Tender For Est. No. Sr/Mesd/Ms/8345/ 2025-26 Providing Renovation, Addition And Alterations To E.I., Lan Networking, Air Conditioning System, Lifts, Fire Alarming, Fire Fighting System And Audio Video System To The Air India Building, Nariman Point,
Tender Overview
Project Description
Tender for Est. No. Sr/Mesd/Ms/8345/ 2025-26 Providing Renovation, Addition And Alterations To E.I., Lan Networking, Air Conditioning System, Lifts, Fire Alarming, Fire Fighting System And Audio Video System To The Air India Building, Nariman Point, Mumbai.
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation, Testing & Commissioning of 750 kVA D.G.SET WITH PANEL -750KVA. DG Set shall be comprise of Following :a) Engine: -The Engine of D.G. set as per (CPCB IV+) comprises of Efficient CRDI system, (Common rail direct Injection system). CRDI is fuel injection system that improves engine performance, efficiency and emissions. It engine shall be as per O2E series (Optimal operating efficiency) i.e. Low emission, high efficiency engines, compact, Robust and rugged design. The lube oil change period should be of 500 hours. It shall be comprises of integral set of radiator system, designed and tested for 50 C ambient temperature. As per CPCB IV + norms the CRDI system shall be enhance the filtration efficiency and provide better performance, lower noise and reduced emissions.A1) Exhaust Gas Treatment system :-The Exhaust Gas Treatment System shall be comprises of DOC& (Diesel Oxidation Catalyst) SCR ( Selective Catalytic Reduction) System to sets of the reaction of emission as per latest CPCB+IV norms. A2) Controller :-The Controller shall be of Microprocessor based, having Graphical LCD display and best in class monitoring and diagnostic capability. It should be integrable with AMF , synchronization & communication compatible.A3) DEF Tank :-(Diesel exhaust fuel )For DEF tank the aqueous urea shall be used to sets off the chemical reaction with exhaust gas. The tank size shall be optimized in accordance to DEF consumption.a) Alternator:-The alternator shall be rated capacity at 0.8 power factor, 415 volts, 3 phase, 4 wire, 50 cycles/sec, 1500 rpm, self excited and self regulated, with brush less excitation. Band of voltage regulation shall be + 2.5% of rated voltage from no load to full load. Insulation class shall be “H”. The alternator shall be conforming to BS:5000/IS 4722 and shall be designed to withstand tropical conditions. Required output shall be under NTP conditions.b) Base Frame & Mounting Arrangement:-The engine & the alternator shall be directly coupled to each other by means of couplings in order to to form very compact arrangement. Cooling system & both these units shall be mounted on a rigid fabricated M.S. common base frame. The base frame of the diesel generating set shall be sturdy and fabricated/ welded construction out of M.S. channel iron base of suitable size for mounting the above engine & alternator. The base frame shall be suitably designed to simplify transportation, handling, slinging, E&C. This base frame shall be painted with anti corrosive epoxy paint. Noise level shall not exceed 75 dB as per CPCB norms of noise. A set of anti vibration pads shall be provided between base frame and engine alternator.c) Battery:-Suitable Dry type Batteries of Standard Make with leads and Terminals shall be part of the equipment. The pack shall be suitably positioned and modular withdraw able to ease of servicing. The Battery pack shall be minimum 180 AH d) Fuel Tank:-Fuel Tank should be located nearest to the DG set enclosure to ensure free flow of diesel. Suitable capacity of the fuel tank to run the set for about 12 hours with mounting bracket, level indicator, fuel inlet, fuel outlet, air vent, drain plug, inlet arrangement for direct filling and set of hoses for inlet & return.e) Exhaust Piping:-The exhaust piping shall be of suitable size and dimensions as per manufacturer’s recommendations. The residential silencer shall be provided to to maintain the noise level as specified. The exhaust piping shall be insulated with heat resistive material like asbestos, glass wool etc. and clamped/supported, mounted on wall/ floor by suitable size clamping arrangement. Outlet of exhaust shall be taken out from the structure as per site conditions and covered to protect from atmosphere effects like rain etc. shall be made good by plastering after completion of work. The material of piping shall be of approved make and quality (for indoor installations).f) Acoustic Enclosure: The enclosure shall be CPCB type approved soundproof enclosure. The enclosure shall be modular construction with hinge bolted structure to provide easy dismantling and reassembling. The DG set with enclosure shall undergo strict quality checks and testing to achieve high-end performance so that the offered DG set with enclosure enables reduction of sound and thus as per latest CPCB norms of noise at 1 mtr. distance under free condition should be 75 dB. |
| 2 | Panel requirement The LV switchboard shall be type tested assemblies, all type tests as defined in latest IEC 61439-1&2. Also it should comply IEC 61641 Internal arc withstand for 65kA for 0.3 Sec. LT panels must be built up from compartment housing, circuit breakers, control-gear, relays, busbars, controls and other items of equipment as per BOQ. Low Voltage switchgear & control gear must comply IEC 60 947 /IS 13947.The Short circuit current with minimum duration of 1sec. for LV switchgear panels shall be as indicated in SLD.The LV Main Switchboard shall be identical in mechanical construction to the LV Switchboard which had been type-tested by an acceptable, multi-fold design with impact test IK07-IK10.The design temperature for the equipment provided in the main low voltage switchboards shall be +50°C. the switchboard shall be of form 4b, for form of separation only metallic compartmentalization shall be used, Hylem / PVC sheets shall not be allowed.Switchboard panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness not less than 2.0 mm. Busbars shall be made of high conductivity, and high strength Aluminum E91 grade Busbars shall be of rectangular cross sections , not more than 6mm thickness better suitable for full load current for phase bus bars and half/ full rated current for neutral bus bar or as stipulated in schedule of quantities. Busbar shall be suitable to withstand the stresses of fault level as specified in schedule of quantities.The material and the spacing of the Busbar supports should be same as per the type tested assembly. Busbar shall be tin plated with silver contacts.The cables and control wires shall be suitable for withstanding 105 deg C. Paint shall be RAL 7032 powder coated or as per the directives of engineer in charge. The APFC /RTPFC panels must be designed, tested & manufactured as per IEC61439- 1 & 2 & IEC 61921 refrence standard.DG SYNCHRONIZING PANEL-1 (FORM4, TYPE6)I/C 1600A, 4P, 50kA, EDO, LSIG ACB - 3 NoI/C 2000A, 4P, 50kA, EDO, LSIG ACB - 1 No9000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 800A, O/G 2000A, 4P, 50kA, EDO, LSIG ACB - 3 NoO/G 1600A, 4P, 50kA, EDO, LSIG ACB - 1 NoO/G 100A, 4P, 25kA, MP MCCB - 1 NoAll incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital voltmeter, Digital Ammeter, Digital MFM compatible for BMS control, CT for metering, CT for Sync Relay, control wiring, Under Voltage relay, Phase Sequence relay, Negative Phase protection Relay, reverse power relay, Over & under frequency relay, MP BASED GENERATOR CONTROL / SYNC RELAY, DC Voltmeter, DC Ammeter, AC power contractor, ON indicator lamp, Off indicator lamp, Push button, TNC switch, AM Switch, Digital Hooter, Annunciation window, Generator Master trip relay, Line voltage minitor, Battery changer.All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.All incomer and outgoing shall be with automatic change over scheme, electrical & mechanical interlocking, auto/Manual on & off of DG Sets, breakers etc.Synchronizing Relay like Woodward/Dief/Deepsea/PCCM or equivalent shall be provided for each DG set. Selection of Master DG Sets, operation(Opening/closing) of breakers as required and complete with interfacing with DG Set Controller 8 Channel temperature scanner for monitoring bearing and winding temperature, 16 window facia annunciator, Auto - manual selector switch for individual breaker & PLC. |
| 3 | Supplying, installation, testing & commisioning of air circuit breaker of 2000A, 500V, 4 pole with inbuilt ZSI module with standard accessories enclosed in a IP-43 MS enclosure and iron frame as isolators.The Air circuit breakers (ACB) shall comply with standards IS/IEC 60947-(1 & 2) & IS/IEC 60664-1 & shall have ICS=ICU=ICW for 1 Sec. ACB shall not derate up to 50’C & shall have break time <30ms & shall have 100% rated neutral pole.The provided ACB shall suitable for terminating aluminum bus bars and shall have ROHS & WEEE Certifications |
| 4 | Supplying, installation, testing & commisioning of 400A FP 16KA MP TM MCCB in IP-43 MS enclosure with RYB phase indicator lamp with MCB including iron frame for mounting of MCCB enclosure. MCCbs shall comply with standards IS/IEC 60947-1 & 2. and shall have to provide electric fault trip indication on panel and with thermal magnetic trip unit (with Adjustable Thermal - 0.7 - 1 Ir and Fixed Magnetic). It shall be current limiting type and shall have an encapsulated double break roto design having two fixed contacts, two moving contacts and two arc chutes per pole with Continuous rated Shunt trip coils & common & snap fit accessaries and should be ROHS & WEEE compliant |
| 5 | Supplying, installation, testing & commisioning of 250A FP 16KA MP TM MCCB in IP-43 MS enclosure with RYB phase indicator lamp with MCB including iron frame for mounting of MCCB enclosure. MCCbs shall comply with standards IS/IEC 60947-1 & 2. and shall have to provide electric fault trip indication on panel and with thermal magnetic trip unit (with Adjustable Thermal - 0.7 - 1 Ir and Fixed Magnetic). It shall be current limiting type and shall have an encapsulated double break roto design having two fixed contacts, two moving contacts and two arc chutes per pole with Continuous rated Shunt trip coils & common & snap fit accessaries and should be ROHS & WEEE compliant |
| 6 | Supplying, installation, testing & commisioning of 100A FP 16KA MP TM MCCB in IP-43 MS enclosure with RYB phase indicator lamp with MCB including iron frame for mounting of MCCB enclosure. MCCbs shall comply with standards IS/IEC 60947-1 & 2. and shall have to provide electric fault trip indication on panel and with thermal magnetic trip unit (with Adjustable Thermal - 0.7 - 1 Ir and Fixed Magnetic). It shall be current limiting type and shall have an encapsulated double break roto design having two fixed contacts, two moving contacts and two arc chutes per pole with Continuous rated Shunt trip coils & common & snap fit accessaries and should be ROHS & WEEE compliant |
| 7 | Supply, Installation, Testing & Commissioning of METER-2 PANEL (FORM4, TYPE6) each withI/C 2000A, 4P, 50kA, EDO, LSIG ACB - 2 No with Electrical & Mechanical Interlocking2500A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 1000A, FP, 4P, 36kA, EDO, LSIG ACB - 2 NoO/G 400A, FP, MP, 36kA. MCCB - 5 NoO/G 200A, FP, MP, 36kA. MCCB - 2 NoO/G 100A, FP, MP, 36kA. MCCB - 3 NoAll incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.(Refer Schedule B in DTP for Detailed Item Description) |
| 8 | Supply, Installation, Testing & Commissioning of METER-3 PANEL (FORM4, TYPE6) each withI/C 2000A, 4P, 36kA, EDO, LSIG ACB - 1 No.2500A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 2000A, 4P, 4P, 36kA, EDO, LSIG ACB - 1 NoO/G 1000A, 4P, 4P, 36kA, EDO, LSIG ACB - 3 NoAll incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 9 | Supply, Installation, Testing & Commissioning of METER-4 PANEL (FORM4, TYPE6) each withI/C 2000A, 4P, 36kA, EDO, LSIG ACB - 1 No .2500A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 2000A, 4P, 4P, 36kA, EDO, LSIG ACB - 2 NoO/G 1000A, 4P, 4P, 36kA, EDO, LSIG ACB - 1 NoO/G 800A, 4P, 4P, 36kA, EDO, LSIG ACB - 3 NoO/G 400A, 4P, 4P, 36kA, MP, MCCB - 1 NoAll incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 10 | Supply, Installation, Testing & Commissioning of METER-5 PANEL (FORM4, TYPE6) each withI/C 2000A, 4P, 36kA, EDO, LSIG ACB - 1 No 2500A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 1000A, 4P, 4P, 36kA, EDO, LSIG ACB - 1 NoO/G 400A, 4P, 4P, 36kA, MP, MCCB - 2 NoO/G 125A, 4P, 4P, 36kA, MP, MCCB - 1 NoO/G 100A, 4P, 4P, 36kA, MP, MCCB - 1 NoAll incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 11 | UPS DISTRIBUTION PANEL-1 & 2 (FORM3B, TYPE2)I/C 630A, FP, 36kA, EDO ACB WITH O/C, S/C, E/F PROTECTION. - 1 No 800A AL. SLEEVED TP+2N BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 400A, FP, MP, 36kA. MCCB - 3 NosO/G 100A, 4P, 4P, 36kA, MP, MCCB - 1 NoAll incomer shall have RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.All outgoing shall have RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 12 | UPS DISTRIBUTION PANEL-3 (FORM3B, TYPE2)I/C 400A, FP, MP, 36kA. MCCB - 1 No 500A AL. SLEEVED TP+2N BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 400A, FP, MP, 36kA. MCCB - 3 Nos250A, FP, MP, 25kA. MCCB - 1 Nos100A, FP, MP, 256kA. MCCB - 1 NosAll incomer shall have RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.All outgoing shall have RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 13 | EXTERNAL LIGHTING & STAIRCASE LIGHTING PANEL (FORM3B, TYPE2)I/C 160A, FP, MCCB - 1 No 200A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 63A FP, MP, 25KA. MCCB - 6 No All incomer shall have RYB phase indicator lamp with MCB, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 14 | LIFT NORMAL PANEL (FORM3B, TYPE2)I/C 400A, FP, MCCB - 1 No 500A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 200A FP,MP, 25KA. MCCB - 02 No O/G 100A FP,MP, 25KA. MCCB - 08 No O/G 32A DP,, 25KA. MCB - 9 No All incomer shall have RYB phase indicator lamp with MCB, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 15 | FIRE LIFT PANEL (FORM3B, TYPE2)I/C 200A, FP, MCCB - 1 No 250A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 100A FP,MP, 25KA. MCCB - 05 No O/G 32A DP,, 25KA. MCB - 6 No All incomer shall have RYB phase indicator lamp with MCB, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 16 | PLUMBING PANEL (FORM3B, TYPE2)I/C 200A, FP, ISOLATOR - 1 No 250A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.O/G 63A DP/FP, MP, 25KA. MPCB WITH 7.5 HP DOL STARTER - 6 No O/G 25A DP, MP, 25KA. MPCB - 2 No O/G 100A FP, MP, 25KA. MCCB - 1 No O/G 32A FP, MP, 25KA. MCCB - 2 No All incomer shall have RYB phase indicator lamp with MCB, Digital MFM compatible for BMS control, CT for metering, control wiring. |
| 17 | Supply, installation, testing and commissioning of Aluminum 400A/630 A 40kA SC for 1 sec Sandwich type BBT. The BBT should be totally type tested as per IEC 61439-6. The Bus bar trunking must be with Copper/ Bimetal Contact, with Tin plated Aluminium (3L+N+PE) 100% N with 50% Integral / Internal Earth. The BBT must be of insulation Class F & operating voltage = 1000V,Impulse withstand of 8kV & Housing of minimum 1.5mm Electro-galvanized steel. The housing enclosure must be electrostatic powder coated of suitable shade. The BBT must of IP 54 indoor. The total bus bar assembly & installaion at site must comply Seismic zone 4. Straight length of feeder / plug in type with hanging brackets, end covers / end caps as per design requirement & site condition |
| 18 | Supply, installation, testing and commissioning of Flange end with Adaptor box, Copper flexibles as per design requirement & site condition suitable for Aluminum 400A/630 A 40kA Sandwich type BBT. |
| 19 | Supply, installation, testing and commissioning of 90 Degree Elbow / T Elbow as per design requirement & site condition suitable for Aluminum 400A/630 A 40kA Sandwich type BBT. |
| 20 | Supply, installation, testing and commissioning of Phase cross over/ expansion joint as per design requirement & site condition suitable for Aluminum 400A/630 A 40kA Sandwich type BBT. |
| 21 | Supply, installation, testing and commissioning of Support hanger as per site condition suitable for vertical Aluminum 400A/630 A 40kA Sandwich type BBT. |
| 22 | Supply, installation, testing and commissioning of Fabrication Support & hardware suitable for Aluminum 400A/630 A 40kA Sandwich type BBT. |
| 23 | Supply, installation, testing and commissioning of Aluminum 800A 40kA SC for 1 sec Sandwich type BBT. The BBT should be totally type tested as per IEC 61439-6. The Bus bar trunking must be with Copper/ Bimetal Contact, with Tin plated Aluminium (3L+N+PE) 100% N with 50% Integral / Internal Earth. The BBT must be of insulation Class F & operating voltage = 1000V,Impulse withstand of 8kV & Housing of minimum 1.5mm Electro-galvanized steel. The housing enclosure must be electrostatic powder coated of suitable shade. The BBT must of IP 54 indoor. The total bus bar assembly & installaion at site must comply Seismic zone 4. Straight length of feeder / plug in type with hanging brackets, end covers / end caps as per design requirement & site condition |
| 24 | Supply, installation, testing and commissioning of Flange end with Adaptor box, Copper flexibles as per design requirement & site condition suitable for Aluminum 800A 40kA Sandwich type BBT. |
| 25 | Supply, installation, testing and commissioning of 90 Degree Elbow / T Elbow as per design requirement & site condition suitable for Aluminum 800A 40kA Sandwich type BBT. |
| 26 | Supply, installation, testing and commissioning of Phase cross over/ expansion joint as per design requirement & site condition suitable for Aluminum 800A 40kA Sandwich type BBT. |
| 27 | Supply, installation, testing and commissioning of Support hanger as per site condition suitable for vertical Aluminum 800A 40kA Sandwich type BBT. |
| 28 | Supply, installation, testing and commissioning of Fabrication Support & hardware suitable for Aluminum 800A 40kA Sandwich type BBT. |
| 29 | Supply, installation, testing and commissioning of Aluminum 1000A 40-50kA SC for 1 sec Sandwich type BBT. The BBT should be totally type tested as per IEC 61439-6. The Bus bar trunking must be with Copper/ Bimetal Contact, with Tin plated Aluminium (3L+N+PE) 100% N with 50% Integral / Internal Earth. The BBT must be of insulation Class F & operating voltage = 1000V,Impulse withstand of 8kV & Housing of minimum 1.5mm Electro-galvanized steel. The housing enclosure must be electrostatic powder coated of suitable shade. The BBT must of IP 54 indoor. The total bus bar assembly & installaion at site must comply Seismic zone 4. Straight length of feeder / plug in type with hanging brackets, end covers / end caps as per design requirement & site condition |
| 30 | Supply, installation, testing and commissioning of Flange end with Adaptor box, Copper flexibles as per design requirement & site condition suitable for Aluminum 1000A 40-50kA Sandwich type BBT. |
| 31 | Supply, installation, testing and commissioning of 90 Degree Elbow / T Elbow as per design requirement & site condition suitable for Aluminum 1000A 40-50kA Sandwich type BBT. |
| 32 | Supply, installation, testing and commissioning of Phase cross over/ expansion joint as per design requirement & site condition suitable for Aluminum 1000A 40-50kA Sandwich type BBT. |
| 33 | Supply, installation, testing and commissioning of Support hanger as per site condition suitable for vertical Aluminum 1000A 50kA Sandwich type BBT. |
| 34 | Supply, installation, testing and commissioning of Fabrication Support & hardware suitable for Aluminum 1000A 50kA Sandwich type BBT. |
| 35 | Supply, installation, testing and commissioning of Aluminum 1600A 40-50kA SC for 1 sec Sandwich type BBT. The BBT should be totally type tested as per IEC 61439-6. The Bus bar trunking must be with Copper/ Bimetal Contact, with Tin plated Aluminium (3L+N+PE) 100% N with 50% Integral / Internal Earth. The BBT must be of insulation Class F & operating voltage = 1000V,Impulse withstand of 8kV & Housing of minimum 1.5mm Electro-galvanized steel. The housing enclosure must be electrostatic powder coated of suitable shade. The BBT must of IP 54 indoor. The total bus bar assembly & installaion at site must comply Seismic zone 4. Straight length of feeder / plug in type with hanging brackets, end covers / end caps as per design requirement & site condition |
| 36 | Supply, installation, testing and commissioning of Flange end with Adaptor box, Copper flexibles as per design requirement & site condition suitable for Aluminum 1250A 40-50kA Sandwich type BBT. |
| 37 | Supply, installation, testing and commissioning of 90 Degree Elbow / T Elbow as per design requirement & site condition suitable for Aluminum 1250A 40-50kA Sandwich type BBT. |
| 38 | Supply, installation, testing and commissioning of Phase cross over/ expansion joint as per design requirement & site condition suitable for Aluminum 1250A 40-50kA Sandwich type BBT. |
| 39 | Supply, installation, testing and commissioning of Support hanger as per site condition suitable for vertical Aluminum 1250A 40-50kA Sandwich type BBT. |
| 40 | Supply, installation, testing and commissioning of Fabrication Support & hardware suitable for Aluminum 1250A 40-50kA Sandwich type BBT. |
| 41 | Supply, installation, testing and commissioning of Aluminum 2000A 50kA SC for 1 sec Sandwich type BBT. The BBT should be totally type tested as per IEC 61439-6. The Bus bar trunking must be with Copper/ Bimetal Contact, with Tin plated Aluminium (3L+N+PE) 100% N with 50% Integral / Internal Earth. The BBT must be of insulation Class F & operating voltage = 1000V,Impulse withstand of 8kV & Housing of minimum 1.5mm Electro-galvanized steel. The housing enclosure must be electrostatic powder coated of suitable shade. The BBT must of IP 54 indoor. The total bus bar assembly & installaion at site must comply Seismic zone 4. Straight length of feeder / plug in type with hanging brackets, end covers / end caps as per design requirement & site condition |
| 42 | Supply, installation, testing and commissioning of Flange end with Adaptor box, Copper flexibles as per design requirement & site condition suitable for Aluminum 2000A 50kA Sandwich type BBT. |
| 43 | Supply, installation, testing and commissioning of 90 Degree Elbow / T Elbow as per design requirement & site condition suitable for Aluminum 2000A 50kA Sandwich type BBT. |
| 44 | Supply, installation, testing and commissioning of Support hanger as per site condition suitable for vertical Aluminum 2000A 50kA Sandwich type BBT. |
| 45 | Supply, installation, testing and commissioning of Fabrication Support & hardware suitable for Aluminum 2000A 50kA Sandwich type BBT. |
| 46 | Supply, installation, testing and commissioning of Tap off box tested as per IEC 61439-6 of 63 A Tap off box (IP-54) made of 1.6mm thick sheet steel enclosure duly powder coating on existing rising mains complete with 4P MCCB, 36kA 4P LSI with earthing connection point & safelty interlock |
| 47 | Supply, installation, testing and commissioning of Tap off box tested as per IEC 61439-6 of 100 A Tap off box (IP-54) made of 1.6mm thick sheet steel enclosure duly powder coating on existing rising mains complete with 4P MCCB, 36kA 4P LSI with earthing connection point & safelty interlock |
| 48 | Supply, installation, testing and commissioning of Tap off box tested as per IEC 61439-6 of 160 A Tap off box (IP-54) made of 1.6mm thick sheet steel enclosure duly powder coating on existing rising mains complete with 4P MCCB, 36kA 4P LSI with earthing connection point & safelty interlock |
| 49 | Supply, installation, testing and commissioning of Tap off box tested as per IEC 61439-6 of 250 A Tap off box (IP-54) made of 1.6mm thick sheet steel enclosure duly powder coating on existing rising mains complete with 4P MCCB, 36kA 4P LSI with earthing connection point & safelty interlock |
| 50 | Supply, installation, testing and commissioning of Tap off box tested as per IEC 61439-6 of 320 A Tap off box (IP-54) made of 1.6mm thick sheet steel enclosure duly powder coating on existing rising mains complete with 4P MCCB, 36kA 4P LSI with earthing connection point & safelty interlock |
| 51 | Supply, installation, testing and commissioning of Tap off box tested as per IEC 61439-6 of 500 A Tap off box (IP-54) made of 1.6mm thick sheet steel enclosure duly powder coating on existing rising mains complete with 4P MCCB, 36kA 4P LSI with earthing connection point & safelty interlock |
| 52 | Providing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbon based environment friendly back fill Ground Enhancing compound complete with all materials, testing & recording the results as per specification no ESE -LA |
| 53 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials, testing & recording the results as per specification No. EA-EP |
| 54 | Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification No. EA-MOBI |
| 55 | Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bitumiNous paint in an approved manner with joints required. As per specification No. EA-EP. |
| 56 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bitumiNous paint in an approved manner with jointsrequired. As per specification No EA-EP. |
| 57 | Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 & CPRI tested having 2 mm thickness upto 3.3 kV |
| 58 | Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete. |
| 59 | Supplying & erecting UV Fly killer/ bug catcher Light Fitting having 2 x 20W UV Tube Lights to cover min. area of 500 sq.ft with powdered coated M.S./ steel body suitable to work on 230V, AC Supply having top mountingarrangement with SS chain complete and 3 core 1 mtr. flexible wire with 1 year warranty. |
| 60 | Supplying, erecting, testing and commissioning selfcontained water cooler 230/250 V 50 cycles nominal cooling capacity of 40 litres/hr and storage capacity 80 litres with partially stainless steel body complete. specification no. AP-WCR/WC |
| 61 | Supplying and erecting ultra violet water purifier with softener for safe drinking water consisting of UV germicidal tube of 8W capacity, choke made of copper wire, two indicator lamps, dual function cartridge with output of purified water 1 litre/min with activated carbon filter and softener operating on 230V, single phase A.C. supply with UV fail & filter change indication system. |
| 62 | Supplying & erecting conventional spike type air termination suitable to carry lightning stroke made up of heavy gauge 40 mm dia copper pipe of standard length with 5 Nos. copper spikes fixed on copper ball as air terminals duly threaded in copper pipe erected on provided foundation in an approved manner. |
| 63 | Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with insulating and non-corrosive bond in an approved manner with required joints As per specification no. EA-EP. |
| 64 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with insulating and non-corrosive bond in an approved manner with required joints As per specification no. EAEP. |
| 65 | Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI |
| 66 | Supply, installation, testing & commissioning of 8 mm aluminium round conductor complete as specified in drawing & meets the requirements of DIN EN 50164- 2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) |
| 67 | Supply, installation, testing & commissioning of roof conductor holder for parapet - polyamide conductor holder: with M8 female thread or diameter 7mm, M8 screw to connect the conductor holder, weather & temperature resistant from -35 to +90 deg C tested. conductor holder @1metre distance. |
| 68 | Adhesive Base |
| 69 | Supply, installation, testing & commissioning of polyamide roof cable holder for flat roof: DIN 48829 formB1, closed from bottom filling weight 1kg (frost resistant concrete) sleeves from polyethylene black @ 1metre distance |
| 70 | Providing of Stand for Fang Fix system 16 kg with base and clamp ,made up of frost resistant concrete and tested upto 100KA lightning current . |
| 71 | Supply, installation, testing & commissioning of cross universal connector, for T & cross connection to route vertical down conductor / mesh formation made of hot dipped galvanised iron with necessary screws etc as required installation with 4 hexagonal bolts M8*25 with M8 hexagonal nuts. |
| 72 | Supply, installation, testing & commissioning of test joint folding clamp suitable to connect 8mm round conductor & max by 30X3 mm GI strip as specified in the drawing & directed by engineer |
| 73 | Supply, installation, testing & commissioning of lightning counter - to count no of lightning strike & it can record the date & time of lightning incident also tested as per IEC 62561-6 |
| 74 | Supply, installation, Testing & commissioning of Smart 200KVA UPS with SMF battery bank for 30 minutes backup. as per IS 13314 & IS 11260 having following capacity & features:- Load 0.8 PF, Full wave / pure sine wave IGBT base rectifier, Isolator Transformer Input THDI < 5% & Input Power factor @ 0.99 With Automatic Internal Static Bypass switch. The static switches shall be rated for 125% continuous Load & should take care of Current imbalance due to power cable impedance. This should provide High availability for system, Manual maintenance switch at input & output. UPS shall sustain input voltage variations from + 20 % & +20% without switching over to batteries and providing output voltage with +/- 1 % regulation, UPS shall be able to sustain input frequency variation of +/- 6 % (Min), The Maximum waveform distortion (THD) of output voltage shall not exceed 3 % RMS for Linear Loads and 5 % RMS for non linear Loads, Output Frequency – 50 Hz ( Mains Synchronized) , +/-0.1 % Free Running. Quoted price shall be inclusive of required rating single core copper conductor cable including terminations,connections of UPS to batteries, battery rack etc complete in all respect and as per direction of Engineer in Charge. |
| 75 | Supply, installation, Testing & commissioning of Smart 100KVA UPS with SMF battery bank for 30 minutes backup. as per IS 13314 & IS 11260 having following capacity & features:- Load 0.8 PF, Full wave / pure sine wave IGBT base rectifier, Isolator Transformer Input THDI < 5% & Input Power factor @ 0.99 With Automatic Internal Static Bypass switch. The static switches shall be rated for 125% continuous Load & should take care of Current imbalance due to power cable impedance. This should provide High availability for system, Manual maintenance switch at input & output. UPS shall sustain input voltage variations from + 20 % & +20% without switching over to batteries and providing output voltage with +/- 1 % regulation, UPS shall be able to sustain input frequency variation of +/- 6 % (Min), The Maximum waveform distortion (THD) of output voltage shall not exceed 3 % RMS for Linear Loads and 5 % RMS for non linear Loads, Output Frequency – 50 Hz ( Mains Synchronized) , +/-0.1 % Free Running. Quoted price shall be inclusive of required rating single core copper conductor cable including terminations,connections of UPS to batteries, battery rack etc complete in all respect and as per direction of Engineer in Charge. |
| 76 | Supplying, erecting, testing and commissioning of 20kVA capacity online pure sine wave, with backup time of 0.5 hrs. PWM & IGBT based UPS with 0.9 to unity output pf, 3 phase input and 3 phase output complete with all protections as per specification no. AP-UPS |
| 77 | Supplying and erecting 12V/100Ah SMF battery with battery terminal wire, dulycharged with 24 months warranty complete. |
| 78 | Diesel Generating set (Credit) |
| 79 | All types of SS material (Credit) |
| 80 | Water Purifier (Credit) |
| 81 | Supplying & erecting cast iron cable indicator plate buried along with route of cable for PVC / XLPE armoured cable as per specification No. CB-CIP |
| 82 | Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.Note:- 1) Standard accessories shall typically include :a) 'Z' section support -30 x 35 mm in size - 312 mm in length - 6 nos. support for one piece ladder of 2.5 m in length each.b) Anchor fastener & nut bolts of adequate size - 16 nos. ( 2 nos. per support)c) Coupler plates with hardware - 70 x 200 x 3 mm thick - 2 nos. for each piece of 2.5 m ladder complete with necessary accessories such as reducer, horizontal elbow & tee, up & down vertical elbow & bend, cross piece complete erected in approved manner.2) Provision for resting arrangement or support for perforated type cable tray shall be made separately as per iron work Item.3) Provision of cover for perforated type cable tray shall be made only where it is absolutely necessary and make sure for locking arrangement.4) Both type of cable trays shall be earthed properly. |
| 83 | Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 200 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.Note:- 1) Standard accessories shall typically include :a) 'Z' section support -30 x 35 mm in size - 312 mm in length - 6 nos. support for one piece ladder of 2.5 m in length each.b) Anchor fastener & nut bolts of adequate size - 16 nos. ( 2 nos. per support)c) Coupler plates with hardware - 70 x 200 x 3 mm thick - 2 nos. for each piece of 2.5 m ladder complete with necessary accessories such as reducer, horizontal elbow & tee, up & down vertical elbow & bend, cross piece complete erected in approved manner.2) Provision for resting arrangement or support for perforated type cable tray shall be made separately as per iron work Item.3) Provision of cover for perforated type cable tray shall be made only where it is absolutely necessary and make sure for locking arrangement.4) Both type of cable trays shall be earthed properly. |
| 84 | Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner. Note:- 1) Standard accessories shall typically include :a) 'Z' section support -30 x 35 mm in size - 312 mm in length - 6 nos. support for one piece ladder of 2.5 m in length each.b) Anchor fastener & nut bolts of adequate size - 16 nos. ( 2 nos. per support)c) Coupler plates with hardware - 70 x 200 x 3 mm thick - 2 nos. for each piece of 2.5 m ladder complete with necessary accessories such as reducer, horizontal elbow & tee, up & down vertical elbow & bend, cross piece complete erected in approved manner.2) Provision for resting arrangement or support for perforated type cable tray shall be made separately as per iron work Item.3) Provision of cover for perforated type cable tray shall be made only where it is absolutely necessary and make sure for locking arrangement.4) Both type of cable trays shall be earthed properly. |
| 85 | Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.Note:- 1) Standard accessories shall typically include :a) 'Z' section support -30 x 35 mm in size - 312 mm in length - 6 nos. support for one piece ladder of 2.5 m in length each.b) Anchor fastener & nut bolts of adequate size - 16 nos. ( 2 nos. per support)c) Coupler plates with hardware - 70 x 200 x 3 mm thick - 2 nos. for each piece of 2.5 m ladder complete with necessary accessories such as reducer, horizontal elbow & tee, up & down vertical elbow & bend, cross piece complete erected in approved manner.2) Provision for resting arrangement or support for perforated type cable tray shall be made separately as per iron work Item.3) Provision of cover for perforated type cable tray shall be made only where it is absolutely necessary and make sure for locking arrangement.4) Both type of cable trays shall be earthed properly. |
| 86 | Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 150 mm width & 20 mm height complete with necessary hardware. |
| 87 | Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 200 mm width & 20 mm height complete with necessary hardware. |
| 88 | Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 300 mm width & 20 mm height complete with necessary hardware. |
| 89 | Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 400 mm width & 100 mm height comprising all required standard accessories. ( CSR 22-23 : 7-11-4) |
| 90 | Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 500 mm width & 100 mm height comprising all required standard accessories. ( CSR 22-23 : 7-11-5) |
| 91 | Filling the holes and core cut with fire barrier sealants having minimum 3 hours fire rating to provide a tight and dependable seal against fire, smoke, toxic fumes and moisture and finishing in an approved manner etc complete. |
| 92 | Providing Core cut of 50 to 100 mm in Concrete ceiling / slab / column for thickness upto 2 feets in an approved manner etc complete. |
| 93 | Providing Core cut of 150 to 200 mm in Concrete ceiling / slab / column for thickness upto 2 feets in an approved manner etc complete. |
| 94 | Supply and erecting of Occupancy sensor light switch having a coverage of min. 6 metre dia at 3.6 metre with site adjustable off timing and instant ON / OFF. |
| 95 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 25 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 96 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 35 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 97 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 98 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 150 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 99 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 185 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 100 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 240 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 101 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 102 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 103 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 16 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 104 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 25 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 105 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 35 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 106 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 16 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 107 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 16 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 108 | Supplying & erecting minimum three & above star rated Centrifugal water pump (Monoblock), 415 V, three phase 50 cycles A.C. supply of 9.375 KW/ 12.5 HP with discharge 1320/670 Litres per Minute (LPM) for head of 21/52 m and 80 mm suction/ 65 mm delivery pipe of size, on provided C.C. foundation as per specification No. WP-CGP |
| 109 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 110 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 111 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 112 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 16 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 113 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 25 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 114 | Supplying, installing, testing and commissioning FR, XLPE armoured cable 12 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU |
| 115 | Supplying & erecting automatic control panel for 3 Ph, 415 volt, A.C.Submersible/centrifugal pump set up to 20 HP consisting of Star Delta starter having relay range 13-21 Amp, S.P.P., Combined ammeter/ voltmeter, phase indicating lamp enclosed in CRCA powder coated Vibration proof enclosure with IP 54 protection. Control Panel should offer single phasing, phase reversal, phase imbalance etc. |
| 116 | Supplying and laying (including excavation of suitable width & depth up to 90 cm)120 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete. |
| 117 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 200 mm outside dia, double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete. |
| 118 | Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 250 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 119 | Supplying and erecting integrated LED street light fitting 26 to 30W IP65 & IK08 class having single piece pressure die-cast aluminium housing , having system lumens output of Min. 2600 Lumens, min. efficacy of 100 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification No FG-ODF/FLS2. |
| 120 | Supplying and erecting integrated LED street light fitting 85-90W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 9300 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver \complete with 3 Years warranty as per specification No FG-ODF/FLS2. |
| 121 | Supplying and erecting Street light bracket for erection of Single fitting made from 40 mm. dia ‘B’ class G.I. pipe 1.0 m. in length along with pole cap of 300 mm length 100 mm dia duly welded as per specification no. FG-BKT/BPC |
| 122 | Supplying and erecting Street light bracket for erection of Double fitting made from 40 mm. dia ‘B’ class G.I. pipe 1.0 m. in length along with pole cap of 300 mm length 100 mm dia duly welded as per specification no. FGBKT/ BPC |
| 123 | Providing & erecting 6 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL |
| 124 | Supplying & erecting Aviation obstruction light consisting of yellow painted diecast aluminium alloy housing with Integral LED aviation light comprising of aluminium housing with polycarbonate enclosure complete. |
| 125 | Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity as 10 T/sq.m at 1.5 m depth including supply of steel, concrete, excavation, fixing provided nut bolts with the help of template, duly plastered as per design complete (for 3 to 5m octagonal / conical GI pole). |
| 126 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 127 | Supplying and erecting integrated LED flood light fitting Max. 70W IP65 & IK07 class having pressure die-cast aluminium housing, having system lumens output of Min. 8400 Lumens, min. efficacy of 120 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 140-270V, inbuilt surge protection of 4 kV, Life class of 50,000 Hrs. at L70B50, including driver with U shaped bracket with 3 Years warranty as per specification No FG-ODF/FLS2. |
| 128 | Supplying and erecting integrated LED Bollard Cylindrical/Cubical shaped 500mm 8W IP65 & IK10 class having extrusion aluminium housing with polycarbonate diffuser, having system lumens output of Min. 800 Lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 140-240V, inbuilt surge protection of 2 kV, Life class of 25,000 Hrs. at L50B50, including driver complete with 2 Year warranty as per specification No FG-ODF/FLS2. |
| 129 | Supplying and erecting integrated LED Post Top 45W IP65 & IK10 class having die cast aluminium housing with UV protected polycarbonate diffuser, having system lumens output of Min.4500 Lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 140-240V, inbuilt surge protection of 2 kV, Life class of 30,000 Hrs. at L50B50 , including driver complete with 2 Year warranty as per specification No FGODF/ FLS2. |
| 130 | Supplying and erecting integrated LED round burial light 6W IP65 & IK10 class having pressure die-cast housing, having system lumens output of Min. 500 Lumens, min. efficacy of 85 lumen/W, CRI>80, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 100-240V, inbuilt surge protection of 4 kV, Life class of 50,000 Hrs. at L50B50, including driver, salt spray tested for 500 Hrs. including making of recess of appropriate size for flushing into surface with 2 Year warranty as per specification No FG-ODF/FLS2. |
| 131 | Supplying and erecting Concealed type foot/step light Max. 5W having IP67. IK10 rated Pressure die cast housing having system lumens output of Min. 500 Lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 5000K, Beam Angle of 110 deg., THD<10%, SDCM<5, p.f. >0.95, operating range of 230-270V, surge protection of 2.5 kV, Life class of 25,000 Hrs. at L70B50, including driver by making necessary arrangement/recess in wall to make it flush with surface with 2 Year warranty. |
| 132 | Supplying & erecting integral post top lantern fixtures (light house type) suitable upto LED 18 W Lamp consisting of combination of spun aluminium canopy & clear acrylic top cover, cast aluminium pole cap on provided pole/ bracket as per specification no. FG-ODF/PTL |
| 133 | Supplying and erecting integrated LED Highbay Fitting 135W IP65 & IK08 class having die cast aluminium housing with polycarbonate diffuser with integrated optics, having system lumens output of Min. 20000 Lumens, min. efficacy of 145 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 140-240V, inbuilt surge protection of 4kV, Life class of 50,000 Hrs. at L50B50 , including driver complete with 3 Year warranty as per specification No FG-ODF/FLS2. |
| 134 | Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short -circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 135 | Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 136 | Supplying, erecting & marking DPMCB 6 A to 32 A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 137 | Supplying, erecting & commissioning 2 pole RCCB 16/25A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB |
| 138 | Supplying, erecting & marking FPMCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 139 | Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 140 | Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 141 | Supplying, fixing and commissioning 4 pole RCBO 63A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indications per specification no SW-RCCB/RCBO |
| 142 | Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TP MCBs total 8 ways /24 poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB |
| 143 | Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TP MCBs total 12 ways /36 poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB |
| 144 | Supplying & erecting triple pole and neutral distribution board (TPNDB),SPMCB of 8 ways / phase (24 poles), with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB |
| 145 | Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 12 ways /phase (36 poles), with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB |
| 146 | Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TP MCBs total 4 ways /12 Poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB |
| 147 | Supplying & erecting triple pole and neutral distribution board (TPNDB), 3 pole/ 4 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles), with door, 1.2mm thickness, surface/flush mounted, on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 |
| 148 | Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB |
| 149 | Point wiring for light/bell hybrid type (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/HW |
| 150 | Point wiring for ceiling fan (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/HW |
| 151 | Secondary point wiring for additional light/ bell point, concealed type in min 20 mm PVC conduit with 1.5 sq.mm. (2+1E) FR/FRLSH grade copper wires with required accessories as per specification No: WG-PW/CW |
| 152 | Wiring for plug on board with modular Switch socket concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW |
| 153 | Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connectionscomplete |
| 154 | Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connectionscomplete. |
| 155 | Supplying and erecting modular type 3 pin 6A multi socket with safety shutter, duly erected on provided plate and boxwith wiring connections complete. |
| 156 | Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete. |
| 157 | Supplying and erecting modular type indicator lamp, duly erected on provided plate and box with wiring connections complete. |
| 158 | Supplying and erecting modular type T.V. socket single outlet, duly erected on provided plate and box with wiringconnections complete |
| 159 | Supplying and erecting modular type blanking plate one module, duly erected on provided plate & box. |
| 160 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 161 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 162 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 163 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 4 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 164 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 165 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 8 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 166 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 12 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 167 | Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC. |
| 168 | Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC. |
| 169 | Supplying and erecting HMS PVC conduit FRLS grade 32 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC. |
| 170 | Supplying and laying HMS PVC conduit FRLS grade 32mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC. |
| 171 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 172 | Supplying and erecting mains with 3x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 173 | Supplying and erecting mains with 3x10 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 174 | Supplying and erecting mains with 4x16 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 175 | Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 225mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete. |
| 176 | Supplying and erecting Energy Saving BLDC Ceiling fan 230 V A.C. 50 cycles 1200 mm, max. energy consumption of 28W having service ratio (CMM/W) of Min. 8 , PF>0.9, THD<10% with IR remote control/compatible speed regulator, Temperature Rise of Max. 40 deg. C, having external mounted control PCB completely erected in position as per specification no. FG-FN/CF |
| 177 | Supplying & fixing anchor type fastener fan hook, with 2 nos. of 10 mm dia x 75 mm long with necessary materials for ceiling fan. |
| 178 | Supplying and erecting fan hook box of 10 mm M.S. round bar bounded to the R.C.C. bars upto 50 mm length each side and pierced through a 16 S.W.G. thick aluminium/M.S. Bowl 100 mm dia.or equivalent square size and having depth upto 75 mm complete erected with duly painted by one coat of red oxide paint and two coats of paint erected in position and within any leakage of slurry of cement concrete on either side of the box and positioned to the bottom level of the slab. |
| 179 | Supplying and erecting „B‟ grade G.I. pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire. |
| 180 | Supplying and erecting anodized aluminium corridor / passage / mirror light LED fitting (2 feet) Max. 12W with high transitivity diffuser with min. system lumens output of 1200 lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver with end caps on provided PVC Block / wooden board with 3 years warranty |
| 181 | Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Min.2200 lumens , min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%, THD<10%, p.f. >0.95,operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warranty. |
| 182 | Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., THD<10%, p.f. >0.95, operating range of 140-260V, in built surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, IP66, IK09 rated on provided PVC Block / wooden board with 3 years warranty. |
| 183 | Supplying and erecting LED square / circular Max. 18 W down lighter/ PANEL Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 184 | Supplying and erecting LED square / circular Max. 7W down lighter/ Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 770 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 185 | Supplying and erecting lumiNous / modular type call bell indicator with plastic body, heavy duty coil and indicator lamp working on 230V A.C. supply with resetting arrangement complete erected on double wooden/ sunmica board |
| 186 | Supplying and erecting LED Panel Light(600mm X 600mm) Max. 35 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min 4200 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50 including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 187 | Supplying and erecting rectangular shaped LED Panel Light(1200mm X 300mm) Max. 35 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min. 4200 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 188 | Supplying and erecting LED Strip light 5m Length Max. 45 W IP20 class having minimum lumens output of 800 Lumens/m, min. efficacy of 90 lumen/W, CRI>80, CCT upto 5000K, Beam Angle of 110 deg., THD<10%, p.f. >0.95, operating range of 230-270V, Life class of 30,000 Hrs. at L70B50, including driver with 1 year warranty. |
| 189 | Supplying and erecting square /round shaped CRCA /die-cast aluminium powder coated housing 13W LED COB MODULE LIGHT with Golden/White ring Model No.: PRO-124 down lighter type I housing Material:Aluminium Power:13W Light Source: CREE LED Col.Temp.:3000K/4000K Beam Angle:30°CRI >80 Current: DC 350mA fixed to the housing complete. |
| 190 | Supplying & erecting original 1.25 mm CRCA sheet metal enclosures with 20A, 2 pin plug & earth socket and 20A. 3 pin plug top with 20A/30A single pole MCB complete erected on angle iron/ GI frame. |
| 191 | Supplying, erecting, testing and commissioning selfcontained water cooler 230/250 V 50 cycles nominal cooling capacity of 80 litres/hr and storage capacity 120 litres with partially stainless steel body complete. specification no. AP-WCR/WC |
| 192 | Supplying and erecting ultra violet storage type water purifier (RO+UV+UF) with softener for safe drinking water consisting of UV germicidal tube of 8W capacity choke made of copper wire and two indicator lamps with output of purified water minimum 0.33 litre/min with activated carbon filter and softener operating on 230V, single phase A.C. supply with UV fail & filter change indication system .(for TDS more than 200) |
| 193 | Supplying, installing, testing and commissioning of 25 kWp ON-GRID Solar PV System / Plant consisting Solar PV Poly Crystalline Panel (335 Wp X 75 Nos.) and Solar ON-GRID Inverter of similar capacity (THD<3%) with interconnecting wires / cables up to solar ON GRID inverter, proper base plate, canopy box to house Inverter and necessary accessories i.e. ACDB/ DCDB , MCB etc. wiring up to solar Inverter in casing and capping, display board, sign board, two distinct earthing, lightning arrester, liaisoning charges, remote monitoring system with maintaining card / chip for 5 years including net charges for RMS System, complete up to net meter installation and export to the grid with 5 year ON-SITE warranty and fully comprehensive maintenance contract as per Specification no. ESD-RT-ONG. |
| 194 | Supplying and erecting LT CT multifunction DLMS compliance energymeter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measure & display trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected to CTs. |
| 195 | PVC armoured/unarmoured cables and wires (Aluminium) (Credit) |
| 196 | PVC armoured / unarmoured cables and wires (Copper) (Credit) |
| 197 | HG / M.S / G.I. Materials / Poles etc. (Credit) |
| 198 | I.C. / M.C. switches / D.P. / D.B./ T.P. / feeder pillar etc. (Credit) |
| 199 | Ceiling/cabin/bracket/pedestal/table fan. (Credit) |
| 200 | Exhaust Fan 9\\" Sweep (Credit) |
| 201 | Fluorescent fittings (Credit) |
| 202 | Accessories such as tube starter / bell / holder/ ceiling rose /MCB/MCCB/Contactor/PT etc. (Credit) |
| 203 | Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC |
| 204 | Supply, installation, testing and Commissioning of 40mm HDPE Pipe (Standard ISI mark) as per the requirement &complete in all respect and as directed to the satisfaction of engineer. |
| 205 | Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. With necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC. |
| 206 | Supplying and erecting HMS PVC conduit FRLS grade 32 mm dia. With necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC. |
| 207 | Supplying and laying HMS PVC conduit FRLS grade 32mm dia. withnecessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC. |
| 208 | Supplying and erecting PVC box trunking of size 50x50 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX. With |
| 209 | Supplying and erecting PVC box trunking of size 75x50 mm.with accessories on wall/ceiling as per specification No: WG-MA/BOX. |
| 210 | Supplying and erecting PVC box trunking of size 75x75 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX. |
| 211 | Supplying and erecting PVC box trunking of size 100x50 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX. |
| 212 | Supplying and installing enhanced cat-6 cable with 4-connector channel, performance test report as per ANSI/TIA-568.2-D suitable for networking complete as per specification. |
| 213 | Supplying and installing cat-6 cable with rodent proof and anti termite jacket suitable for networking as per specification No. WG-COC/NC |
| 214 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 215 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 216 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 4 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 217 | upplying and fixing tool-less IO (Ethernet) flush/surface type in provided modular box as per specification no. WG-NAS/IO |
| 218 | Supplying and fixing 1 m length, UTP patch cord of enhanced Cat 6 type with 4-connector channel, performance test report as per ANSI/TIA-568.2-D in position as per specification No. WG-COC/PC |
| 219 | Supplying and fixing 2 m UTP patch cord of cat 6 type in position as per specification No. WG-COC/PC |
| 220 | Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG-NAS/PP |
| 221 | Testing and commissioning of Pentascanning test for CAT 6A cable as per the technical specificaton mentioned and as per the requirement & complete in all respect and as directed to the satisfaction of engineer. |
| 222 | Testing and commissioning of OLTS (Optical loss test through OTDR) test for OFC as per the technical specificaton mentioned and as per the requirement & complete in all respect and as directed to the satisfaction of engineer. |
| 223 | Supplying and fixing 15U wall mount rack (Dimension-DxWxH – 500x600x767 mm) as per specification No. WG-NAS/RAK |
| 224 | Supplying and fixing 42U floor mount server rack (Dimension-DxWxH – 800x600x1866 mm) as per specification No. WG-NAS/RAK |
| 225 | Supplying and erecting LSZH armoured multimode optical fibre cable with 12 fibres, core dia 50/125 μm (OM4) suitable up to 10 GBPS ethernet distance at 850 nm of wavelength, on wall/ceiling or laid in provided pipe/trench as per specification No. WG-COC/OFC |
| 226 | Supplying and fixing SC/LC type multimode pigtails (OM4) as perspecification complete. WG-NAS/LIU2 |
| 227 | Supplying and fixing 12 ports light guide unloaded interconnect unit, wall mounted type, with adapter panel for termination of optical fibre cables on wall in provided U rack complete as per specification no. WG-NAS/ LIU |
| 228 | Supplying and fixing 24 ports light guide unloaded interconnect unit, rack mounted type, with adapter panel for termination of optical fibre cables in provided U rack complete as per specification no. WG-NAS/ LIU |
| 229 | Supplying and fixing SC/LC type multimode duplex adapter to couple two connectors between OFC & Fibre switch/Fibre module as per specification no. WG-NAS/MMA |
| 230 | Supply, installation, testing and commissioning of Layer 3 Core Switch (24x10G) as per the technical specification mentionedand as per the requirement & complete in all respect and as directed to the satisfaction of engineer. |
| 231 | Supplying, fixing, and configuring 24 ports + (4 SFP+) ports Managed Layer 2 switch of and web View/CLI, 6KV surge protection on ethernet port and console port for management as per specification complete. |
| 232 | Supplying, fixing, and configuring 24 ports + 4 (SFP+) port, Managed Layer 2, POE Switch of , 370W, 6KV surge protection on ethernet port and console port for management erected in provided rack complete. |
| 233 | Supplying, fixing, and configuring 8-ports managed gigabit, Layer-2 switch, 10/100/1000 base-T, POE smart switch plus 2 SFP erected in provided rack complete. |
| 234 | Supplying, fixing, and configuring 10G Base -SR (SFP+) simplex MMtransceiver erected in provided rack complete. |
| 235 | Supplying, fixing, and configuring 1-port mini-GBIC SX MM fibre transceiver (up to 550m, support 3.3V power) erected in provided rack complete. |
| 236 | Supplying, erecting & commissioning 100 pairs M.S. junction box made from min. 1.5mm thick MS sheet as per specification no. WG-TW |
| 237 | Supplying, erecting & commissioning 50 pairs FR junction box with moulded plastic enclosure as per specification no. WG-TW |
| 238 | Supplying, erecting & commissioning MDF Box 800x800 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW |
| 239 | Supplying & erecting 100 pair, 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW |
| 240 | Supplying & erecting 50 pair, 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW |
| 241 | Supplying & erecting 20 pair, 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW |
| 242 | Supplying & erecting 0.5 mm dia, copper jumper wire as per specification No. WG-TW |
| 243 | Supplying, erecting & commissioning 10 pair module for connection & disconnection of telephone cable as per specification no. WG-TW |
| 244 | PVC armoured / unarmoured cables and wires (Copper) (Credit) |
| 245 | HG / M.S / G.I. Materials / Poles etc. (Credit) |
| 246 | PVC pipes/materials (Credit) |
| 247 | Supplying, installing, testing and commissioning of AHRI Certified Water Cooled Centrifugal Water Chilling Machines (With VFD) . Chiller shall be with simgle Centrifugal compressor. The delivered capacity of each machine shall be 600 TR (Actual) at the design conditions mentioned below and comprise of machine/floor mounted motor with VFD starter, water cooled condenser, refrigerant piping and control wiring, Factory filled first charge of refrigerant & oil and accessories including safety controls mounted in central micro-processor based console panel, sockets, flow switches, sensors, cable termination adopter box with suitable rating of 4 pole MCCB/ACB/ as per OEM Standards. Refrigerant used as shall be Ozone friendly R-134 A. Vibration isolators as neoprene rubber pads shall be provided for the chiller and included in price. (2W + 2S) Evaporator shall be factory insulated with 19 mm Thick Nitrile Rubber/Elastomeric Foam as per OEM standard. DP switch to be provided at evaporator and condenser duly interlocked for safe operation of chiller. Centrifugal Compressor shall be chiller OEM make only.Unit mounted/Floor mounted Air cooled VFD to be provided. In case of floor mounted VFD, the cost of cabling from VFD to chiller shall be included in the chiller price.Chiller should be having stepless capacity control from 100% to 10% load at constant condesner entering water temprature. Chiller should compatible for Aluminium cable termination or Junction box to be considered for Aluminium cable incomer. Flange end connections with matching flanges for chiller and condenser at inlet & outlet to be considered. BMS card shall be included in the price and vendor shall provide open protocol and suitable to connect with Modbus/ Lonwork/ Bacnet Motor suitable for 415±5% V, 50 Hz, 3 phase AC supply. Factory Witness of #1no. of Chiller at design Condition at constant condenser entering water temp. at following point load to be provided.Testing of chiller should be only with VFD which is to be supplied at site with chiller.Testing with Sample VFD in factory is not acceptable.Point load:1) 100 % Load2) 75% Load3) 50% Load4) 25% Load The Evaporator performance shall be as follows: Chilled Water Temperature- Inlet - 53.60 °F ( 12.0 Deg C) Chilled Water Temperature- Outlet - 44.60 °F ( 7.0 Deg C) Fouling Factor - 0.0005 FPS Flow rate of Evaporator: 1550 USGPM Pressure Drop - Max. 8 mtr of head The Condenser performance shall be as follows: Condenser Water Temperature- Inlet - 89.60°F (32 Deg C) Outlet Chilled Water Temperature- outlet - 96.80°F ( 36 Deg C) Fouling Factor - 0.001 FPS Flow Rate of condenser: 2280 USGPM Pressure Drop - Max. 8 mtr of head Performance Parameters:Minimum COP at AHRI conditions shall be 6.3 or more at 580TR capacity and IPLV 0.34 kw/TR or less. Maximum IkW/ TR at 100% Load - 0.65 kw/Tr or less, NPLV 0.35 kw/Tr or less at design conditions. Unit should be AHRI Certified and BEE Certified having Minium 4 Star Rating Supplying, erecting, testing, and commissioning of digital active 150 A harmonic filter cum power conditioner, with digital closed loop active filter with source current sensing, 32 bit digital signal processing with less than 1 millisecond response time, high speed IGBTs in power circuit with necessary CTs to be mounted on existing cable/bus and shunted to supply along with digital display showing voltage, current, frequency, kW, kVA, kVAr , PF, VTHD, ITHD and waveform with alarm for 3 phase 4 wire system as per specification No. CP-ED/DAHF |
| 248 | Supplying, erecting, testing, and commissioning of digital active 150 A harmonic filter cum power conditioner, with digital closed loop active filter with source current sensing, 32 bit digital signal processing with less than 1 millisecond response time, high speed IGBTs in power circuit with necessary CTs to be mounted on existing cable/bus and shunted to supply along with digital display showing voltage, current, frequency, kW, kVA, kVAr , PF, VTHD, ITHD and waveform with alarm for 3 phase 4 wire system as per specification No. CP-ED/DAHF |
| 249 | Supply, installation, testing and commissioning of vertical Inline Primary Pump which is mounted on a common base with electric motor for re-circulation of water for the central air conditioning system. The pumps shall be flexible coupled protected by OSHA complaint coupling guard, with CI casing, SS (CF8) /bronze impeller, high strength steel shaft (prefarably SS 304) and MS fabricated base plate .The pump motor shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply of (IE3) efficiency class. Motor shall be squirrel cage, Class F insulation, 1500 RPM (Max.) Pump, base, coupling and motor shall be factory assembled. The capacity of motor shall be at least 10% in excess of BHP requirement of pump. The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit. Minimum efficiency of pump shall be as mentioned below including pump foundation, suitable support/Mounting Arrangement including making connection of inlet & outlet with fittings including nut, bolts, packing etc.) with plaster, Anti vibration arrangement of cushy foot mountings is deemed to be included in this item cost. Flotrex valve and Suction guide to be provided by pump manufacturar for unit responsability. Pumps and Valves duly insulated with 25mm thick Class O Nitrile Rubber Sheet. Pump curves & loss calculations shall be furnished during approval from competant authority. Pumps shall be BMS compatible.Pump rating shall be PN 16 preferably. (Primary Pump)Water flow rate: 1500USGPM, Static head: 20 mtr, Impeller: Bronze, Efficiency: NLT 80% (2W +2S) |
| 250 | Supply, installation, testing and commissioning of Vertical Inline Secondary Pump which is mounted on a common base with electric motor for re-circulation of water for the central air conditioning system. The pumps shall be flexible coupled protected by OSHA complaint coupling guard, with CI casing, SS (CF8)/bronze impeller, high strength steel shaft (prefarably SS 304) and MS fabricated base plate .The pump motor shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply of (IE3) efficiency class. Motor shall be squirrel cage, Class F insulation, 1500 RPM (Max.). Pump, base, coupling and motor shall be factory assembled. The capacity of motor shall be at least 10% in excess of BHP requirement of pump. The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit. Minimum efficiency of pump shall be as mentioned below. This includes pump foundation, suitable support/Mounting Arrangement including making connection of inlet & outlet with fittings including nut, bolts, packing etc.) with plaster. Pumps Shall be BMS & VFD compatible. Flotrex Valve and Suction guide to be provided by pump manufacturar for unit responsability. Pumps and Valves duly insulated with 25mm thick Class O Nitrile Rubber Sheet. Contractor to submit proposed pump model with duty curve. Pump rating shall be PN 16. The chilled water pumps shall also include the cost of thermal insulation. Secondary chilled water pumps shall be suitable for operation on variable frequency drives & conforming to the specifications of variable speed pumping system. The capacity of motor shall be at least 10% in excess of BHP requirement of pump wiht following specifications: Water flow rate: 2280 USGPM, Static head: 40 mtr, Impeller: Bronze, Efficiency: NLT 80% (2W +2S) (Secondary Pump) |
| 251 | Supply, installation, testing and commissioning of vertical Inline Pump mounted on a common base with electric motor for re-circulation of water for the central air conditioning system. The pumps shall be flexible coupled protected by OSHA complaint coupling guard, with CI casing, SS (CF8) /bronze impeller, high strength steel shaft (prefarably SS 304) and MS fabricated base plate .The pump motor shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply of (IE3) efficiency class. Motor shall be squirrel cage, Class F insulation, 1500 RPM (Max.) Pump, base, coupling and motor shall be factory assembled. The capacity of motor shall be at least 10% in excess of BHP requirement of pump. The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit. Minimum efficiency of pump shall be as mentioned below including pump foundation, suitable support/Mounting Arrangement including making connection of inlet & outlet with fittings including nut, bolts, packing etc.) with plaster, Anti vibration arrangement of cushy foot mountings is deemed to be included in this item cost. Flotrex valve and Suction guide to be provided by pump manufacturar for unit responsability. Pump curves & loss calculations shall be furnished during approval from competant authority. Pumps shall be BMS compatible.Pump rating shall be PN 16 preferably. Water flow rate: 2280USGPM, Static head: 33 mtr, Impeller: Bronze, Efficiency: NLT 80% (2W + 2S) (Condenser Pump) |
| 252 | Supplying, installing, testing and commissioning of FRP cooling tower with FRP water basin, PVC fillings with integral louvers and drift eliminators complete with hot water basin either fitted with spray nozzles or having self rotating sprinkles, statically and dynamically balanced axial flow type fan-direct driven or driven through reduction gear box with TEFC induction motor, suction screen, make up-quick fill arrangement, overflow and drain connections with necessary valves and suitable inspection ladder, access arrangement for cooling tower interior, cement concrete foundation, steel/mesonary supporting structure, anti-vibration mountings etc. complete as per specifications and as required.Cooling Tower Multicell Type (CTI Certified) As Per Specification with following operating parameters : (3W+1S) (Cooling Tower)Wet Bulb Temp. - 27.2° CEntering Water Temp. - 32.0° CLeaving Water Temp. - 37.5° CTotal Flow Rate - 2250 GPM (2W+2S) |
| 253 | Supplying, installing, testing and commissioning of PRESSURISED COLD WATER EXPANSION TANK WITH AIR SEPARATER with S.S braided pipe flexible connector suitable for total volume of water in cold water circuits along with necessary accessories such as centrifugal air separator, pumps etc. in order to keep cold water system under (+) pressure and to prevent entrapment of pressure and to prevent entrapment of air in the system. The tank shall be precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have 50 MM system connection and 20 mm drain and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The complete system shall be sourced from single manufacturer and supplied and installed with all accessories and safety fixtures and safety fixtures required for proper functioning of the complete hydronic system. The expansion tank shall be supplied along with pressurization unit.The unit shall be housed in powder-painted canopy suitable for external installation, if required.The capacity of tank shall be 3000 GPM approx. (for chilled water system). |
| 254 | Supply, Installation, Testing, Commissioning of Pressurization Unit shall consist of two Nos. (1 working + 1 stand-by) high pressure pumps of suitable pressure rating mounted on M.S. frame, complete with interconnecting piping, isolation valves, NRV, Y-strainer, pressure gauge, pressure transmitter, auto-logic panel (IP55) with dry-run protection, electrical MCB and interconnecting wiring. The unit shall be housed in powder-painted canopy suitable for external installation, if required. Flow:2 CMH, Head: 25 m Water Column. |
| 255 | Supply, installation, testing and commissioning of a combined Air and Dirt Separator of M.S construction as per specifications on the return water line located at the pump suction or a suitable location as suggested. The separator should be complete with high capacity air vent, service valve, butterfly valve, flanges, drain valve etc. of below sizes:-300 mm Dia Air Separator , duly insulated.(for chilled water circuit) (Air Dirt Seprator) |
| 256 | Supply, installation, testing and commissioning of Ceiling Suspended/Floor Mounted Chilled water double skin Air Handling Unit of mentioned capacities below. Air Handling Unit shall have Double Skin Construction of 50 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD water cooled coil. Cooling coil shall have 12.7 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS. Note ESP Shall be 50mm and It shall be verify from contractor from construction drawings before ordering. AHU CAPACITY- 23000 CFM |
| 257 | Supply, installation, testing and commissioning of Ceiling Suspended/Floor Mounted Chilled water double skin Air Handling Unit of mentioned capacities below. Air Handling Unit shall have Double Skin Construction of 50 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD water cooled coil. Cooling coil shall have 12.7 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS. Note ESP Shall be 50mm and It shall be verify from contractor from construction drawings before ordering. AHU CAPACITY- 18500 CFM |
| 258 | Supply, installation, testing and commissioning of Ceiling Suspended/Floor Mounted Chilled water double skin Air Handling Unit of mentioned capacities below. Air Handling Unit shall have Double Skin Construction of 50 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD water cooled coil. Cooling coil shall have 12.7 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS. Note ESP Shall be 50mm and It shall be verify from contractor from construction drawings before ordering. AHU CAPACITY- 13600 CFM |
| 259 | Supply, installation, testing and commissioning of Ceiling Suspended/Floor Mounted Chilled water double skin Air Handling Unit of mentioned capacities below. Air Handling Unit shall have Double Skin Construction of 50 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD water cooled coil. Cooling coil shall have 12.7 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS. Note ESP Shall be 50mm and It shall be verify from contractor from construction drawings before ordering. AHU CAPACITY- 12800 CFM |
| 260 | Supply, installation, testing and commissioning of Ceiling Suspended/Floor Mounted Chilled water double skin Air Handling Unit of mentioned capacities below. Air Handling Unit shall have Double Skin Construction of 50 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD water cooled coil. Cooling coil shall have 12.7 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS. Note ESP Shall be 50mm and It shall be verify from contractor from construction drawings before ordering. AHU CAPACITY- 11200 CFM |
| 261 | Supply, installation, testing and commissioning of Ceiling Suspended/Floor Mounted Chilled water double skin Air Handling Unit of mentioned capacities below. Air Handling Unit shall have Double Skin Construction of 50 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD water cooled coil. Cooling coil shall have 12.7 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS. Note ESP Shall be 50mm and It shall be verify from contractor from construction drawings before ordering. AHU CAPACITY- 9000 CFM |
| 262 | Supply, installation, testing and commissioning of Ceiling Suspended/Fan Coil Unit Chilled water double skin Air Handling Unit of mentioned capacities below. Air Handling Unit shall have Double Skin Construction of 50 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD water cooled coil. Cooling coil shall have 12.7 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS. Note ESP Shall be 50mm and It shall be verify from contractor from construction drawings before ordering. AHU CAPACITY- 3000 CFM |
| 263 | Supply, installation, testing and commissioning of Ceiling Suspended/Fan Coil Unit Chilled water double skin Air Handling Unit of mentioned capacities below. Air Handling Unit shall have Double Skin Construction of 50 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD water cooled coil. Cooling coil shall have 12.7 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS. Note ESP Shall be 50mm and It shall be verify from contractor from construction drawings before ordering. AHU CAPACITY- 2000 CFM |
| 264 | Supply, Installation, Testing & Commissioning of Cassette Type Fan Coil Unit for Water Cooled Chiller Air Conditioning System complete with chilled water cooling coil, 2-way / 3-way motorized valve, insulated condensate drain piping connection, factory fitted drain pump, washable air filter, wired / cordless remote controller, hanging arrangement, vibration isolators and all necessary accessories required for proper operation, duly insulated and tested & commissioned as per site requirement. Capacity : 1200 CFM,Model No. : MKA-1200N,Quantity : 1 Main Unit + 1 Panel Unit. |
| 265 | Supply, Installation, Testing & Commissioning of Readymade AHU Valve Station complete with Butterfly Valves 5 Nos.,Y strainer-1 No.,PIBC Valve with Actuator & Sensor complete with bypass line, with temp.and pressure gauges to inlet & outlet lines, duly painted & insulated with Closed cell Nitrile Rubber Insulation of suitable thickness nitrile rubber of 25 mm thickness with Chemically Treated Woven Glass Fibre Covering for following AHUs as per requirement.AHU 23000 CFM (100 MM PIPE SIZE) |
| 266 | Supply, Installation, Testing & Commissioning of Readymade AHU Valve Station complete with Butterfly Valves 5 Nos.,Y strainer-1 No.,PIBC Valve with Actuator & Sensor complete with bypass line, with temp.and pressure gauges to inlet & outlet lines, duly painted & insulated with Closed cell Nitrile Rubber Insulation of suitable thickness nitrile rubber of 25 mm thickness with Chemically Treated Woven Glass Fibre Covering for following AHUs as per requirement.AHU 12800 CFM (80 MM PIPE SIZE) |
| 267 | Supply, Installation, Testing & Commissioning of Readymade AHU Valve Station complete with Butterfly Valves 5 Nos.,Y strainer-1 No.,PIBC Valve with Actuator & Sensor complete with bypass line, with temp.and pressure gauges to inlet & outlet lines, duly painted & insulated with Closed cell Nitrile Rubber Insulation of suitable thickness nitrile rubber of 25 mm thickness with Chemically Treated Woven Glass Fibre Covering for following AHUs as per requirement.AHU 11200 CFM (65 MM PIPE SIZE) |
| 268 | Supply, Installation, Testing & Commissioning of Readymade AHU Valve Station complete with Butterfly Valves 5 Nos.,Y strainer-1 No.,PIBC Valve with Actuator & Sensor complete with bypass line, with temp.and pressure gauges to inlet & outlet lines, duly painted & insulated with Closed cell Nitrile Rubber Insulation of suitable thickness nitrile rubber of 25 mm thickness with Chemically Treated Woven Glass Fibre Covering for following AHUs as per requirement.AHU 3000 CFM (40 MM PIPE SIZE) |
| 269 | Supply, Installation, Testing & Commissioning of Readymade AHU Valve Station complete with Butterfly Valves 5 Nos.,Y strainer-1 No.,PIBC Valve with Actuator & Sensor complete with bypass line, with temp.and pressure gauges to inlet & outlet lines, duly painted & insulated with Closed cell Nitrile Rubber Insulation of suitable thickness nitrile rubber of 25 mm thickness with Chemically Treated Woven Glass Fibre Covering for following AHUs as per requirement.AHU 2000 CFM (32 MM PIPE SIZE) |
| 270 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 500 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 271 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 450 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 272 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 400 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 273 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 350 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 274 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 300 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 275 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 250 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 276 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 200 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 277 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 150 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 278 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 125 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 279 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 100 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 280 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 80 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 281 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 65 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 282 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 50 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 283 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 40 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 284 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 32 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 285 | Supply Installation of MS 'C' class chilled water pipe line / drain linealong with accessories and thermal insulation of Class O nitrile rubber M.S. 25 mm 'C' class Varoius Diameter of piping confirming to IS: 1239/3569 heavy class Chilled water piping including all necessary fitting like anchor fasteners, Including Puff Support, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. All indoor piping & valves insulated 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' Nitrile Rubber finished with factory laminated Aluminkum Foil . All expose piping & valves insulated with Nitrile Rubber finished with 26 guage alluminum cladding. Insulation Thickness shall be 25 mm upto 50 mm dia Pipe, 32mm thick from 65 mm dia to 200 mm dia, 38 mm thick above 200 mm dia. |
| 286 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 500 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 287 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 450 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 288 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 300 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 289 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 250 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 290 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 200 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 291 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 150 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 292 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 100 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 293 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 80 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 294 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 65 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 295 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 50 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 296 | Supply Installation of MS 'C' class condenser water pipe line along with accessories. M.S. 'C' class 40 mm Dia of piping confirming to IS: 1239/3569 heavy class Condenser water piping including all necessary fitting like anchor fasteners, pipe supporting frame structure, couplings, seamless bends, elbows, Tees, union, reducers, expander ASA 150 ISRF flanges, CAF gaskets, nuts & bolts etc. |
| 297 | Supply, Installation and testing of UPVC 483 piping with 9 mm thick class 'O' nitrile rubber insulation with elbow, bends, tees, clean outs etc. complete with all necessary accessories for 40 mm dia. drain pipe. |
| 298 | Supply, Installation and testing of UPVC 483 piping with 9 mm thick class 'O' nitrile rubber insulation with elbow, bends, tees, clean outs etc. complete with all necessary accessories for 32 mm dia. drain pipe. |
| 299 | Supply, Installation and testing of UPVC 483 piping with 9 mm thick class 'O' nitrile rubber Insulation with elbow, bends, tees, clean outs etc. complete with all necessary accessories for 25 mm dia. drain pipe. |
| 300 | Carrying out core cutting of size 3'' to 5'' dia x 15'' length in the c.c./rock/stone wall with help of specialized core cutting machine in proper manner and finishing the site as original. |
| 301 | Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. |
| 302 | SITC of Triple Duty Valve Primary, Secondary and condenser pumps 250m dia Valve Furnish and install on the discharge side of each pump . Each valve is to incorporate the following three functions in one body: It features a calibrated balancevalve, non-slam check valve, and positive shut-off valve all rolled into one.Tight shut-off, spring-closure type silent non-slam check and effective throttling with flow measurement capability. The body shall have (2) 1/4” NPT connections on each side of the valve seat. Two connections to have brass pressure and temperature metering ports, with Nordel check valves and gasketed caps. Two other connections to be supplied with brass drain plugs. Metering ports are to be interchangeable with drain ports to allow for measurement flexibility when installed in tight locations. The valve disc shall be bronze plug & disc type with high impact engineered resin seat to ensure tight shut-off and silent check operation. The valve stem shall be stainless steel with flat surfaces provided for adjustment with open-end wrench. For Grooved Piping: Valve body shall be ductile iron with grooved ends and Armstrong anti-rotation ArmgripTM lugs on the inlet and outlet of the body. Flange adapters, where necessary, are to be PN16 or PN25 ductile iron flanges with antirotation lugs and EPT gaskets. For Welded Flange Piping: (For 10 bar flanges:) Valve body shall be Cast Iron with PN16 flanged ports. (For 20 bar flanges:) Valve body shall be Ductile Iron with PN25 flanged ports. The valve shall be selected and installed in accordance with the manufacturer’s instructions and be suitable for the pressure and temperature specified. |
| 303 | SITC of Suction Guide and strainer Primary, Secondary and condenser pumps 250m dia Valve Furnish and install on the suction of each pump an Suction Guide, with Outlet Flow Stabilizing Guide Vanes, removable Stainless Steel Strainer and Fine Mesh Start-up Strainer. (For 10 bar flanged pipe:) Supply valve with Cast Iron body with PN16 flanged ports. The mechanical contractor shall inspect the strainer prior to activating the pump and, further, shall remove the Fine Mesh Start-up Strainer after a short running period. (24 hours maximum). Space shall provided for removal of the Strainer and connection of a blow-down valve |
| 304 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG |
| 305 | SITC of of Temp Gauge with thermowell of approved Make & Range 0-50 Deg C , Dial Size 100 mm.The Temp. Guage to be of Industrial type and all Internal working Parts in SS 304 Quality. Sensor Probe Length - apx. 200mm.As per technical specification mention in tender. |
| 306 | Supplying and erecting GI sheet 1.25 mm (18 SWG) having zinc coating of 350 microns with galvanization process compliance to IS 2629:1985 to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint. |
| 307 | Supplying and erecting GI sheet 1.6 mm (16 SWG) having zinc coating of 350 microns with galvanization process compliance to IS 2629:1985 to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint. |
| 308 | Providing adhesive thermal insulation for supply return air duct with 19mm nitrile rubber insulation having R-value as per the prevailing provisions in ECBC2017. |
| 309 | Supply & Installation of 20 mm thick open cell nitrile insulation.it shall be FM approved & UL94 tested .thermal conductivity of insulation should be 0.034W/mk at 25deg C. |
| 310 | Supplying and installing of collar damper of galvanised iron material of upto 120 microns for anti corrosive resistance for supply air grill of suitable size. |
| 311 | Supplying and erecting aluminium powder coated linear grill of suitable size for width length without collar dampers having matching colour with the existing false ceiling and suitable for deflection of 15/30/45°. |
| 312 | SITC of extruded aluminium louvers with frame bird screen 50mm prefilter frame, mounted arrangement etc. as per specification and drawing. |
| 313 | Supply, installation, testing and commissioning Dampers.(Fire Dampers G.I shall meet the fire resistance rating of 2 hours as per UL555 and shall be tested and certified by CBRI.Fire Damper frame shall be galvanized steel of 1.6mm thickness, formed into a C channel in 4-piece construction with flanges suitable for duct connection. Damper Blades shall be single skin galvanized steel of 1.6mm thickness and must have 3 accurately rollformed longitudinal grooves for reinforcement and proper closure and operation. The blades shall be arranged in parallel to provide positive shut off. Each Blade shall have axles supported on both sides with sintered bronze self lubricating bearings turning in an extruded hole in the frame. All Blades shall be interconnected using linkage in the frame section . Each Damper shall be operated through a actuator. Each Damper shall be supplied with a factory mounted sleeve made from Minimum 1mm thick galvanized steel of minimum 250mm length) |
| 314 | Supply, Installation, Testing & Commissioning of Fusible link type fire damper. Should be UL (555) listed & CBRI approved.With one or 2 side flanges as per the site condition. Fire rating should be 1 1/2 hrs as per the UL 555. Blades shall be held in position throueh fusible link of temo. of 74 deg.C. |
| 315 | Supply, installation, testing and commissioning of volume control box with collar for control damper of required sizes in GI construction with operating mechanism, mounting arrangement, rubber refrigerant kits etc. complete. |
| 316 | Supply, Installation, Testing & Commissioning (SITC) of Variable Air Volume (VAV) Box complete with factory-fabricated casing, airflow sensor, volume control damper, actuator, controller, and all necessary accessories. Complete as required for proper operation. |
| 317 | Supplying & erecting tile type modular diffuser made from aluminium sheet with powder coated matching to the ceiling shade for provided supply and return air complete. |
| 318 | Supply, fabrication, installation and testing of flexible canvas connections constructed between ductable unit/dampers/ducting of suitable size with fire resist flexible double canvas sleeve complete. |
| 319 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps). |
| 320 | Making cement concrete foundation including excavation (60 x 60 x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay). |
| 321 | HVAC Plant Room Panel (Panel Must conform to IEC 61439 part 1 & 2)Design, fabrication, assembling, wiring, supply, installation, testing & commissioning of motor control centre, which shall be fabricated out of 2 mm thick CRCA sheet steel in form in 3b formation with reinforcement of suitable size angle iron, channel, T section iron & / flat wherever necessary. Cable gland plates shall be provided on top as well as at bottom of teh panels. Panels shall be treated with anti corrosive process before painting as per specifications with 2 caots of red oxide primer & final approved shade of powder coated paint. 2 No. earthing terminals shall be provided for 3 phase, 415 V, 4 wire, 50 Hz supply systems. Liftinmg hooks shall also be provided in case of large panels.Approval shall be taken for panel before fabrication.INCOMER1 No. of 3200 A 4P EDO Type ACB (50 KA) with microprocessor based release.8 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's, 7 Sets - 0-500 V, 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB. with suitable Switchgear with Surge, Earth Leak Protection and BMS Compatible.OUTGOING :-630A FP MCCB - 6160A FP MCCB - 12400A FP MCCB - 2100A FP MCCB - 2All Outgoing Feeders shall be provided with ON, OFF, TRIP Indication Lamps (LED Type), suitable range multifuncation meteres with Selector Switch. |
| 322 | Cooling Tower Power Distribution Panel (Panel Must conform to IEC 61439 part 1 & 2)Design, fabrication, assembling, wiring, supply, installation, testing & commissioning of motor control centre, which shall be fabricated out of 2 mm thick CRCA sheet steel in form in 3b formation with reinforcement of suitable size angle iron, channel, T section iron & / flat wherever necessary. Cable gland plates shall be provided on top as well as at bottom of teh panels. Panels shall be treated with anti corrosive process before painting as per specifications with 2 caots of red oxide primer & final approved shade of powder coated paint. 2 No. earthing terminals shall be provided for 3 phase, 415 V, 4 wire, 50 Hz supply systems. Liftinmg hooks shall also be provided in case of large panels.Approval shall be taken for No. panel before fabrication. COOLING TOWER PANEL1 No. of 400 A 4P MP, MCCB (36 KA) 1 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's, 1 Sets - 0-500 V, 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.5 Sets Indicating LED lamps for MCCB ON/OFF/ TRIP with protective SP MCB's, 3 Sets Indicating LED lamps R, Y, B Phase with protective SP MCB's, 3 Sets of CTs of the ratio 1600/5A with class 0.5 Accuracy for Metering, burden 15 VA, 400 A TPN Aluminium Bus Bar with colour coded PVC Sleeves, Outgoing: 06 No. of 100 A, 4P MCCB MP , 25 kA Breaking Capacity, 1 Set of R-Y-B indication Lamps as required. |
| 323 | Supply, Installation, Testing & Commissioning of AHU Starter Panel complete with MCCB incomer, Variable Frequency Drive (VFD), contactor, overload protection, control components, indicating lamps and accessories. Suitable for 415V, 3 Phase, 50Hz operation with Auto/Manual control, soft start, speed regulation and BMS compatibility. Complete with internal wiring, gland plate, cable termination, testing and commissioning as required. |
| 324 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 2.5 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 325 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 326 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 327 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 16 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 328 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 329 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 330 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 400 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 331 | Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories. |
| 332 | Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete, and recording the results Specification no. EA-MOBI |
| 333 | Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EAEP. |
| 334 | Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. |
| 335 | Chiller (Credit) |
| 336 | Primary Pumps (Credit) |
| 337 | Secondary Pumps (Credit) |
| 338 | MS Pipe (Credit) |
| 339 | GI Ducting (Credit) |
| 340 | Chiller panels & AHU Panels (Credit) |
| 341 | Grill & Diffusers (Credit) |
| 342 | SITC of Electric Traction Passenger Lift with Rated capacity :- 20 Passenger/1350 Kg Floors :-B1 to 22 Floor (24 Stops/24 Landings all doors opening on the same side) Travel :- 98 mtrs Location of Lift Machine:- machine room, MR Rated speed :- 2.5 mps VS Car/Landing door clear opening of 1000 mm W x 2100 mm H Clear Car size of Clear Car size of 1800 mm W x 1700 mm D x 2500 mm H; Lift shaft available having clear size of 2500 mm W x 1450 mm D ; Pit Depth ; 3500mm & Overhead 5800 mm , Doors type :- Central Opening Doors (2 Panels) Doors with frame made from SSHL 304 Grade sheet of 1.2mm thick in hairline finish for car and all landing doors with SS door architraves/frames. The lift doors shall have Fire Class Integrity of minimum 120min (EN81-58) .Lift car enclosure made from car finish : Rear Mid Panel = SSHL 304 Grade ,Rear Corner Panels = SSHL 304 Grade ,Side Mid Panels = SSHL 304 Grade , Side Corner Panels = SSHL 304 Grade Front Panels = SSHL 304 Grade SS sheet of 1.2mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with false ceiling with Hairline Stainless Steel (304 Grade) with adequate LED lights, Cross flow fan for ventilation & appopiate flooring, handrails, emergency light etc. Hall Button with HPI ; FPI, 7\\" TFT-LCD UP/DN Car position indicator with / without attendant key switch, with the following standard features Anti-nuisance Car Call Protection, Independent Service (for Duplex only), Overload Device Nudging, Emergency Firemen’s Service, Emergency Car Light Unit Infrared Curtain Door Protection, Door Time Protection, Emergency Alarm Button, Extra Door Time of Lobby & Parking Door Open/Close Button, Manual Rescue Operation, Belt Inspection Drive, Auto Fan Cut Off ,Car Chime, LVA/ACD Lift controller based on microprocessor with VF Regenerative (Closed Loop) Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT. General: - Job includes entire procedure of obtaining all necessary erection permissions & \\"License to Work the Lift\\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. · The above rate includes Fully Comprehensive warranty for 1 year from the date of commissioning |
| 343 | SITC of Electric Traction Passenger Lift with Rated capacity :- 20 Passenger/1350 Kg Floors :-Ground to 22 Floor (23 Stops/23 Landings all doors opening on the same side) Travel :- 90 mtrs Location of Lift Machine:- machine room, MR Rated speed :- 2.5 mps VS Car/Landing door clear opening of 1000 mm W x 2100 mm H Clear Car size of Clear Car size of 1800 mm W x 1700 mm D x 2500 mm H; Lift shaft available having clear size of 2500 mm W x 1450 mm D ; Pit Depth ; 3500mm & Overhead 5800 mm , Doors type :- Central Opening Doors (2 Panels) Doors with frame made from SSHL 304 Grade sheet of 1.2mm thick in hairline finish for car and all landing doors with SS door architraves/frames. The lift doors shall have Fire Class Integrity of minimum 120min (EN81-58) .Lift car enclosure made from car finish : Rear Mid Panel = SSHL 304 Grade ,Rear Corner Panels = SSHL 304 Grade ,Side Mid Panels = SSHL 304 Grade , Side Corner Panels = SSHL 304 Grade Front Panels = SSHL 304 Grade SS sheet of 1.2mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with false ceiling with Hairline Stainless Steel (304 Grade) with adequate LED lights, Cross flow fan for ventilation & appopiate flooring, handrails, emergency light etc. Hall Button with HPI ; FPI, 7\\" TFT-LCD UP/DN Car position indicator with / without attendant key switch, with the following standard features Anti-nuisance Car Call Protection, Independent Service (for Duplex only), Overload Device Nudging, Emergency Firemen’s Service, Emergency Car Light Unit Infrared Curtain Door Protection, Door Time Protection, Emergency Alarm Button, Extra Door Time of Lobby & Parking Door Open/Close Button, Manual Rescue Operation, Belt Inspection Drive, Auto Fan Cut Off ,Car Chime, LVA/ACD Lift controller based on microprocessor with VF Regenerative (Closed Loop) Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT. General: - Job includes entire procedure of obtaining all necessary erection permissions & \\"License to Work the Lift\\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. · The above rate includes Fully Comprehensive warranty for 1 year from the date of commissioning |
| 344 | SITC of Electric Traction Passenger Lift with Rated capacity :- 20 Passenger/1350 Kg Floors :- B2 to 22 Floor (25 Stops/25 Landings all doors opening on the same side) Travel :- 105 mtrs mtrs Location of Lift Machine:- MR Rated speed :- 2.5 mps VS Car/Landing door clear opening of 1000 mm W x 2100 mm H Clear Car size of Clear Car size of 1800 mm W x 1700 mm D x 2500 mm H; Lift shaft available having clear size of 2500 mm W x 1450 mm D ; Pit Depth ; 3500mm & Overhead 5800 mm , Doors type :- Central Opening Doors (2 Panels) Doors with frame made from SSHL 304 Grade sheet of 1.2mm thick in hairline finish for car and all landing doors with SS door architraves/frames. The lift doors shall have Fire Class Integrity of minimum 120min (EN81-58) .Lift car enclosure made from car finish : Rear Mid Panel = SSHL 304 Grade ,Rear Corner Panels = SSHL 304 Grade ,Side Mid Panels = SSHL 304 Grade , Side Corner Panels = SSHL 304 Grade Front Panels = SSHL 304 Grade SS sheet of 1.2mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with false ceiling with Hairline Stainless Steel (304 Grade) with adequate LED lights, Cross flow fan for ventilation & appopiate flooring, handrails, emergency light etc. Hall Button with HPI ; FPI, 7\\" TFT-LCD UP/DN Car position indicator with / without attendant key switch, with the following standard features Anti-nuisance Car Call Protection, Independent Service (for Duplex only), Overload Device Nudging, Emergency Firemen’s Service, Emergency Car Light Unit Infrared Curtain Door Protection, Door Time Protection, Emergency Alarm Button, Extra Door Time of Lobby & Parking Door Open/Close Button, Manual Rescue Operation, Belt Inspection Drive, Auto Fan Cut Off ,Car Chime, LVA/ACD Lift controller based on microprocessor with VF Regenerative (Closed Loop) Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT. General: - Job includes entire procedure of obtaining all necessary erection permissions & \\"License to Work the Lift\\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. · The above rate includes Fully Comprehensive warranty for 1 year from the date of commissioning |
| 345 | SITC of Indoor Escalator with following specifications:STEP WIDTH: 1000 mmHORIZONTAL/FLAT STEPS: 2/2INCLINATION: 35 degVERTICAL RISES: 3600mmOperational Speed: 0.5 m/sTRASPORTATION CAPACITY: 6000 P/HMAIN POWER SUPPLY: 3 × 415 V (-10% to +6%) at 50 Hz (±2 Hz), 240 V lighting supplyBALUSTRADE TYPE: 10mm thick Tamperred Glass (Slim Type)BALUSTRADE HEIGHT: 1000mmHANDRAIL MATERIAL: Synthetic Rubber with Nylon Linning (Black)DECKING [INNER & OUTER]: Stainless steelSKIRTING: Sheet steel with black anti-friction coatingACCESS/LANDING COVER: Ribbed aluminum with natural colorSTEP TYPE: One piece die cast AluminumSTEP COLOR:SilverSTEP DEMARCATION: Yellow painted lines at three sidesCOMB SEGMENT: Aluminum with plastic inlayLOAD DEFLECTION: Max 1:750TRUSS STRUCTURE: Hollow profiles, L-profiles and U-profilesMOTOR: 3-phase, 6-pole induction motor and F insulation with IP55 protectionDrive: VVVFGEAR BOX: Worm gearHANDRAIL DRIVE: Friction drive wheel via pressure rollersBRAKE : Operational brakeDRIVE CHAIN: Duplex drive chainSTEP CHAIN: Precision roller type, with heat-treated linksCONTROLLER TYPE: Microprocessor based PCBCONTROLLER CABINET: Steel Cabinet with IP 54 protection OPERATION MODE: Automatic start / stopOther Features: Comb plate impact devices, Handrail inlet switches, Step sag switches, Broken step chain switches (chain tension control switches, lower), Motor speed monitor (overspeed, under-speed, unintentional reverse, and braking deceleration), Motor thermal protection, Mains supply isolator, Emergency stop buttons beside key switches, Stop switches within upper and lower maintenance pits, Handrail speed and breakage monitor, Access cover safety switches, Mechanical step band lock, Missing step detector, Brake lift monitoring switch, Broken drive chain device, Skirt switches, Anti climb barrier, Step reverse fences, Handrail anti-static roller, Step anti-static brush, Phase failure Indicator, Monitoring contacts, Buzzer alarm, Fire alarm relay, Wrong direction warning.Traffic light, Comb light. |
| 346 | Dismantling the existing 23 Passenger/Stretcher/Goods lift of all types travelling G+22 floors (23 Landings/23Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete. |
| 347 | Dismantling the existing 23 Passenger/Stretcher/Goods lift of all types travelling B+2+G+22 floors (25 Landings/25 Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete. |
| 348 | Credit of Lifts & Escalator (Credit) |
| 349 | Supply, Installation, Testing and Commissioning (SITC) of Horizontal Multistage Main Fire Hydrant & Sprinkler Pump, electric motor driven, capacity 2850 LPM at 160 m total head (including static head, friction losses and 10–15% design safety margin), complete with 120 kW, 415 V, 3 Phase, 50 Hz, TEFC squirrel cage induction motor, common base frame, flexible coupling with coupling guard, suction and delivery pressure gauges, butterfly valves, non-return valve (NRV), pressure relief valve (if required), anti-vibration pads, foundation bolts, interconnecting piping, electrical cabling from local control panel, and all necessary accessories, including testing and commissioning, complete in all respects as per NBC 2016, IS 15105, IS 3844 and relevant IS standards. |
| 350 | Supply, Installation, Testing and Commissioning (SITC) of Horizontal Multistage Jockey Fire Hydrant & Sprinkler Pump, electric motor driven, capacity 180–300 LPM at 160 m total head (including static head, friction losses and 10–15% design safety margin), complete with 15 kW, 415 V, 3 Phase, 50 Hz, TEFC squirrel cage induction motor, horizontal multistage pump, common base frame, flexible coupling with coupling guard, suction and delivery pressure gauges, isolation valves, non-return valve (NRV), pressure switch, pressure transmitter (if required), anti-vibration pads, foundation bolts, interconnecting piping, electrical wiring from the local control panel, and all necessary accessories, including testing and commissioning, complete in all respects as per NBC 2016, IS 15105, IS 3844 and relevant IS standards. |
| 351 | Supply, Installation, Testing and Commissioning (SITC) of Horizontal Multistage Terrace Booster Fire Pump, electric motor driven, capacity 2850 LPM at 45–50 m total head (including friction losses and design safety margin), complete with 55 kW, 415 V, 3 Phase, 50 Hz, TEFC squirrel cage induction motor, horizontal multistage pump, common base frame, flexible coupling with coupling guard, suction and delivery pressure gauges, butterfly valves, non-return valve (NRV), pressure relief valve (if required), anti-vibration pads, foundation bolts, interconnecting piping, electrical wiring from the local control panel, and all necessary accessories, including testing and commissioning, complete in all respects as per NBC 2016, IS 15105, IS 3844 and relevant IS standards. |
| 352 | Supply, Installation, Testing and Commissioning (SITC) of Horizontal Split Case Diesel Engine Driven Main Fire Hydrant Pump, capacity 2850 LPM at 160 m total head (including static head, friction losses and 10–15% design safety margin), complete with suitably rated diesel engine (approximately 250 HP or as per pump manufacturer’s selection), flexible coupling with coupling guard, common base frame, diesel fuel tank, battery with charger, engine control panel, cooling system, exhaust silencer with piping, suction and delivery pressure gauges, butterfly valves, non-return valve (NRV), pressure relief valve (if required), anti-vibration pads, foundation bolts, interconnecting piping, all accessories, testing and commissioning, complete in all respects as per NBC 2016, IS 15105, IS 9137 and relevant IS standards. |
| 353 | Supply, Installation, Testing and Commissioning (SITC) of Fire Pump Control Panel for Horizontal Multistage Main Fire Hydrant Pump, Horizontal Multistage Booster Fire Pump and Horizontal Multistage Jockey Pump, fabricated from CRCA sheet, floor-mounted, dust and vermin-proof, IP-54 protection, powder-coated finish, suitable for 415 V, 3 Phase, 50 Hz AC supply, complete with incomer MCCB, outgoing MCCBs/MPCBs, contactors, thermal overload relays, control transformer, selector switches (Auto/Manual), indicating lamps, digital voltmeter and ammeter with selector switch, phase indication, emergency stop, ON/OFF push buttons, terminal blocks, internal wiring, copper busbars, cable glands, earthing terminals, space heaters (if required), and all accessories for automatic and manual operation of the fire pumps, including pressure switch logic for the jockey pump and sequential starting of the main and booster pumps, complete with testing and commissioning, conforming to NBC 2016, IS 15105, IS/IEC 61439 and relevant fire safety standards. |
| 354 | Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½\\") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FFSPR. |
| 355 | Supplying and erecting G.I. pipe ‘C’ class ERW 25 mm dia with necessary fittings complete as per specification no. FF-PP |
| 356 | Supplying and erecting G.I. pipe ‘C’ class ERW 50 mm dia with necessary fittings complete as per specification no. FF-PP |
| 357 | Supplying and erecting G.I. pipe ‘C’ class ERW 65 mm dia with necessary fittings complete as per specification no. FF-PP |
| 358 | Supplying and erecting G.I. pipe ‘C’ class ERW 75/80 mm dia with necessary fittings complete as per specification no. FF-PP |
| 359 | Supplying and erecting G.I. pipe ‘C’ class ERW 100 mm dia with necessary fittings complete as per specification no. FF-PP |
| 360 | Supplying and erecting G.I. pipe ‘C’ class ERW 150 mm dia with necessary fittings complete as per specification no. FF-PP |
| 361 | Supplying and erecting G.I. pipe ‘C’ class ERW 200 mm dia with necessary fittings complete as per specification no. FF-PP |
| 362 | Supplying and erecting G.I. pipe ‘C’ class ERW 250 mm dia with necessary fittings complete as per specification no. FF-PP |
| 363 | Supplying and erecting G.I. pipe ‘C’ class ERW 300 mm dia with necessary fittings complete as per specification no. FF-PP |
| 364 | Providing coating of bitumen paint & 4mm thick wrapping for underground 150 mm ring main of fire fighting system. |
| 365 | Supplying and erecting 75/80 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS |
| 366 | Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS |
| 367 | Supplying and erecting 150 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS |
| 368 | Supplying and erecting 200 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, screen of SS end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS |
| 369 | Supplying and erecting 75/80 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV |
| 370 | Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV |
| 371 | Supplying and erecting 150 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV |
| 372 | Supplying and erecting 200 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV |
| 373 | Supplying and erecting 250 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV |
| 374 | Supplying and erecting 300 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV |
| 375 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 376 | Supplying and erecting 65 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 377 | Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 378 | Supplying and erecting 100 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 379 | Supplying and erecting 150 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 380 | Supplying and erecting 200 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 381 | Supplying and erecting 75/80 mm dia cast iron double flange ball type NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV |
| 382 | Supplying and erecting 100 mm dia cast iron double flange ball type NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV |
| 383 | Supplying and erecting 150 mm dia cast iron double flange ball type NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV |
| 384 | Supplying and erecting 200 mm dia cast iron double flange ball type NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV |
| 385 | Supplying and erecting 250 mm dia cast iron double flange ball type NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV |
| 386 | Supplying and erecting 300 mm dia cast iron double flange ball type NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV |
| 387 | Supplying and erecting 20 mm dia gun metal gate valve complete with PN16 pressure rating, as per specification no. FF-VL/GV |
| 388 | Supplying and erecting 25 mm dia gun metal gate valve complete with PN16 pressure rating, as per specification no. FF-VL/GV |
| 389 | Supplying and erecting 50 mm dia gun metal gate valve complete with PN16 pressure rating, as per specification no. FF-VL/GV |
| 390 | Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV |
| 391 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV |
| 392 | Supplying and erecting 63mm dia, reinforced rubber lined (R.R.L.) hose pipe, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL |
| 393 | Supplying and erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FFFFA/NZ |
| 394 | Supplying and erecting 150 mm dia fire brigade header suitable for supplying water in fire tank complete as per specification no. FF-FA/FBC |
| 395 | Supplying and erecting fire brigade header ( Siamese connection )of 150 mm dia, for supplying water in fire tank complete as per specification no. FF-FA/FMC |
| 396 | Supplying and erecting 300 mm dia 1.5m in height air vessel / tank fabricated from min 5mm thick M.S. sheet complete as per specification no. FF-FFA/ACT |
| 397 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV |
| 398 | Supplying, Installing, Testing and Commissioning (SITC) of Glycerine (Oil) Filled Pressure Gauge, 100 mm dial size, stainless steel case, bottom entry, suitable pressure range 0–16 kg/cm² (0–16 bar) or as required, with brass/stainless steel wetted parts, accuracy Class 1.6 or better, complete with isolation valve, siphon/snubber (if required), mounting accessories, fittings, testing and commissioning, suitable for fire hydrant, sprinkler and pump systems, conforming to relevant IS/EN standards. |
| 399 | Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS |
| 400 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP |
| 401 | Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\\"x6\\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) |
| 402 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. |
| 403 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete. |
| 404 | Excavating hard murum / stone metal road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site as required complete. |
| 405 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps). |
| 406 | Making cement concrete foundation including excavation (60 x 60 x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay). |
| 407 | Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mm long with UL/FM |
| 408 | Providing installation testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required |
| 409 | Providing Round bottom fire bucket of 9 Litres capacity as per IS 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark on provided stand/ wall hook complete. |
| 410 | Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete. |
| 411 | Supply, installation, testing and commissioning (SITC) of Sprinkler Alarm Valve Set complete with Alarm Valve, Trim, Pressure Gauges, Water Motor Gong, Test & Drain Valve, Butterfly Valve, and all necessary accessories as per IS/NBC standards. |
| 412 | Supplying and erecting of fire Exit & Fire Extinguisher signage Indicating the floor-number in words & system (Fire Extinguisher & Accessories ) (Non CSR Approved by S. E. Office , Mumbai vide T.S letter no- 108 Date- 13/01/2022 ) |
| 413 | Supply,Instlaation,testing zincaluminite fire water storage tank having capacity 10 KL having structre aboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC). |
| 414 | Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fasterness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4\\" x 3\\" x 3\\"mm hinged for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mm for end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenos schott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated. |
| 415 | Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON. |
| 416 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 417 | Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 418 | Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete. |
| 419 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected. |
| 420 | Carrying out core cutting of size 3\\" to 5\\" dia x 15\\" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. |
| 421 | Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. |
| 422 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU (For Booster Pump Cable) |
| 423 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 150 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU (For Main Fire Pump Cable) |
| 424 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL ( For Fire Fighting Panel incoming Cable) |
| 425 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU (For Jockey Pump Cable) |
| 426 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 120 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete. |
| 427 | Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete, and recording the results Specification no. EA-MOBI |
| 428 | Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. |
| 429 | Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU |
| 430 | Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP |
| 431 | Supplying, installing, testing and commissioning of addressable multi detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warrant. |
| 432 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD . |
| 433 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD. |
| 434 | Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \\"Break Glass\\" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP. |
| 435 | Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF-AFAS/CRM |
| 436 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/M |
| 437 | Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM |
| 438 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH. |
| 439 | Supplying, erecting, testing and commissioning 1000 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF-PA/AFR |
| 440 | Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC |
| 441 | Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF-PA/MIC |
| 442 | Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete. |
| 443 | Supplying, erecting, testing and commissioning rust free microphone table stand of chrome plating/powder coating or S.S. material, up to 500 mm height and suitable base for sturdy mechanism ensuring trouble free movement complete. |
| 444 | Supplying, erecting, testing and commissioning of 2 core shielded cable complete as per specification no. FF-PA/MCC |
| 445 | Supplying and erecting 25 mm dia gun metal gate valve complete with PN16 pressure rating, as per specification no. FF-VL/GV |
| 446 | Supplying and erecting 20/25mm dia gun metal air release cock,with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV |
| 447 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 448 | Supplying and erecting 65 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 449 | Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 450 | Supplying and erecting 100 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 451 | Supplying and erecting 150 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 452 | Supplying and erecting 200 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 453 | Supplying and erecting 250 mm dia. cast iron double flange butterfly valve Gear Operated of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 454 | Supplying and erecting 300 mm dia. cast iron double flange butterfly valve Gear Operated of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 455 | Supplying and erecting 400 mm dia. cast iron double flange butterfly valve Gear Operated of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 456 | Supplying and erecting Manual Balancing Valve of size 400 mm dia. Material of valve shall be cast iron double flange Including neceesary Hardware and insulation required for balancing of chiller / condenser line complete with PN16 pressure rating. Etc, Complete. |
| 457 | Supplying and erecting Manual Balancing Valve of size 300 mm dia. Material of valve shall be cast iron double flange Including neceesary Hardware and insulation required for balancing of chiller / condenser line complete with PN16 pressure rating. Etc, Complete. |
| 458 | Supplying and erecting Manual Balancing Valve of size 250 mm dia. Material of valve shall be cast iron double flange Including neceesary Hardware and insulation required for balancing of chiller / condenser line complete with PN16 pressure rating. Etc, Complete. |
| 459 | SITC of Single Arch Rubber Bellow for Chillers Evaporator, Chillers Condenser, Primary Pump, Condenser Pump, Cooling Tower, Secondary Pump -- 250mm with Control Guide Assembly |
| 460 | SITC of 250mm dia. Motorized Butterfly Valves With Controller With FRP Insulation. |
| 461 | SITC of 300mm dia. Motorized Butterfly Valves With Controller With FRP Insulation. Please Enable Macros to View BoQ information |
| 462 | SITC of 300mm dia. Motorized Butterfly Valves With Controller With FRP Insulation. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 12 daysTender Documents