Tender For Provision Of Lift, Hand Rail, Sign Board, Tactile Flooring, R , Toilets And Accessible Reception) In Jcc Khamanon Distt Fatehgarh Sahib (Electrical Services Only)
Tender Value
82.12 Lakhs
Estimated cost
Bid Submission
22 Sep 2026
5 days left
EMD
1.65 Lakhs
Bank guarantee accepted
Document Fee
5000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Fatehgarh Sahib → Punjab
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of Lift, Hand Rail, Sign Board, Tactile Flooring, R , Toilets And Accessible Reception) In Jcc Khamanon Distt Fatehgarh Sahib (Electrical Services Only)
BOQ
| Sl. No. | Item Description |
| 1 | Providing Audio Visual System & Auditory Signals in Judicial Court Complex, Khamanon Distt. Fatehgarh Sahib. |
| 2 | Supply, installation, testing & Commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event , 1000 alarm log history events, Qwerty/ Touch Screen keypad for operation. The panel should be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 250 analog addressable devices (Devices and detectors). The panel shall work in degrade mode in case of CPU failure, Products not having this feature will offer Redundant CPU. Four access levels, flash EPROM, Panel Shall include 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. The panel shall support with Integrated 8 channel Digital Voice Evacuation System Controller capable of broadcasting Evacuation Messages on same peer-to-peer Network and 2 ways Communication Fire Fighters System capable of supervising all the speaker circuits with adequate zone control and accessories. Failure of Fire Panel CPU shall not result in failure of DVC operation. The Fire Fighters Telephone System shall be capable of having minimum 5 Telephones in conference in multiple FFT Risers. The panel shall be expandable upto Min. 10 loop, UL & FM approved. Panel shall have provsion for Modbus/ Bacnet over IP protocol for future integration with BMS. However, for present arrangement FA system will be standalone with 24x7 monitoring. The panel shall be capable for remote accessibility on a mobile app through cloud platform/solution. Designed to meet UL864, 10th.It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 3 | Supply, installation, testing & Commissioning of Loop Cards Class A Wiring with min. supporting cable length Up to 1.2 Km UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 4 | Supply, installation, testing & Commissioning of Digital Voice Command Controlling Board combines the capabilities of a powerful digital audio processor, an eventdriven audio message generator, and a router.The DVC has two wire digital audio ports to connect to wire DAL segments. The DVC may be networked Programmable from NUP port. Up to 32 minutes of standard quality or 4 minutes of high quality digital audio storage of user-selected/created messages and tones. Supports twisted-pair wire media. Supports single- and multi-mode fiber-optic media when used with fiber option modules. 4-channel analog audio supported.The DVC Should be Compatible with Auxiliary input for line level, 1.0 VRMS, or 1.41 Vp-p low level audio. Selectable AGC, user control of audio level, and audio supervision are supported. UL Listed: S635.ULC Listed: S635.FM Approved. The solution should be from single OEM. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 5 | Supply, installation, testing & Commissioning of Paging Microphone compatible with Emergency evacuation Control Panel UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 6 | Supply, installation, testing & Commissioning of Addressable Smoke photo-Thermal Multicriteria Detector and base with sensitivity range as per NFPA 72. The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches. Designed to meet UL & FM Approved . The solution should be from single OEM. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 7 | Supply, instalietion, testing & Commissioning of Addressable High Sensitivity Photo Detector and Base with sensitivity level as per NFPA 72( 0.02% to 2% Obs/feet) Mandatory for critical rooms like Server room, computer room, UPS room, Record room, malkhana, almad room.The detector shall have the optic block to amplify signals from smoke, but diminish stray internal reflections that can cause false alarms. The detector should have on board drift compensation, transient rejection algorithms with Superior EMI protection. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary / Electronic decimal swiches Designed to meet UL & FM Approved The solution should be from single OEM. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 8 | Supply, installation, testing & Commissioning of Addressable Rate of Rise Heat Detector and base rated at 8.3 deg C/min.NFPA 72. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches.UL & FM Approved The solution should be from single OEM. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 9 | Supply, installation, testing & Commissioning of Addressable wireless mesh technology based photo electric smoke detector and base. The detector shall work within the legitimate working freequency band between 865 MHz to 867 MHz. The detector shall be able to communicate with the wireless gateway. The detector shall have the sensitivity range as NFPA 72 (0.5 to 4.0% obs/ft). The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary Electronic decimal switches designed to meet UL and FM approved .The solution should be from single OEM.It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 10 | Supply, installation, testing & Commissioning of Addressable wireless mesh technology based Multi-criteria Photo-Thermal Detector and base with sensitivity range as per NFPA 72 ( 0.5 to 4.0% obs/ft). The detector shall work within the legitimate working freequency band between 865 MHz to 867 MHz. The detector shall be able to communicate with the wireless gateway. The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary Electronic decimal switches designed to meet UL and FM approved . The solution should be from single OEM.It includes the (CAMC of 2 Years after completion of one year defect liability period). |
| 11 | Supply, installation, testing & Commissioning of approved make Addressable loop powered gateway module capable of connecting 31 devices. The gateway module shall form a hybrid mesh wireless network with the detectors/devices as per the OEM limitation. The module shall comply UL listed. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period). |
| 12 | Supply, installation, testing & Commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device complete in all respects as approved and desired by the Engineer in-charge at site.UL & FM Approved It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 13 | Supply, installation, testing & Commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for Audible annunciation and Min.110 cd flashintg at 1 Hz for visual indication. UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 14 | Supply, installation, testing & Commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes/ Telephone Jack. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary / Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 15 | Supply, installation, testing & Commissioning of Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 16 | Supply, installation, testing & Commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device.UL & FM Approved Module shall be supplied with mounting plate from OEM for ease of installation & maintenance.The solution should be from single OEM. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 17 | Supply, installation, testing & Commissioning of Addressable Relay Module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs. The relay module shall provide contact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 18 | Supply, installation, testing & Commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 19 | Supply, installation, testing & Commissioning of Addressable Fire Fighter's Telephone Jack for two way communication between Remote Fire Fighter & Fire Command Center UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 20 | Supply, installation, testing & Commissioning of Digital Audio Amplifier with cabinet & Amp power supply. Amplifier shall be capable of N:N/N:1 configuration and shall be dual channel capable of processing Two of 8 audio channels and a total of Min 95 W ( It may be 1 unit or Combination of Multiple units to achieve the Requirement) at 70.7 VRMS output along with necessary enclosures with local FFT Raiser. The Digital Audio Amplifier shall be fully monitored for fault and alarm reporting. The proposed Digital Audio Amplifiers shall (be Wall/Panel Mounted) Failure of Fire Panel CPU shall not result in failure of Amplifier operation. Amplifiers shall be distributed across the building/floor to manage the sound attenuation problem & for the best sound intelligibility. All amplifiers shall provide back up of minimum 5 hours using secondary power source(battery power/UPS power) complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 21 | Supply, installation, testing & Commissioning of chassis (Small size) for Amplifier and Digital Series Distribution Board. Chassis should be fabricated from 14-gauge steel, e key-locked door is provided with a pin-type hinge, two keys and the necessary hardware to mount the door, Right- or left-hand hinges, selectable in the field. Door opens 180°, door should be heat dissipation refers to the process of transferring heat away from a system, component, or device to maintain its temperature within acceptable limits. Chassis should be of same make OEM as complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 22 | Supply, installation, testing & Commissioning of 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling/Wall Mount Speakers. The speakers shall be of the same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 23 | Supply, installation, testing & Commissioning of back box for 2W multi--Tap (0.25W; 0.5W; 1W; 2W), Ceiling/Wall Mount Speakers. UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 24 | Supply, installation, testing & Commissioning of Exit LED M ST LED LED based exit sign with dimming function, Reading distance, exit sign Two-sided 25m, Voltage 220-240VAC / 50-60Hz, Power consumption 3.3W / 3.5VA, Battery 3.6V/1.2Ah NiMH, Battery protection Over charge protection /deep discharge protection, Charging Time 16 hours, Battery back-up time 1 hour / 3 hours / 8 hours (from dip switch), Light source 15 LED, Approvals EN 60598-1, EN 60598-2-22, EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3, Ambient temperature 5 to 40 °C, Humidity Up to 95%, IK rating IK09, IP rating IP40, Dimensions 265 x 53 x 222 mm, Weight 540 / 742 gr , Colour Anodized aluminum / black plastic, Materials Aluminum, Acrylic Plate, Mounting method Ceiling, wall bracket, suspended, pendulum, flag mount, Delivered as self-contained/auto test luminaire Choice of 1, 3 or 8 hour autonomy via DIP switch IP 40 – dustproof luminaire Reading distance upto 25 meters.High lumen output – 1h = 180lm / 3h = 110lm /8h = 40lm Technical lifetime of LED > 100 000 hours , 4 Pictograms (left, right, down, up) are included in the luminaire ordering part code complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 25 | Supply, installation, testing & Commissioning of Agora LED NM LED IP42 230V 2X6W 1h/3h/8h. The luminiare comes in plastic housing. Mounting bracket is not required for this luminaire, IP42/NA 0 Non -Maintained Self Testing 12V / 7Ah Pb, LED based for anti-panic area, surface assembly Delivered as self-contained/auto test luminaire Choice of 1, 3 or 8 hour autonomy via DIP switch High lumen output – 1h = 360lm / 3h = 170lm / 8h = 70lm Simple and quick assembly and maintenance Technical lifetime of LED > 100 000 hours • IP42 – dust and waterproof luminaire, Voltage 220-240VAC / 50-60Hz Power consumption 11.4W / 11.8VA Battery 12V / 7Ah Pb Battery protection Over charge protection /deep discharge protection Charging Time 23 hours, Battery back-up time 1 hour / 3 hours / 8 hours (from dip switch), Light source LED 2x6, Technical lifetime (light source) >100 000 hours, Lumen output, emergency (1h / 3h / 8h) 3200 / 1600 / 800 lm, Approvals EN 60598-1, EN 60598-2-22, EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3, Ambient temperature 5 to 40 °C, Humidity Up to 95%, IP rating IP42, Dimensions 302 x 94 x 210 mm, Weight 4200 / 4420 gr, Materials PC/ABS, PC, Aluminium, Mounting method Wall mounting complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 26 | Supply, installation, testing & Commissioning of Online UPS 1 kva 800 Watts Tower UPS with 1 hour battery backup. Operating Temperature Range 0 to 40 Degree @ 100% Load @ 50 Degree with 50% Load,Storage Temperature -15°C~60°C, Relative Humidity 0-95% No condensates, Acoustic Noise 40 dBA @ 1 Meter, Cooling Forced air cooling by the internal fans, Input Socket IEC C13, Output Socket IEC C14, No of output sockets 3 No's, Rated Input Voltage 208/220/230/240 Vac, Maximum working input voltage range 160 to 300 Vac @ 100% Load, 100 to 300 Vac @ 50% Load, Input Power Factor 0.99, Input THDi% 5%, Generator Set Yes 1.5 x UPS Capacity, Rated kVA 1000 VA, Rated kW 800 Watts, Load type Resistive load/ lagging load/ non-linear load/ transformer load/ lighting load, Load power factor range 0.5~1 lagging, Load Crest Ratio 3:1, Online Efficiency 88%, Rated Battery Voltage 36 Vdc, Battery Type VRLA (Valve Regulated Lead Acid Battery), 12VDC, Battery backup Back UP : 936VAH, Maximum charging current 10 Amps, ECO Mode Available, Communication (Independent SCI) Available, Intelligent Card slot (Independent SCI) Available, OVCD Available, EPO Function Available, Intelligent Fans Speed control Available, Auto restart function Available, Cold start Available complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 27 | Supply, mstallation, testing & Commissioning of Transformer for Digital Audio Amplifier of same OEM complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect ability period) |
| 28 | Supply, installation, testing & Commissioning of Digital Series Distibution Board and its associated amplifiers provikte bulk amplification capability to the Digital Voice Command it converts digital audio to analog and routes it toaudio amplifiers and optional backups. An optional Firefighters' telephone riser on the boand supports local and network FFTcommunications, Input capacity of four digital audio channels. Four love-level audio outputs for connection to amplifiers inthe same cabinet. Eight high level audio inputs (four primary, four backup), each input capable of handling 125W of audio at 25VRMS or 100W at 70. TVRMS when used with DS AMP. Local FFT nser, capable of acting as a connection on the digital FFT riser DS-BUS interface to communicate with local bulk amplifiers and power supplies Up to 105 seconds of standard quality backup digital message storage (from VenFire Tools message library, orcreated by the installer) for use in the event of communication loss with the DVC isolated alarm bus input, to be used for backup activation of alarm messages when normal communication with the DVC is lost Audio output activation via network control-by-event equations resident within the DVC The solution should be frem single OEM It includes the (CAMC of 2 Years after completion of one year defect ability period) |
| 29 | HEAVY GAUGE WELDED CONDUIT PIPES: |
| 30 | Supply & erection of Heavy guage welded conduit pipe (ISI marked) as per IS:9537:Part-II for wiring purposes including bends, junction boxes, Steel hooks, GI saddle clamps and other petty materials etc., where necessary including painting as per PWD General Specifications:- |
| 31 | HGW Conduit Pipe 25mm dia. (1.6mm thick) Flushed |
| 32 | RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES: |
| 33 | Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½\\" deep for walls and CI 3\\" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 34 | Wiring 6Amp. wall socket point |
| 35 | Wiring 6Amp. Plug control comprising wall socket point |
| 36 | PVC INSULATED FR COPPER CONDUCTOR CABLES: |
| 37 | Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 38 | Overall size 1.5sq.mm (Un-sheathed) |
| 39 | Overall size 2.5sq.mm (Un-sheathed) |
| 40 | Supply and erection of fire survival cable for fire alarm & PA system with annealed stranded copper conductor, fire resistant mica tape wrapped (at 950°C for 180 minutes), XLPE insulated, LSHZ (low smoke & zero halogen) bedding, LSZH (low smoke & zero halogen) red outer sheath, galvanized steel wire armour, 600/1000 volts grade, Fire resistant to IEC 331 & BS7846 F2/BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3) left bare in pipe or casing or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 41 | Fire Survival cable 2Core x 1.5 sq.mm ( for detectors, speakers and other modules) |
| 42 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES: |
| 43 | Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 44 | Heavy Gauge PVC Conduit Pipe 20mm dia. (Flushed) |
| 45 | Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed) |
| 46 | Lifts ( 1 no 13 Passenger and 1 no 8 Passenger) |
| 47 | Supply, Installation, Testing and Commissioning of 1 Nos. Lift of 13 Passengers Machine Room Less.Type and Capacity : Approximately 884 Kg ,13 Passengers Speed: 1.0 Meter per second Type of drive: AC Variable Voltage Variable Frequency with 16-Bit Microprocessor. Motor: Permanent Magnet Gearless Machine to be hoisted on the top of guide rail within the elevator hoist way and Motor compatible for 180 Starts Per hour. Travel: Approximately 4 meter (G+1) Serving: 2 Floors 2 Stops 2 Openings 2 Levels (All on the same side) Hoist way Required: 2440mm (Wide) x 1800mm (Deep) Clear dimensions Headroom Height (HR): 4500 mm beyond finished floor level of last landing Pit Depth: 1600mm below the finish floor level of first landing Car Size Area: Minimum 2.06 square meter and Maximum 2.20 square meter Car Enclosure: Constructed out of Heavy duty stainless steel (textured) Scratch proof Finish (Vandal Proof) with honeycomb finish/hairline finishCar Entrance: Center Opening Automatic Doors of Stainless steel finish panel in Scratch Resistance/ Vandal proof with a clear opening of 900mm (wide) x 2000mm (high) Door operation: Automatic DC Door operation with adjustable door opening and closing timings Control: Simplex full selective collective control with and without attentdant Operation: Automatic Power Supply: 415 Volts, 3- phase, 50Hz Alternating Current Flooring: 20mm SS Floor skid - Resistant as per standard Fan: Blower Fan in Car for ventilation with Auto cut off Lighting: Diffused LED for Car Lighting |
| 48 | Indicators: LED Dot matrix / Digital 7 segment direction and position indicators in the car and at all landings Hand Rail: Stainless Steel round Hand rail on rear side not less than 600mm long at 900mm above floor levelCall Button Height: Call button (Outside the lift) placed at a height between 800mm-1meter from the floor level Control Panel Height: Control panel placed at a height between 800mm-1meter from the floor level Std. Govt. features. |
| 49 | Other Features : 1. Battery operated emergency light with rechargeable battery 2. Battery operated emergency alarm with rechargeable battery 3. Adjustable Guide shoes 4. Micro movement LED based Heavy Duty buttons 5. Door Open and Close buttons 6. Emergency Intercom provided inside the elevator 7. Emergency Intercom usable without the voice communication 8. Load weighing device with overload bypass feature and Overload function with Audio Visual Indication 9. Steel items, door frames sill angle's, fascia plates, spring buffers & other drive parts of superior quality.10. Automatic phase reversal device and Phase Failure protection11. Call registration 12. Audio & Video System installed in the lift indicating arrival at a floor 13. Manual break lever 14. Additional car gate lock 15. Automatic break testing infrared safety curtain |
| 50 | 16. Braille Buttons (Inside and outside) with Braille instructions for the communication system 17. Kick plate/Skirting 18. Lift anoucement system to announce floor level's in english/Local language only and indication of door for entrance / exit is either Open or Close 19. Car Operating Panel 20. Car platform constructed out of cold rolled grain oriented formed sheets of steel 21. Phase two device fire man drive 22. Fire Man switch at main lobby 23. Car false ceiling in stainless steel |
| 51 | 24. Pit ladder 25. Anti Nuisance car call protection 26. Door Nudging 27. Automated Resuce Device to bring the elevator to the nearest landing in case of power failure.28. Emergency Alarm @ Main Floor29. The provision of mirror on the wall of car opposite lift door not extend below 900mm form lift floor to avoid confusing people with impaired sight.30. The emergency communication system should be coupled with an inductive loop system installed all around lift. Telephone units where provided, should have inbuilt inductive coupled to assist persons suing hearing aids.31. Hands Free Press and Speak Intercom.32. Rescue Device to bring the Elevator to a nearest Landing in case of power failure |
| 52 | Supply, Installation, Testing and Commissioning of 1 Nos. Lift of 8 Passengers Machine Room Less.Type and Capacity : Approximately 544 Kg , 8 Passengers Speed: 1.0 Meter per second Type of drive: AC Variable Voltage Variable Frequency with 16-Bit Microprocessor. Motor: Permanent Magnet Gearless Machine to be hoisted on the top of guide rail within the elevator hoist way and Motor compatible for 180 Starts Per hour. Travel: Approximately 4 meter (G+1) Serving: 2 Floors 2 Stops 2 Openings 2 Levels (All on the same side) Hoist way Required: 1800mm (Wide) x 1800mm (Deep) Clear dimensions Headroom Height (HR): 4500 mm beyond finished floor level of last landing Pit Depth: 1600mm below the finish floor level of first landing Car Size Area: Minimum 2.06 square meter and Maximum 2.20 square meter Car Enclosure: Constructed out of Heavy duty stainless steel (textured) Scratch proof Finish (Vandal Proof).with honeycomb finish/hairline finish.Car Entrance: Center Opening Automatic Doors of with ACVF drive Stainless steel finish panel in Scratch Resistance/ Vandal proof with a clear opening of 800mm (wide) x 2000mm (high) Door operation: Automatic DC Door operation with adjustable door opening and closing timings Control: Simplex full selective collective control with and without attentdant Operation: Automatic Power Supply: 415 Volts, 3- phase, 50Hz Alternating Current Flooring: 20mm SS Floor skid - Resistant as per standard Fan: Blower Fan in Car for ventilation with Auto cut off Lighting: Diffused LED for Car Lighting |
| 53 | Indicators: LED Dot matrix / Digital 7 segment direction and position indicators in the car and at all landings Hand Rail: Stainless Steel round Hand rail on rear side not less than 600mm long at 900mm above floor levelCall Button Height: Call button (Outside the lift) placed at a height between 800mm-1meter from the floor level Control Panel Height: Control panel placed at a height between 800mm-1meter from the floor level Std. Govt. features. |
| 54 | Other Features : 1. Battery operated emergency light with rechargeable battery 2. Battery operated emergency alarm with rechargeable battery 3. Adjustable Guide shoes 4. Micro movement LED based Heavy Duty buttons 5. Door Open and Close buttons 6. Emergency Intercom provided inside the elevator 7. Emergency Intercom usable without the voice communication 8. Load weighing device with overload bypass feature and Overload function with Audio Visual Indication 9. Steel items, door frames sill angle's, fascia plates, spring buffers & other drive parts of superior quality.10. Automatic phase reversal device and Phase Failure protection11. Call registration 12. Audio & Video System installed in the lift indicating arrival at a floor 13. Manual break lever 14. Additional car gate lock 15. Automatic break testing infrared safety curtain |
| 55 | 16. Braille Buttons (Inside and outside) with Braille instructions for the communication system 17. Kick plate/Skirting 18. Lift anoucement system to announce floor level's in english/Local language only and indication of door for entrance / exit is either Open or Close 19. Car Operating Panel 20. Car platform constructed out of cold rolled grain oriented formed sheets of steel 21. Phase two device fire man drive 22. Fire Man switch at main lobby 23. Car false ceiling in stainless steel |
| 56 | 24. Pit ladder 25. Anti Nuisance car call protection 26. Door Nudging 27. Automated Resuce Device to bring the elevator to the nearest landing in case of power failure.28. Emergency Alarm @ Main Floor29. The provision of mirror on the wall of car opposite lift door not extend below 900mm form lift floor to avoid confusing people with impaired sight.30. The emergency communication system should be coupled with an inductive loop system installed all around lift. Telephone units where provided, should have inbuilt inductive coupled to assist persons suing hearing aids.31. Hands Free Press and Speak Intercom.32. Rescue Device to bring the Elevator to a nearest Landing in case of power failure |
| 57 | SURFACE PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES: |
| 58 | Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia (ISI Marked) installed on surface etc., complete with PVC boxes (Plastic on surface boxes) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), MS saddle clamp, PVC Circular junction Boxes (Four way 1½\\" deep for walls), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material and painting as required:- |
| 59 | Wiring light point |
| 60 | Wiring 6Amp. wall socket point |
| 61 | XLPE INSULATED UN-ARMOURED CABLES (LOOSE):-Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications |
| 62 | Overall size 25sq.mm (4Core) Un-armoured (Loose) |
| 63 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES: |
| 64 | Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 65 | Double Walled Corrugated HDPE Pipe 63/ 51mm (Outer/ Inner dia.) |
| 66 | XLPE INSULATED UN-ARMOURED CABLES (ON SURFACE):Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications |
| 67 | Overall size 25sq.mm (4Core) Un-armoured (On-Surface) |
| 68 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES: |
| 69 | Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 70 | Heavy Gauge PVC Conduit Pipe 20mm dia. (Flushed) |
| 71 | MINIATURE CIRCUIT BREAKERS: |
| 72 | Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 73 | MCB Single Pole 6-32amp. (10kA, Curve-C) |
| 74 | MCB Four Pole 50, 63amp. (10kA, Curve-C) |
| 75 | MCCB's (MOULDED CASE CIRCUIT BREAKER): |
| 76 | Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:- |
| 77 | MCCB Four Pole 63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 78 | COPPER EARTHING :-(8 SWG COPPER EARTHING :):-Earthing with 8 SWG (4mm dia.) electrolytic copper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation |
| 79 | Earthing with 8 SWG (4mm dia.) copper wire thimbled with 30cm x 60cm x 2mm thick copper plate burried 10.50 metre (34.44 feet) below ground level (up to 14metre in Length) with G.I. pipe 20mm dia. (A-class), 9metre long |
| 80 | Additional Length copper wire 8 S.W.G. (4mm dia.) in 20mm dia. G.I. pipe (On Surface) |
| 81 | SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB's/ RCBO's/ RCCB's: |
| 82 | Supply and erection of sheet metal Double Door Distribution Boards IP 43-IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:- |
| 83 | TP&N Horizontal Double Door Distribution Board 4 way each |
| 84 | Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 11, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 22, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysSep 22, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓