Tender For Annual Rate Contract For The Work Of Construction Of Open Wells, Supply, Installation And Commissioning Of Pump Sets And Providing, Laying, Jointing And Testing Of Di & Hdpe Pipelines With Interconnection Works Under For For Sub Division K
Tender Overview
Project Description
Tender for Annual Rate Contract For The Work Of Construction Of Open Wells, Supply, Installation And Commissioning Of Pump Sets And Providing, Laying, Jointing And Testing Of Di & Hdpe Pipelines With Interconnection Works Under For For Sub Division Kumbhalgarh Under Jurisdiction Of Phed Division Rajsamand With One Year Defect Liability Period.
BOQ
| Sl. No. | Item Description |
| 1 | Earth work in excavation over areas (exceeding 30cm depth, 1.5 mtr in width and 10 SQM in plan) for construction of open well, lift up to 1.5 Mtr. including taking out the excavated soil and disposal of surplus excavated soil as directedwithin a lead of 50 meter. |
| 2 | All Type of Soil |
| 3 | 0 to 3 mtr. |
| 4 | ordinary rock 3 to 6 mtr. |
| 5 | IN HARD ROCK ( REQUIRED BLASTING) |
| 6 | 6 to 24 mtr |
| 7 | Add extra over item No. 2.39.1 for every additional lift of 1.5 Mtr. or part thereof : In all kind of soils. |
| 8 | 1.5 to 3 mtr. |
| 9 | Add extra over item No. 2.39.1 for every additional lift of 1.5 Mtr. or part thereof : In Ordinary Rock and Hard rock In ordinary rock and hard rock |
| 10 | 3 to 4.5 mtr. |
| 11 | 4.5 to 6 mtr. |
| 12 | 6 to 7.5 mtr. |
| 13 | 7.5 to 9 mtr. |
| 14 | 9 to 10.5 mtr. |
| 15 | 10.5 to 12 mtr. |
| 16 | 12 to 13.5 mtr. |
| 17 | 13.5 to 15 mtr. |
| 18 | 15 to 16.5 mtr. |
| 19 | 16.5 to 18 mtr. |
| 20 | 18 to 19.5 mtr |
| 21 | 19.5 to 21 mtr. |
| 22 | 21 to 22.5 mtr. |
| 23 | 22.5 to 24 mtr. |
| 24 | 24to 25.5 mtr. |
| 25 | Add 20% extra over item No. 2.39 for excavation in saturated soil where pumping or baling out of water is required, including shoring strutting where required and dewatering. |
| 26 | From 1 m to 25 m BGL |
| 27 | Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel props and removal of formwork for upto floor five level for : |
| 28 | Walls (any thickness) including attached pilasters, buttresses plinth and string course. |
| 29 | Add extra for shuttering in circular work (in respective centering and shuttering items) 20% |
| 30 | Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor five level. ('Original producers' who manufacture billet directly from iron ores and roll the bilets to produce steel conforming to IS:1786) |
| 31 | Thermo-mechanically Treated bars (Conforming of relevent IS code) |
| 32 | Providing and laying cement concrete including curing, compaction etc. complete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, levelling course etc up to floor five level excluding the cost of centering and shuttering. |
| 33 | M20 grade Nominal Mix 1: 1.5: 3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size). |
| 34 | Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide |
| 35 | Random rubble stone masonary for foundation and plinth in cement sand mortar above 30 cm thick wall in: |
| 36 | Cement Mortar 1:4 ( 1 cement : 4 Sand ) |
| 37 | Random Rubble stone masonry with hard stone in superstructure above plinth level and upto five level above 30cm. thick walls in : |
| 38 | Cement Mortar 1:4 ( 1-Cement : 4-Sand). |
| 39 | Plaster on new surface on wall in cement sand mortar 1:3 including racking of joints etc. complete fine finish : |
| 40 | 20 mm thick |
| 41 | Finishing wall with water proofing cement paint of approved brand and manufacture and or required shade to give an even shade including all scaffolding: |
| 42 | New work (Two or more coats applied @ 3.84 kg/10 sqm). |
| 43 | Painting one thin coat with white lead of approved brand and manufacture on wet or patchy portion of plastered surfaces. |
| 44 | New steel work ( two or more coats) |
| 45 | Labour charges for horizontal boring 100 mm dia in open well in rocky strata with all types of rock cutting & drilling tools etc. including all T&P required for job including dewatering arrangement. |
| 46 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc. |
| 47 | All kinds of soil |
| 48 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and stacking serviceable material for measurements and disposal of unserviceable material as directed, with in a lead of 50 Mtr. including all safety provisions required .: |
| 49 | Ordinary rock |
| 50 | Hard rock (requiring blasting) |
| 51 | Hard rock(blasting prohibited) |
| 52 | Dismantling of flexible pavement for pipe line line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks per technical specification and scope of work. |
| 53 | Bituminous courses |
| 54 | Granular courses |
| 55 | Dismantling of cement concrete pavement for pipe line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work. |
| 56 | Providing and laying in position cement concrete M10 grade nominal mix 1:3:6 (1 Cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size) in base course complete including all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, complete work as per technical specification and scope of work. |
| 57 | Providing and laying in position cement concrete in specified grade over prepared base course complete including finishing, curing, all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, complete work as per technical specification and scope of work. |
| 58 | M20 grade Nominal Mix1: 1.5: 3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size). |
| 59 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended up to date), with internal cement mortar lining suitable for potable water with rubber ring (EPDM) joints as per IS: 5382-1985 including all taxes (Central and local), transportation and freight charges, inspection charges, loading/ unloading charges, including cost of labour and material, specials (Tee, bend etc.) satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge. (excluding earth work)Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately. |
| 60 | 80 mm |
| 61 | 100 mm |
| 62 | 150 mm |
| 63 | Providing, lowering, laying and jointing in trenches, standard lengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended up to date) with necessary jointing material like mechanical connectors,i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by butt fusion/ electro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer in-charge of following class and diameter. (excluding earth work) .Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply may be in coil or straight length in 6 M/12 M. |
| 64 | HDPE PE-80 PN-6 |
| 65 | 63 mm dia |
| 66 | 75 mm dia |
| 67 | 90 mm dia |
| 68 | 110 mm dia |
| 69 | 125 mm dia |
| 70 | 140 mm dia |
| 71 | HDPE PE-100 PN-6 |
| 72 | 63 mm dia |
| 73 | 75 mm dia |
| 74 | 90 mm dia |
| 75 | 110 mm dia |
| 76 | 125 mm dia |
| 77 | 140 mm dia |
| 78 | HDPE PE-80 PN-10 |
| 79 | 90 mm dia |
| 80 | 110 mm dia |
| 81 | HDPE PE-100 PN-10 |
| 82 | 90 mm dia |
| 83 | 110 mm dia |
| 84 | P&F G.I.Pipes (External Work ) with G.I. fittings excluding union (IS 1239 Mark ) including trenching and earth filling etc . |
| 85 | 65 mm dia nominal bore b class |
| 86 | 65 mm dia nominal bore b class |
| 87 | 80 mm dia nominal bore b class |
| 88 | Providing, lowering, laying, aligning, fixing in position and jointing at all level/ depths DI standard specials with rubber ring (EPDM)/ nut bolt and insertion sheet and jointing as per IS: 9523-2000 or as amended up to date, such as tees, bends, tapers, caps etc. within trenches in DI pipe line complete including all material, labour, taxes, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge (excluding earth work). |
| 89 | All End Socketed |
| 90 | Upto 300 mm Diameter |
| 91 | Above 300mm and up to 600 mm diameter |
| 92 | All End Flanged |
| 93 | Upto 300 mm Diameter |
| 94 | Above 300mm and up to 600 mm diameter |
| 95 | Single Flange/ MJ Collar |
| 96 | Upto 300 mm Diameter |
| 97 | Above 300mm and up to 600 mm diameter |
| 98 | Double Flange Pipe (up to 1 mtr. length) |
| 99 | Upto 300 mm Diameter |
| 100 | Above 300mm and up to 600 mm diameter |
| 101 | Providing, lowering, laying, aligning, fixing in position at all level/ depths CI Class - B specials as per IS : 1538, amended up to date in trenches complete including all material, labour, testing and commissioning along with pipe line/ appurtenance as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. |
| 102 | Plain ended CI specials including tail piece, spigot end and socket end. |
| 103 | Up to 300 mm dia |
| 104 | Above 300 mm and up to 600 mm dia |
| 105 | Double flanged CI pipe fittings. |
| 106 | Up to 300 mm dia |
| 107 | Above 300 mm and up to 600 mm dia |
| 108 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete including all taxes, material, labour, inside lining, outside coating, testing and commissioning along with pipe line as per technical specifications and direction of Engineer- in-charge. |
| 109 | MS pipe specials up to 600mm dia (with minimum 5mm thickness sheet) |
| 110 | Providing Household Tap Connection as per technical specification and approved drawing as per relevant IS code (amended up to date) from HDPE/uPVC/DI/AC/MS/GI pipe line up to consumer meter/premises by using PP mechanical Integrated saddle with inbuilt flow control valve made out of SS316 designed for 5 LPM discharge at 0.5 bar pressure , not exceeding the flow of 7 LPM at 2 bar and a compression elbow, moulded in single piece/ fusion welded (Complete job) including digging out suitable size of pits and trench for laying service line in all kinds of soil; depositing and refilling of pit &jhiri with watering & ramming/compacting in layers and disposal of surplus excavated soil as directed with in a lead of 100 meter ; providing & fixing of all fitting duly approved in accordance with specification for potable water including GM Full-way Valve (IS:778 Mark) or wheel valve and specials with 20 mm nominal dia MDPE pipe PE 80 PN 16 as per ISO 4427 / 20 mm nominal dia PPR C (Three layered) pipe PN16 SDR 7.4 (IS:15801:2008) (ISI mark) and above ground level using PPR-C pipe with standard PPR fittings/ GI pipes in the premises for fixing a tap / meter box (excluding) ,including accessories with flushing, cleaning, disinfecting and testing of pipe line complete required for making of service connection complete in all respect including labour charges . The service line should be laid at least 45 cm below ground level.Note: Road cut and restoration is not part of this item and paid separately. |
| 111 | For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 mtr |
| 112 | Add extra over item no 11.01 above for providing 20 mm PE 80 PN 16 as per ISO 4427 MDPE pipe including excavation, providing, laying & jointing of service line above 5.00 mtr. |
| 113 | Road cutting for house hold service connection in minimum trench width wherever road crossing is required. Road cutting of cement concrete,WBM, Black top etc. of all thickness shall be done by using a concrete cutter machine keeping minimum trench width and restoration of the road with Cement concrete with PCC M-10 and CC M-30 grade as per specification and direction of Engineer in charge.. |
| 114 | Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves) , Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN- 1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG- 400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanised rubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS AISI 316/410 Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 115 | Manually Operated CI Sluice valve of Class PN-1.0 |
| 116 | 80 mm HW |
| 117 | 100 mm HW |
| 118 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 119 | 80 mm dia |
| 120 | 100 mm dia |
| 121 | 125 mm dia |
| 122 | 150 mm dia |
| 123 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, DI Body Flanged End Tamper proof Kinetic Air Valve of approved makes of following pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(amended up to date) Body, High pressure cover , Low pressure cover, Cowl and Joint support ring - Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865,Float- LP ball & HP ball : AISI 304 stainless Steel, Seat ring & Gasket - EPDM/NBR ,HP Orifice & HP orifice plug : Bronze/ SS ,Bush: Bronze,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & cover inside and outside fasteners - CS/ Galvanised steel, Outlet of big orifice will have a screen to prevent Tamper of float, with DI metal seated D/F Non rising stem Sluice Valves as per (IS: 14846 amended up to date) PN 1.6 ratings Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 124 | Class PN 1.6 |
| 125 | 40 mm dia |
| 126 | 50 mm dia |
| 127 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, combination Air Release Valve Kinetic type with single chamber housed Double orifice and have 3 functions, large Air exhaust, small Air venting and large air intake during vacuum of pipeline of approved makes of following pressure rating and dia and as per following specifications: Governing standard - AWWA C512 ,Body and bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG- 400/12 as per IS 1865,Float & internal trim: AISI 304 stainless Steel, Seat ring & Gasket - EPDM/NBR Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & cover inside and outside Fasteners - CS/ Galvanised steel,Outlet of big orifice will have a screen to prevent Tamper of float, Big orifice size should be equal or larger than the inlet flange bore, for fully comply with AWWA C512. ), Valve including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 128 | Class PN 1.6 |
| 129 | 50 mm dia |
| 130 | 80 mm dia |
| 131 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (Suitable for Sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning Technical Specifications and as per direction of Engineer. Class PN 1.0 |
| 132 | 80 mm dia |
| 133 | 100 mm dia. |
| 134 | 125 mm dia. |
| 135 | 150 mm dia. |
| 136 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15 as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as per specifications and standard drawings and as per direction of Engineer-in-Charge. |
| 137 | For Class-AA loading |
| 138 | Sluice valve chamber of size 1.13 m x0.85 m x1.325 m- for pipe size-up to 100 mm |
| 139 | Sluice valve chamber of size 1.17m x 0.95m x1.47mfor pipe size-from 125-to-150mm |
| 140 | For Class-A loading |
| 141 | Sluice valve chamber of size1.13m x0.85m x1.27m for pipe size-upto100mm |
| 142 | Sluice valve chamber of size1.17m x0.95m x1.415m for pipe size-from 125-to-150mm |
| 143 | For in-campus Valve Chambers |
| 144 | Sluice valve chamber of size1.13m x0.85m x1.225m for pipe size-upto100mm |
| 145 | Sluice valve chamber of size1.17m x0.95m x1.37m for pipe size-from 125-to-150mm |
| 146 | Construction of RCC Air valve chamber for different type of valves including earthwork excavation, 100mm PCC M15 as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, Plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as per specifications and standard drawings and as per direction of Engineer-in-Charge. |
| 147 | For Class-AA loading |
| 148 | Air valve chamber of size0.9m x1m x1.695m for air valve size-from 50 mm-to-80mm |
| 149 | For Class-A loading |
| 150 | Air valve chamber of size0.9m x1m x1.71m for air valve size-from 50 mm-to-80mm |
| 151 | For in-campus Valve Chambers |
| 152 | Air valve chamber of size0.9m x1m x1.66m for air valve size-from 50 mm-to-80mm |
| 153 | SITC of Bulk Flow Meter with removable mechanism class \\"B\\" confirming to ISO:4064:2005/ IS: 2373 of approved make of following dia sized pipelines and specifications complete: Media : Water (Clear ), Temp. 50 deg., Pr. rating: PN16, Protection type: IP- 68, Body Material: IS-210 Gr. FG-200, Accuracy Class :Class B (±2 % @ Nominal flow rate), Magnetic Drive, Dry Dial, Epoxy powder coated, Pulse out put option, Anti-magnetic protection including all materials and making connection with existing pipeline required for Bulk Flow Meter including cutting the existing pipeline etc. complete in all respect as per technical specification and as per direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 154 | BFM 80 mm |
| 155 | BFM100 mm |
| 156 | BFM 125 mm |
| 157 | BFM 150 mm |
| 158 | BFM 200 mm |
| 159 | Work of Inter Connection in AC/PVC/HDPE pipe line up to 1.5 mtr depth by digging out suitable size of pit at site of work including dewatering and providing adequate safety arrangement at site, cutting of existing pipeline, jointing of Tee (complete) and other specials to make inter connection repair leak proof and then refill the pit from excavated sand by ramming it at sides of pipe & upto ground level for entire job contractor will use his own T&P & labour and will arrange transportation of material required from store. (Material such as Tee/ Tee Clamp/rubber sheet/ CID joints required for inter connection shall be provided by the department free of cost). |
| 160 | In all type Soil |
| 161 | 80 mm to 110 mm |
| 162 | 125 mm to 165 mm |
| 163 | Work of Inter Connection in CI/DI/MS pipe line up to 1.5 mtr depth by digging out suitable size of pit at site of work including dewatering and providing adequate safety arrangement at site, cutting of existing pipeline, jointing of Tee (complete) and other specials to make inter connection repair leak proof and then refill the pit from excavated sand by ramming it at sides of pipe & upto ground level for entire job contractor will use his own T&P & labour and will arrange transportation of material required from store. (Material such as Tee/ Tee Clamp/rubber sheet/ CID joints required for inter connection shall be provided by the department free of cost). |
| 164 | In all type Soil |
| 165 | 80 mm to 100 mm |
| 166 | 125 mm to 150 mm |
| 167 | Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B\\" class), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number 25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect. |
| 168 | 32 mm dia |
| 169 | 50 mm dia |
| 170 | 65 mm dia |
| 171 | 80mm dia |
| 172 | Providing, lowering, aligning, fixing in position in pipe line, CI double flanged swing type Non Return Valves (NRV) of approved make of following Pressure rating & dia complete, confirming to IS: 5312 (part -1)/ 2004 (amended up to date) and of following specifications: Body, Cover & disc of Grey cast iron of IS:210/ FG200. Face to face dimensions as per IS 5312 (part -1):2004 , Flanges Drilled as per IS:1538. Epoxy (Non-Toxic & suitable for drinking water) applied on body, cover and disc inside and outside . Body seat ring of SS/CS Door face ring - EPDM/ Neoprene (food grade quality) ,Shaft of SS- AISI- 410 ,Hinge Malleable cast iron / SS AISI 316 ,Bonnet Gasket EPDM, Bush- Leaded tin Bronze/ PTET, Gasket EPDM/NBR ,Nut-Bolt as per IS:1363 and IS: 1367 (galvanised steel) ,Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 173 | Class PN 1.0 |
| 174 | 80 mm dia |
| 175 | 100 mm dia |
| 176 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, CI single Air Valve Flanged/ Screwed type of approved makes for following pressure rating & dia complete, confirming to IS: 14845-2000 (amended up to date) and of following specifications: Body , Cover and Cowl - Grey Cast Iron as per IS:210- FG 200 ,Float - Stainless Steel AISI 304 / IS: 3444 ,Float Guide- HBT1,Body seat ring - Leaded tin bronze/ SS , Seal ring and face ring - EPDM/NBR, Ends flanged according to IS 6418 or Screwed type shall have external pipe threads conforming to IS 554 Fasteners - CS Epoxy paint inside outside of food grade safe for drinking water ,Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 177 | Class PN 1.0 |
| 178 | 15 mm S-1 Type |
| 179 | 25 mm S-1 Type |
| 180 | Class PN 1.6 |
| 181 | 15 mm S-1 Type |
| 182 | 25 mm S-1 Type |
| 183 | Removing & Re-fixing of Precast concrete interlocking blocks for laying of pipe line by manual method, stacking of serviceable & non serviceable material separately, disposal of dismantled material lead up to 50 mtr. The C.C. interlocking paving blocks be laid on average 25 mm thick bed of coarse sand and the joints to be filled with fine sand. Laying procedure on compacted sub base as defined. Complete job is to be executed as per the directions of Engineer in charge. The rates to be inclusive of fixing of 70 percent reusable precast concrete interlocking block and cost of required new precast concrete interlocking block against damaged, including all lead and lift as per Technical specifications. (Interlocking block manufactured by fully computerized automatic stationery hydraulic vibro pressed machine & full computerized automatic batching plant of class A-1 as per BS:6717-2001. Tensile splitting strength and breaking load as per BS: 6717-2001 Colour: Grey cement natural colour. Variation in Dimension : Less than 1.6 mm Variation in thickness: Less than 3.2 mm) Note: If existing precast block used more than 70%, than for every 1% use above 70%, deduction of 1% in cost shall be done for every 1% use above 70%. |
| 184 | 60 mm thick. |
| 185 | 80 mm thick. |
| 186 | 100 mm thick |
| 187 | supply and installation of Pump sets |
| 188 | Supply & Installation of single phase ISI marked submersible motor pump set of three star or better rating of BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. |
| 189 | Up to 2.0 KW |
| 190 | Above 2.0 KW |
| 191 | Supply & Installation of 3 phase ISI marked submersible motor pump set of three star or better rating of BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. |
| 192 | Up to 5.5 KW (7.5 HP) & head up to 120 mtr. |
| 193 | Up to 5.5 KW (7.5 HP) & head above 120 mtr. |
| 194 | 7.5 KW (10 HP) & head up to 120 mtr. |
| 195 | 7.5 KW (10 HP) & head above 120 mtr. |
| 196 | 9.3 KW (12.5 HP) & head up to 120 mtr. |
| 197 | 9.3 KW (12.5 HP) & head above 120 mtr. |
| 198 | 11 KW (15 HP) & head up to 120 mtr. |
| 199 | 11 KW (15 HP) & head above 120 mtr. |
| 200 | 13 KW (17.5 HP) & head up to 120 mtr. |
| 201 | 13 KW (17.5 HP) & head above 120 mtr. |
| 202 | 15 KW (20 HP) and above, head up to 120 mtr. |
| 203 | 15 KW (20 HP) and above, head above 120 mtr. |
| 204 | Supply and Fixing of Electric feeder panel (having projected canopy)for submersible pump set Single phase up to 5 HP, comprising of DOL Starter, MCB, Indicating Light, Ammeter, Volt meter, connection plate, condensers of approved make and the panel enclosure should be made out from 18 gauge M.S. Sheet with powder coating. Panel size Height 600 mm Width 500 mm depth 250 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\\" and double door including in built locking system. The legs should be embedded in M-15 cement concrete platform. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The operation of panel should be suitable for on 240 Volt AC Supply. |
| 205 | Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB, DOL starter, overload relay, ampere meter, volt meter, phase preventer, phase indicators, lighting arrangement etc. complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM). All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be of minimum size 900 x 600 x 300mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\\" and double door including in built locking system. The legs should be embedded in M-15 cement concrete platform. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. |
| 206 | Up to 5.00 HP |
| 207 | Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay, ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc. complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM). All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be of minimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\\" and double door including in built locking system. The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. |
| 208 | Above 5 HP and up to 10 HP |
| 209 | Above 10 HP and up to 15 HP |
| 210 | Above 15 HP and up to 20 HP |
| 211 | Above 20 HP and up to 30 HP |
| 212 | Supply & Fixing of ISI marked three core PVC flat submersible cable as per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc. |
| 213 | 3 core 4.0 Sq.mm |
| 214 | 3 core 6.0 Sq.mm |
| 215 | 3 core 10.0 Sq.mm |
| 216 | 3 core 16.0 Sq.mm |
| 217 | Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 218 | 10.0 Sq.mm, 4 core |
| 219 | 16.0 Sq.mm, 4 core |
| 220 | 25.0 Sq.mm, 3.5 core |
| 221 | 35.0 Sq.mm, 3.5 core |
| 222 | Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 223 | Supply & Fixing M S clamp set of 50x6 mm flat from iron with nuts and bolts etc. for holding the riser pipe assembly of submersible pump set. |
| 224 | Supply & Fixing tube well cover of MS sheet 8mm thick at top & 5mm thick 100mm wide shroud around the edge so as to form a cap on the top end of casing pipe with GI Nipple 45cm long & two GI flanges at both ends in 80mm sizes passing through a hole in the centre of MS sheet. A 25 mm socket with end plug shall also be welded over top plate. A GI nipple having outside thread of size 1/2\\" (for installation pressure gauge) shall be provided & welded with 80mm GI nipple near top plate nipple shall be provided with end plug. |
| 225 | 125 mm dia |
| 226 | 150 mm dia |
| 227 | 200 mm dia |
| 228 | 250 mm dia |
| 229 | Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B\\" class), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number 25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect. |
| 230 | 32 mm dia |
| 231 | 50 mm dia |
| 232 | 65 mm dia |
| 233 | 80mm dia |
| 234 | Providing & Lowering in tube well ISI marked HDPE pipe as per IS 4984:1995 or amended up to date in PE 80 grade and class PN 10 of following dia. including HDPE/GI fittings and PVC rope confirming to IS 5175:1992 or amended up to date, along with clamping of submersible cable etc. complete in allrespect. |
| 235 | 40 mm dia |
| 236 | 50 mm dia |
| 237 | 63 mm dia |
| 238 | 75 mm dia |
| 239 | 90 mm dia |
| 240 | Providing, installing, testing and commissioning of double flanged bulk flow meter with removable mechanism, of class B conforming to ISO 4064/1 or amended up to date of approved make including cost of all material and labour as per specifications with GI Box (sheet 16 SWG) suitable with locking arrangement of following dia. |
| 241 | 50 mm dia |
| 242 | 65 mm dia |
| 243 | 80 mm dia |
| 244 | Providing & Fixing pump safety cage as per specifications or as directed by Engineer in charge. |
| 245 | Providing & Fixing of double flanged, CI body, ISI marked NRV of approved make of following sizes |
| 246 | 65 mm dia |
| 247 | 80 mm dia |
| 248 | Proving and Fixing 32 mm dia Full way valve or wheel valve as per IS:778 or amended up to date of approvedmake, on pump delivery pipe. |
| 249 | Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg. including all jointing material as perspecification with safety cover. |
| 250 | Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at synchronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected on C.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 251 | Centrifugal Monoblock Pump set (Single Stage) |
| 252 | 2.2 KW (3.0 HP) |
| 253 | 3.7 KW (5.0 HP) |
| 254 | 5.5 KW (7.5 HP) |
| 255 | 7.5 KW (10 HP) |
| 256 | 9.3 KW (12.5 HP) |
| 257 | 11.0 KW (15 HP) |
| 258 | 15.0 KW (20.0 HP) |
| 259 | 18.5 KW (25.0 HP) |
| 260 | Centrifugal Monoblock Pump set (Double Stage) |
| 261 | 3.7 KW (5.0 HP) |
| 262 | 5.5 KW (7.5 HP) |
| 263 | 7.5 KW (10.0 HP) |
| 264 | 9.3 KW (12.5 HP) |
| 265 | 11.0 KW (15.0 HP) |
| 266 | 15.0 KW (20.0 HP) |
| 267 | Vacuum Pump set (Monoblock) |
| 268 | Providing, installation, testing and commissioning of Mono block Vacuum pump set with base plate including C.C. foundation / cross channels / RSJ frame and foundation bolts etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge. |
| 269 | 0.75 KW (1 HP), single Ph |
| 270 | 2.2 KW (3 HP), three Ph |
| 271 | Vacuum Pump set (Coupled) |
| 272 | Providing, installation, testing and commissioning of Submerged Centrifugal Pump sets with motor 4 pole synchronised speed of 1500 rpm ( water immersed, dry air filled, class \\"F\\" insulated TEWC motor integrally mounted on volute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 273 | 15 KW |
| 274 | 18.5 KW |
| 275 | 22 KW |
| 276 | 30 KW |
| 277 | Providing, installation, testing and commissioning of submersible Monoblock pump set conforming to IS 8034 and 2 pole motor operating at synchronised speed of speed 3000 RPM, with water proof winding. Pump shall be suitable for various delivery head and discharge with stainless steel shaft. Motor suitable for working on 415 V ± 10%, 3 Ph, 50 Hz AC and with water lubricated bearing to accept entire hydraulic thrust. Supply, with cable guard, thrust carbon/fibrebearing to withstand entire hydraulic thrust. The pump set shall be suitable for direct coupling, with suitable suction strainer. Pump should have suitable discharge out let as per manufacturer's design. Antithrust stream lined non return valve shall be provided with the pump and minimum 6 m submersible copper conductor cable in single / double run and 2 pairs of suitable size erection clamp 10 mm thick shall be provided with each pump etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 278 | 2.2 KW (3.0 HP) |
| 279 | 3.7 KW (5.0 HP) |
| 280 | 5.5 KW (7.5 HP) |
| 281 | 7.5 KW (10 HP) |
| 282 | 9.3 KW (12.5 HP) |
| 283 | 11.0 KW (15 HP) |
| 284 | 15.0 KW (20.0 HP) |
| 285 | Providing, installation, testing and commissioning of submersible dewatering pump set conforming to relevant IS codes and as per scope of work and Technical Specifications, with water proof winding. Pump shall be suitable for various delivery head and discharge with stainless steel shaft, impeller, pump and motor body. Motor suitable for working on 415 V± 10%, 3 Ph, 50 Hz A.C. Supply, with cable guard. The pump set shall be suitable for direct coupling, with suitable suction strainer etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 286 | 0.75 KW (1.0 HP) |
| 287 | 1.5 KW (2.0 HP) |
| 288 | 2.2 KW (3.0 HP) |
| 289 | 3.7 KW (5.0 HP ) |
| 290 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick . Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 291 | Manually Operated CI Sluice valve of Class PN-1.0 |
| 292 | 80 mm HW |
| 293 | 100 mm HW |
| 294 | 125 mm HW |
| 295 | 150 mm HW |
| 296 | 200 mm HW |
| 297 | 250 mm HW |
| 298 | 300 mm HW |
| 299 | SITC DOL Starter type LT Panel of following rating, all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar 1.6mm/ 2.0mm thick duly Electrostatic Powder Coated with angle frame including other ancillaries ( Insulators, Acrylic Sheet , Backlight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Neutral Links , Spiral , Saddle & Packing Material ) etc. complete as per Technical Specifications and as per direction of Engineer-In-Charge. |
| 300 | DOL STARTER 2.2 KW (3 HP)- : For 2 motors (1 W+ 1S)I/C - MCB 25A ,FP, 10 KA, C Curve (1) , AnalogVoltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 30/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve(3) andO/G- MCB 16A ,TP, 10 KA, C Curve (2), Power Cont 9A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (4-6A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red- 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 2 Kvar (2) |
| 301 | DOL STARTER 3.7KW (5 HP ) - : For 2 motors (1 W+ 1S) I/C - MCB 32A,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T.30/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow - 1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) andO/G- MCB 25A ,TP, 10 KA, C Curve (2), Power Cont 12ATP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red- 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 2 Kvar (2) |
| 302 | DOL STARTER 5.5 KW (7.5HP) - : For 2 motors (1 W+ 1S) I/C -MCB 40A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp.Selector Switch (1), C. T. 30/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve(3) andO/G- MCB 25A ,TP, 10 KA, C Curve (2), Power Cont 12ATP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red- 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 2 Kvar (2) |
| 303 | SITC STAR DELTA Starter type LT Panel of following rating: all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar1.6mm/ 2.0mm thick duly Electrostatic Powder Coated with angle frame including other ancillaries ( Insulators, Acrylic Sheet , Backlight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Neutral Links , Spiral, Saddle & Packing Material ) etc. and 100A/ 125A,TPN, Aluminium Bus Bar with Colour coated heat shrinkage sleeves complete as per Technical Specifications and as per direction of Engineer-In- Charge. |
| 304 | STAR DELTA STARTER 7.5 KW (10.0 HP) - : For 2motors (1 W+ 1S)I/C - MCB 63A ,FP, 10 KA, C Curve (1) , AnalogVoltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve(3) andO/G- MCB 32A ,TP, 10 KA, C Curve (2), Power Cont 18ATP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red- 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 5Kvar (2), S/D Timer(2) |
| 305 | STAR DELTA STARTER 9.3 KW (12.5 HP) - : For2 motors (1 W+ 1S)I/C - MCB 63A ,FP, 10 KA, C Curve (1) , AnalogVoltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve(3) andO/G- MCB 40A ,TP, 10 KA, C Curve (2), Power Cont 18ATP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red- 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 5Kvar (2), S/D Timer(2) |
| 306 | STAR DELTA STARTER 11.0 KW (15.0 HP) - : For2 motors (1 W+ 1S)I/C - MCB 63A ,FP, 10 KA, C Curve (1) , AnalogVoltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve(3) andO/G- MCB 40A ,TP, 10 KA, C Curve (2), Power Cont 25ATP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (9-13A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red- 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 7.5Kvar (2), S/D Timer(2) |
| 307 | STAR DELTA STARTER 15.0 KW (20.0 HP) : For 2motors (1 W+ 1S)I/C- MCCB 100A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp.Selector Switch (1), C. T. 100/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve(3) andO/G- MCCB 63A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (2), Power Cont 32A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (12-18A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type7.5Kvar (2), S/D Timer(2) |
| 308 | STAR DELTA STARTER 18.5 KW (25.0 HP) - : For2 motors (1 W+ 1S)I/C- MCCB 125A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp.Selector Switch (1), C. T. 125/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve(3) andO/G- MCCB 100A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (2), Power Cont 32A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (16-24A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 10 Kvar (2), S/D Timer(2) |
| 309 | STAR DELTA STARTER 22.0 KW (30.0 HP) - : For2 motors (1 W+ 1S)I/C- MCCB 125A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp.Selector Switch (1), C. T. 125/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve(3) andO/G- MCCB 100A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (2), Power Cont 40A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (23-32A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 12.5 Kvar (2), S/D Timer(2) |
| 310 | Providing, lowering, aligning, fixing in position in pipe line, CI double flanged swing type Non Return Valves (NRV) of approved make of following Pressure rating & dia complete, confirming to IS: 5312 (part -1)/ 2004 (amended up to date) and of following specifications: Body, Cover & disc of Grey cast iron of IS:210/ FG200. Face to face dimensions as per IS 5312 (part -1):2004 , Flanges Drilled as per IS:1538. Epoxy (Non-Toxic & suitable for drinking water) applied on body, cover and disc inside and outside . Body seat ring of SS/CS Door face ring - EPDM/ Neoprene (food grade quality) ,Shaft of SS- AISI- 410 ,Hinge Malleable cast iron / SS AISI 316 ,Bonnet Gasket EPDM, Bush- Leaded tin Bronze/ PTET, Gasket EPDM/NBR ,Nut-Bolt as per IS:1363 and IS: 1367 (galvanised steel) ,Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ |
| 311 | 80 mm dia |
| 312 | 100 mm dia |
| 313 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete including all taxes, material, labour, inside lining, outside coating, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge. MS pipe specials up to 600mm dia (with minimum 5mm thickness sheet) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender