed to wall with Galvanised iron saddles and screws / buried in ground/ drawn in conduit/ fixed to poles or any other indicated situation for loop earthing including connected upto test terminal point complete all as specified and directed.Note:- Insulators/conduit/pipe shall be measured and paid separately under respective item of works |
| 20 | S&F in repair Junction box IP 65 with plain walls of size 167mm x 125mm x82mm made up of polystyrene having shutter and lifting knob with provision of earth strip entry glands fixed to walls or pole with nuts, bolts, washers and testing complete all as specified and directed. |
| 21 | S&F in repair 32 mm bore class 3 grade PVC pipe for protection of earth strip completein trenches / fixed to walls/ fixed to poles with suitable clamps at 0.5 meter apart span complete all as specified and directed. Note:- Rates for flat iron clamps, bolts, nuts and washer etc are deemed to be included in rate quoted) |
| 22 | Labour charges to carry out earth resistance test with well calibrated suitable earth resistance tester after opening the test points and recording the result in presence of MES representative complete all as per IS 3043 of 1966.Note:- (i) The result should be recorded in the result sheet and on building at place directd.(ii) Testing equipment & ladder has to be arranged by the contractor on his own.The quoted rate is deemed to be inclusive of this provision. |
| 23 | M&L for earthing with galvanised earth plate electrode 600x600x 6mm thick buried directly in ground (earth pit not less than 2.25m below ground level) with top edge of the plate not less than 1.50 m below ground level, connected with gi strip of size 32x 6 mm by means of bolts, nuts, check nuts and washers of GI or steel and connected earthing testing point/bus-bar including GI 40mm bore (dia) light grade protection pipe, earth plate surrounded by a packed thickness of char coal or coke dust mixed with common salt, magnesium sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC pit in cement concrete 1:3:6 (20mm graded stone aggregate) and pre-cast RCC cover slab of size 350x350x50 mm in cement concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT bars @ 100mm centre to centre in both ways, GI wire mesh, funnel with GI watering pipe 20mm bore (dia) medium grade including necessary excavation in any type of soil, returning, filling in and removal of surplus spoil disposal to out side MoD land and all as shown in electrical plate no. 3 of MES schedule Part-l and testing on completion including taking down old unserviceable one complete all as specified and directedNotes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.00 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. |
| 24 | Earthing with copper earth plate electrode 600x600x3.15mm thick burried directly in ground (earth pit not less than 2.25 metre below ground level) with top edge of the plate not less than 1.50 metre below ground level, connected with copper earth strip of size 20x3mm by means of bolts, nuts, check nuts and washers of copper and connected earthing testing point/bus-bar including GI 40mm bore (dia) light grade protection pipe, earth plate surrounded by a packed thickness of char coal or coke dust mixed with common salt, magnesium sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC pit in cement concrete 1:3:6 (20mm graded stone aggregate) and pre-cast RCC cover slab of size 350x350x50 mm in cement concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT bars @ 100mm centre to centre in both ways, GI wire mesh, funnel with GI watering pipe 20mm bore (dia) medium grade including necessary excavation in any type of soil, returning, filling in and removal of surplus spoil disposal to out side md land and all as shown in electrical plate no. 3 of MES Schedule Part-l and testing on completion including taking down old unserviceable one complete all as specified and directed. Note:- (i) Main earthing strip from earth plate electrode to test point upto length of 7.00 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. |
| 25 | M&L for installing and commissioning copper coated chemical earthing electrode of length 3 mtr, inner dia of 40 mm and outer pipe of dia 76 mm with minimum thickness of 250 micron, after boring 20 metre deep, 150 mm in dia in hard/soft soil with help of boring machine, filling the bore hole with black cotton soil upto 17 mtrs level i.e below the electrode bottom level, filling remaining portion by pouring suitable chemical bentonide compound duly mixed with water and filling earth enhancement material (minimum approx. 30 kg) into the augured hole in slurry form and allowed to set, covering of the composite structure (earth electrode + earth enhancement material), covering remaining portion with backfill soil/ material, welding copper strip 20 x 3mm with existing head of earth electrode including necessary PCC earth pit work and including all necessary nut, bolts, washers etc complete all as specified and directed. Note:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.0 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance (less than 5 Ohms) is not obtained the contractor shall redo the earthing without any extra cost to the department. |
| 26 | M&L for prepration of new IDENTIFIER/ MARKER madeout of preferably metalic of size 30cm x 20cm x 2mm thick metalic board fixed on MS Angle 30 x 30 x 5 mm of 450 mm long to be fixed to ground by means of cement concrete including painting with two coats of synthetic enamel paint over a coat of red oxide primer and writting the earth resistance complete and coloured with following colour coading to identify.(a) For Chemical Earth Pits - RED color(b) For conventional/ Maintenance free earth pits- YELLOW colour.(c) Lightning Arrester Earth - LE (Trangular shape)(d) LT Panel earth/ UPS earth -PE (Square shape)(e) Height of the identifier should be 60cm above the ground level all as directed. |
| 27 | M&L for testing,commissioning & installation of lightning arrester ESE LA 107 m radius supply of early streamer emission (ESE) lightning protection complete with lightning air terminal. The system should be corrosion resitant street stainless steel chrome body capable of working in hazardous atmoshphere and prottection against direct lightning point as well conducting / diverting it to earth completly after tracing the lightning in advance as per NFC 17-102:2011 certification the Air Terminalshould be tested for switrching implus current of 40 KA and for Local CPRI with 5 Possitive and 1 negative impluse. The ESE air terminal shall offer a protection radius of 107m high protection FRP Insulator with the mast complete with the following connected fittings and fixtures :-(a) L.A. Accessories GI MAST 5MTR 50MM DIA upply of GI Mast 5 Meter hight along with suitable base plate for mounting the terminal along with highly insulated adopter to the mount ESE Air Terminal with the Mast Adapter shall have suitable Metal connecting point with the Stay wire shall be securely fixed the Base Plate. - 01 Nos(b)L.A. Accessories strike counter 6 DIGIT Supply of Lightning Strike Counter ( 6 Digit display)of non ressistable(electromechanical) Type which allow the automatic counting of the strike received by the lightning Protection system. This information used to enhance lightning protection security & increase the effectiveness of inspection & maitenance procedures.it should in IP-65 enclouser with minimum sensitivity of 1 KA & maximum capacity 100KA .No external Power source is required- 01 Nos(c) L.A. Accessories INSULATOR ESE LA - 01 Nos (d) L.A. Accessories ROPEWIRE 3 MM - 01 Nos |
| 28 | (e) Earthing Electrode 17.2/3 MTPCBR Model:, Length (mtr):, Terminal Size:, Inner Strip:, Outer Pipe Diameter (min) mm:, THK:, Model:, Length (mtr):, Terminal Size:, Inner Strip:, Outer Pipe Diameter (min) mm:, THK: Supply of maintenance free tripod earthing system for ESE technology Lightning Conductor (3 Nos. per set) of 17mm x3mtr Steel High Tensile EN-8D Grade Rod with Copper Bonding of minimum 250 microns, having pre-welded copper bonded connection clamp at top and M17 threaded at bottom for coupler attachments, clamp head assembly, prewelded and copper bonded connection clamp, having provision to connect external cables & strips, back fill compound (BFC) 2x25 Kg highly conductive resistivity lowering ground enhancement compound tested & certified by National Test House (Govt.of India Lab) as per IEC 62561-7 and ASTM G57-06 for a resistivity of 0.244 ohms-mtr with advanced heavy duty polyplastic earth inspection pit coverhaving unique design and lockable made of high grade polypropylene complete all as specified and directed - 03 Nos(f)Single core copper cable COPPER CABLE 70 SQ MM Supply of 70 Sqr Mm Single core Copper Cable for Down Conductor upto 35 RM or as per site requirement. (g) Installation of LA and Accessories test link box single Bus Bar. Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 12, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 03, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysOct 05, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender