Tender For Supply Installation Testing and Commissioning of Ht Vcb Panel Alongwith Streetlights And Allied External Electrical Works At Stp/Etp, Pgimer Satellite Centre, Sangrur (Punjab).
Tender Overview
Project Description
Tender for Supply Installation Testing and Commissioning of Ht Vcb Panel Alongwith Streetlights And Allied External Electrical Works At Stp/Etp, Pgimer Satellite Centre, Sangrur (Punjab).
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 14-Sep-2026 | The list of clause no. 1.2.5 may be read as | Technical Bid | 17-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | SUB HEAD - ELECTRICAL INTERNAL WORK : |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 3 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 7 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). |
| 8 | Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material andconstruction as per IS : 10322 with driver Replaceable) as per the equirement with Driver efficiency >85%, Operating voltage AC 140270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation |
| 9 | Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Nam Engraved/embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) |
| 10 | 18-22 Watt |
| 11 | SUB HEAD - STREET LIGHT WORK : |
| 12 | Supply of Aluminum conductor multistrand XLPE insulated armoured & served cable of following sizes and rating. |
| 13 | Aluminum conductor XLPE insulated armoured & served cable working voltage 1100 volts grade 4-Core, 10sqmm.. |
| 14 | Supply of Aluminum conductor multistrand XLPE insulated armoured & served cable of following sizes and rating. |
| 15 | Aluminum conductor XLPE insulated armoured & served cable working voltage 1100 volts grade 4-Core, 25sqmm. |
| 16 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/HDPE pipe as required. |
| 17 | Upto 35sqmm |
| 18 | Supply & drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 19 | 3 X 1.5sqmm |
| 20 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cmbelow ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 21 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 22 | Earthing with G.I. earth pipe 4.5 metre long, 40mm dia including accessories, and providing masonary enclosure with cover plate and having locking arrangement and watering pipe extra with charcoal/ coke and salt as required. |
| 23 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with G.I. thimble etc. as required. |
| 24 | Supply & erection of 7 mtr long Hot dipped galvanized pole of octagonal cross-section continuously tapered made out from high tensile steel of minimum thickness 3mm complete with the base plate of minimum size 200mm X 200mm X 12mm, foundation bolts along with inbuilt junction box, termination of cable with lugs, connectors for the cable termination and with supply & fixing of one number 6amps single pole MCB, C-curve, 10KA for each luminaries. The diameter from across the dimensions of the base plate and top should be minimum 130mm and 70mm A/F (Across Face). The size of the pole and foundation bolts shall be suitable to withstand the maximum wind speed/ pressure as per IS-875. There shall be not any circumferential welding on the pole. The method and material shall comply with as BSEN-10025 grade S355 or equivalent poles should be hot dipped galvanized in single dip to 70 microns min confirming to IS 2629-1966. |
| 25 | The material and specifications of flange plate/ base plate shall be as per IS 2062. The poles shall be erected in the RCC foundation with special foundation bolts 'J' type minimum M24 X 750mm long galvanized M.S. Rod duly threaded in the existing RCC foundation of suitable size as per the approved drawing. The material of the steel bolts shall be confirming to grade EN-8 exposed threaded portion of foundation bolts shall be hot dipped galvanized. |
| 26 | Providing cement concrete foundation with the following specifications including excavation and finishing the surface. |
| 27 | The foundation base shall be constructed with cement concrete gatka of ratio 1:5:10 of size 600mm X 600mm X 100mm high. |
| 28 | RCC foundation shall be constructed from cement concrete mixture M-20 grade of ratio 1:1.5:3 of size 500mm X 500mm X 1100mm high, (including 100mm projection above the ground level) above the foundation base. (including removal of malba from site)complete in all respect as required. |
| 29 | Reinforcement with Tor-steel should be as Under: |
| 30 | Horizontal rings made from 8mm dia = 6Nos |
| 31 | Vertical rods made from 10mm dia 38” long = 6Nos |
| 32 | Complete in all respect as required on site. |
| 33 | Supply & erection of G.I. Pipe bracket having 1.5 mtr long arm duly welded on G.I. Pipe canopy of suitable length and thickness. Bracket shall have minimum suitable angle of inclination 15 degree for mounting streetlight luminaries and having proper fixing arrangement as required. Design of bracket should be existing bracket design installed on infront of Nehru reception poles. |
| 34 | Single arm bracket |
| 35 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt) |
| 36 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70,under voltage and over voltage protection, EMI EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K |
| 37 | (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 38 | 72 watt |
| 39 | SITC of time lite DB , IP 54 MS Enclosure duly power coated , with outdoor stand mounted of housing 63 Amp TPN MCB incomer, Astronomical Timer Switch switch, TP contactor for its automatic switching 4 no.s outgoing of 16 A,including termination of cable from main panel and in time lite DB with installation of the feeder pillar by grouting the stand of 4 no. legs in concrete as suitable for feeder pillar and complete in all respect as required on site. The Drawing of the streetlight panel should be got approved before fabrication from engineer in charge. |
| 40 | SUB HEAD -ELECTRICAL SUB-STATION WORK : |
| 41 | HT PANEL:- (INCOMER CUM OUTGOING) |
| 42 | Supply, Installation, Testing and Commissioning of indoor type floor mounted MV board type tested as per IEC 62271-100 and the metal clad enclosure istype tested as per IEC 62271-200, 11 kV, 800A VCB Panel with totally enclosed,expendable & electrically interlocked, horizontal drawout, horizontal isolation type breaker as per IS 13118, as per specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and closing breaker suitable for use on 11kV, 3Phase, 50Hz A.C. supply with short circuit fault level of 350 MVA, complete with self contained electrically interlocked rack in and rack out mechanism, air insulated & encapsulated tinned copper bus bars of 800 ampere capacity, breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 3Cx 300*sq.mm. XLPE 11kV cable Panels Should be type tested for internal Arc 26.3 KA for 1 Sec.11KV 800A trolley mounted VCB shall be accepted. (cable entry from bottom, end termination with heat shrinkable jointing material etc. as required.) |
| 43 | VCB Panel must consisting of following |
| 44 | 11kV, 800A, 26.3KA for 3 sec with spring charging motor rated for 230V AC, tripping coil and closing coil at 110V DC. |
| 45 | 1 No. Microprocessor based numerical relay with O/L, E/F and S/C protection compatible for automation System & comply to IEC 61850. |
| 46 | Trip Circuit spervision relay. |
| 47 | Master Trip Circuit Relay |
| 48 | Digital Ammeter |
| 49 | Multifunction Meter With Modbus Communication |
| 50 | Fuses/MCB as per requirement |
| 51 | Plug & Socket |
| 52 | L/R switch |
| 53 | TNC Switch |
| 54 | Energy meter |
| 55 | Emergency Push Button |
| 56 | Indicating lamp set of standered 8 nos. |
| 57 | Powerpack (230V AC to 110V DC) with 10-15 Min Back up |
| 58 | BUSBAR AND BUSCHEMBER |
| 59 | 800 ampere air insulated & encapsulated tinned Copper Bus Bar |
| 60 | HT PANEL for ETP |
| 61 | OUTGOING FEEDER -01 nos. VCB Panel consisting of following - |
| 62 | Dual core dual ratio set of 3 nos. CT 100-50/5-5A, CL1.0/5P10 10VA for each core |
| 63 | PT set of 3 nos. 11000/√3 // 110/√3 V, CL1.0 50VA ( DRAWOUT TYPE ) |
| 64 | Aux. relays for Transformer protection |
| 65 | Digital Voltmeter |
| 66 | Energy meter |
| 67 | 6 window annunciator with Common hooter |
| 68 | As above |
| 69 | Filteration and Dehyderation of 500 KVA transformer oil with high vaccume filteration plant of minimum 5KL,per hour capacity for minimum four cycles and continue up to the required BDV value.Job aslo includes cleaning of conservator,draning of oil as required and filling the same in tank/conservator.The charges aslo includes for skilled and unskilled manpower,carrier of empty drum/ tankers & dehyderated machine etc.Allied tools to get the job of repair and dehydration of transformer done. |
| 70 | Supply and replacement of silica gel crystal. |
| 71 | Supply of New transformer oil conforming IS: 335 |
| 72 | Testing of transformer : The Job includes following testing. |
| 73 | Insulation resistance test HV-E, HV-LV,: P-P, P-E |
| 74 | Trasnformer turn ratio test |
| 75 | Winding resitance test |
| 76 | Primary injection from HT side |
| 77 | Magnetic curent test LV Supply from LV side |
| 78 | As above |
| 79 | supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: |
| 80 | 300 sq. mm |
| 81 | Less credit for old 11 kV, 800A VCB Panel complete in all respect including removal of the same from the PGI premises. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 2 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender