Defence Statutory Bodies & Commissions/Committees Closing in 12 days TDR #57451901

Tender For Shifting And Replacement Of Existing Lt Panel And Lt Cables With Connected Accessories In Upper Block Of 92 Base Hospital At Bb Cantt, Srinagar.

Issued by Statutory Bodies & Commissions/Committees · srinagar, Jammu and Kashmir
Tender Value
43.67 Lakhs
Estimated cost
Bid Submission
01 Oct 2026
12 days left
EMD
87400
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
srinagar → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender For Shifting And Replacement Of Existing Lt Panel And Lt Cables With Connected Accessories In Upper Block Of 92 Base Hospital At Bb Cantt, Srinagar.

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 16-Sep-2026 Corrigendum for Revised BOQ BOQ 01-Oct-2026

BOQ

Name of Work:- SHIFTING AND REPLACEMENT OF EXISTING LT PANEL AND LT CABLES WITH CONNECTED ACCESSORIES IN UPPER BLOCK OF 92 BASE HOSPITAL AT BB CANTT, SRINAGAR.
Sl. No. Item Description
1Excavation in trenches, not exc 1.5 m wide and not exc 1.5 m in depth; for laying of cables, pipes etc. and getting out all excavated material in any type of soil, complete all as specified and directed.
2Returning, filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick, complete all as specified and as directed.
3Removing of excavated surplus soil to a distance not exc 50 m and depositing where directed at a level not exc. 1.5 m above the starting point, complete all as specified and directed.
4M&L for locally available river sand in trenches 15 cm below cable and 8cm above / around UG cable for cable protection, in duct under and above the cables including punning around cable, complete all as specified and directed.Note: - Punned thickness shall only be measured and paid.
5Supply and laying GI pipe 'light grade' 40 mm bore in trenches, under floors, roads, along poles for protection of cables with all necessary fittings and sealing ends, complete all as specified and directed.
6Supply and laying GI pipe 'light grade' 50 mm bore in trenches, under floors, roads, along poles for protection of cables with all necessary fittings and sealing ends, complete all as specified and directed.
7Supply and laying GI pipe 'light grade' 80 mm bore in trenches, under floors, roads, along poles for protection of cables with all necessary fittings and sealing ends, complete all as specified and directed.
8Supply and laying GI pipe 'light grade' 100 mm bore in trenches, under floors, roads, along poles for protection of cables with all necessary fittings and sealing ends, complete all as specified and directed.
9Supply and laying unreinforced PCC Cable protection cover, class LV, type-1 flat with size 250 x 150 x 40 mm laid flat width wise, complete all as specified and directed.
10Supply, laying and testing cable XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross- sectional area 400 sq mm, 3.5 core, complete all as specified and directed.
11Supply, laying and testing cable XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross- sectional area 150 sq mm , 3.5 core, complete all as specified and directed.
12Supply, laying and testing cable XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross- sectional area 95 sq mm, 3.5 core, complete all as specified and directed.
13Supply, laying and testing cable XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross- sectional area 70 sq mm, 3.5 core, complete all as specified and directed.
14Supply, laying and testing cable XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross- sectional area 50 sq mm, 3.5 core, complete all as specified and directed.
15Supply, laying and testing cable XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross- sectional area 25 sq mm, 4 core, complete all as specified and directed.
16Supply, laying and testing cable XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross- sectional area 10 sq mm, 2 core, complete all as specified and directed.
17M & L for Copper busbar, weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick with ingress protection of IP-54 grade having copper bus bar of rating 500 Amp capacity, 415 volt colour code with neutral including 315 Amp MCCB three phase and netural with encloser including indication lamp, Angle iron leg and PCC foundation complete all as specified and directed.
18Material and labour for road cutting of minimum sizes 30cm x 30cm for laying cables etc and making good the disturbed surface to match existing surface using plain cement concrete 1:2:4 type B-2 (using 40mm graded crushed stone aggregate), complete all as specified and as derected.
19Earthing complete with galvanised iron earth plate electrode 600x600x6mm buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of earth plate not less than 1.5mtr below normal ground level, connected with 32x6mm size GI strip as earth lead, by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15, type B-1 in pit with precast RCC M-15(1:2:4), type B-1 (using 20mm graded crushed stone aggregates) in cover reinforced with XPM not less than 4.0 Kg per Sqm, test point etc. all as shown in electric plate No-3 of SSR Part-I (2009), complete with necessary earth work in any type of soil, removal to a distance not exceeding 50mtr, including testing on completion, complete all as specified and directed.
20Supply, installation, testing and commissioning in replacement of LT Panel board suitable for 415 Volts, 3 Phase 4 wire, 50 Hz AC supply system outdoor type floor mounted along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick with ingress protection of IP-54 grade having copper bus bar of rating 600 Amps, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. The panel shall be front openable and having inner & outer shells. The inner shell dully compartmented for each control gear, including powder coating internally and externally the entire steel surfaces. All the cover shall be provided with suitable locking arrangements. The size of the outer shell should not be less than 1200mm x 1200mm x 450mm, mounted on angle iron stand made out of angle size 50 x 50 x 6mm grouted in PCC foundation in cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate), including suitable sizes of cable glands for incomming and outgoing cables with accomodating the following control gears and accessories:-
21(a) MCCB 400 Amps 4 pole ,36 KA 415 Volts (Incomer ) -01 Nos(b) MCCB 315 Amps 4 pole ,36 KA 415 Volts (outgoing ) -02 Nos(c) MCCB 250 Amps 4 pole ,36 KA 415 Volts (outgoing ) -02 Nos(d) copper Bus bar of capacity 630 Amps 3phase and neutral -1 set.(e) ON Load Change over switch 400 Amps 4 pole- 01 No(f) Digital type voltmeer 0-500 volts.(g) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 No(h) Indicating LED lamps R,Y& B -01 set
22Supply, installation, testing and commissioning in replacement of LT Panel board suitable for 415 Volts, 3 Phase 4 wire, 50 Hz AC supply system outdoor type floor mounted along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick with ingress protection of IP-54 grade having copper bus bar of rating 600 Amps, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. The panel shall be front openable and having inner & outer shells. The inner shell dully compartmented for each control gear, including powder coating internally and externally the entire steel surfaces. All the cover shall be provided with suitable locking arrangements. The size of the outer shell should not be less than 1200mm x 1200mm x 450mm, mounted on angle iron stand made out of angle size 50 x 50 x 6mm grouted in PCC foundation in cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate), including suitable sizes of cable glands for incomming and outgoing cables with accomodating the following control gears and accessories:-
23(a) MCCB 315 Amps 4 pole ,36 KA 415 Volts (Incomer ) -01 No(b) MCCB 250 Amps 4 pole ,36 KA 415 Volts (outgoing ) -02 Nos(c) MCCB 200 Amps 4 pole ,25 KA 415 Volts (outgoing ) -06 Nos(d) copper Bus bar of capacity 500 Amps 3 phase and neutral -1 set.(e) ON Load Change over switch 315 Amps 4 pole- 01 No(f) Digital type voltmeer 0-500 volts.(g) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 No(h) Indicating LED lamps R,Y& B -01 set
24Supply, installation, testing and commissioning in replacement of LT Panel board suitable for 415 Volts, 3 Phase 4 wire, 50 Hz AC supply system outdoor type floor mounted along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick with ingress protection of IP-54 grade having copper bus bar of rating 400 Amps, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. The panel shall be front openable and having inner & outer shells. The inner shell dully compartmented for each control gear, including powder coating internally and externally the entire steel surfaces. All the cover shall be provided with suitable locking arrangements. The size of the outer shell should not be less than 1200mm x 1200mm x 450mm, mounted on angle iron stand made out of angle size 50 x 50 x 6mm grouted in PCC foundation in cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate), including including suitable sizes of cable glands for incomming and outgoing cables with accomodating the following control gears and accessories:-
25(a) MCCB 400 Amps 4 pole ,36 KA 415 Volts (Incomer ) -01 No(b) MCCB 315 Amps 4 pole ,36 KA 415 Volts (outgoing ) -01 No(c) MCCB 250 Amps 4 pole ,36 KA 415 Volts (Outgoing) -02 Nos(d) copper Bus bar of capacity 630 Amps 3phase and neutral -1 set.(e) ON Load Change over switch 400 Amps 4 pole- 01 No(f) Digital type voltmeer 0-500 volts.(g) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 No(h) Indicating LED lamps R,Y& B -01 set
26Supply, installation, testing and commissioning in replacement of LT Panel board suitable for 415 Volts, 3 Phase 4 wire, 50 Hz AC supply system outdoor type floor mounted along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick with ingress protection of IP-54 grade having copper bus bar of rating 400 Amps, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. The panel shall be front openable and having inner & outer shells. The inner shell dully compartmented for each control gear, including powder coating internally and externally the entire steel surfaces. All the cover shall be provided with suitable locking arrangements. The size of the outer shell should not be less than 1200mm x 1200mm x 450mm, mounted on angle iron stand made out of angle size 50 x 50 x 6mm grouted in PCC foundation in cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate), including including suitable sizes of cable glands for incomming and outgoing cables with accomodating the following control gears and accessories:-
27(a) MCCB 250 Amps 4 pole ,36 KA 415 Volts (Incoming ) -01No(b) MCCB 200 Amps 4 pole ,25 KA 415 Volts (outgoing ) -02 Nos(c) MCCB 160 Amps 4 pole ,16 KA 415 Volts (Outgoing) -02 Nos(d) copper Bus bar of capacity 450 Amps 3 phase and neutral -1 set.(e) Digital type voltmeer 0-500 volts.(f) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 No(g) Indicating LED lamps R,Y& B -01 set
28Supply, installation, testing and commissioning of sheet metal encloser suitable for 415 Volts, 3 Phase 4 wire, 50 Hz AC supply system outdoor type floor mounted along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick with ingress protection of IP-54 , having copper bus bar of rating 1000 Amps, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleevesmounted on angle iron stand made out of angle size 50 x 50 x 6mm grouted in PCC foundation in cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate), including including suitable sizes of cable glands for incomming and outgoing cables with accomodating the following control gears and accessories:-
29(a) ON Load Change over switch 630 Amps 4 pole- 01 No (incomming)-01 No(b) MCCB 630 Amps 4 pole ,50 KA 415 Volts (incomming ) -01No(c) MCCB 400 Amps 4 pole ,36 KA 415 Volts (Outgoing) -01 No(d) copper Bus bar of capacity 1000 Amps 3phase and neutral -1 set.(e) Digital type voltmeer 0-500 volts.(f) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 No(g) Indicating LED lamps R,Y& B -01 set
30Supply and fixing of sheet metal enclosure box duly powder coated & framing work with locking system and having double door fixing arrengment system suitable of size/type for vertical type distribution board vertical loadline type of rating VTPN 4 way type 415 volt 3 phase AC supply holding system with IP protection rating with ISI marked and having fitted neutral and earth link bus bar and mounting base chanels and blanking plates suitable for holding of main MCCB as incommer and out going MCB complete system alongwith providing and mounting in side of DB box of 01 No of MCCB TP160 Amps with breaking rupting capacity 25 KA and having adjustable setting type and also providing of 12 Nos of MCB SP 63 Amps 10KA 'C' curve type of the same manufacture make as per of distribution board make complete set and including dully fixed surface on wall or concealed in wall and making all necessary electrical and also refixing the electric meter and its wiring connection including taking down of existing DBs, complete all as specified and directed.
31Supply and fixing, cable route marker for LT cable duly engraved (LT 1.1 KV cable) on 150 mm dia MS round plate 10mm thik duly painted with yellow colour paint and fix on MS angle of 40mmx40mmx5mm with nuts and bolts and embedded in PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregate concrete block of size 230mmx230mmx150mm, including necessary excavation and eath work, complete as specified and directed.
32Supply and laying HDPE DWC Pipe outer dia 90/76 mm. for protection and covering the XLPE cable upto 150 sqmm 3.5 core complete all as specified and directed.
33Dismantling and taking down the existing LT cables of any sizes complete all as specified and directed.
34Dismainting of old LT panel /Busbar box of any sizes, complete all as specfied and directed.
35Supply and fix danger notice plate of 1.6 mm thick mild steel sheet, for 415 Volt vitreous enamelled white , with letters figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for 20 x 15 cm size, complete all as specified and directed.
36S & F informatory board for indicating the power installation of size 1.20 x 0.90 m made of aluminium sheet 2mm thick with frame of stainless steel rectangular pipe 25 x 15 mm and outer boarder of stainless steel pipe 35mm dia and each side with marking of colour and pasted with heating process. The letters shall be 75 mm to 100 mm high of white colour cut to shape with special plotter and in proper manner. The board shall be fixed with 02 Nos stainless steel pipes of dia 75 mm of 304 grade glossy finish, with MS plate 3 mm thick welded at bottom of pipes and board shall be fixed at height of 3.00 m (Tope level of board) above GL and embedded and grouted in ground in cement concrete 1:2:4 type B-1 including necessary excavation and earth work complete all as specified and directed. Note: Letter of writing word shall be given by Engr-in charge.
37Surface excavation n.exc 30 cm deep and averaging 15 cm deep and getting out soft/hard soil, complete all as specified and directed.
38M & L fo plain cement concrete 1:3:6 type C-1 (using 40 mm graded crushed stone aggregate) 75mm thick as in sub base of path, complete all as specified and directed.
39Providing and laying 80mm thick factory made chamfered edge cement concrete paver block of M-30 grade with approved colour, design & pattern as in footpath, parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of coarse sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with fine sand and cutting of paver block as per required size and pattern, finishing and sweeping extra sand;, complete all as specified and directed.
40M & L for plain cement concrete Type B-1 1:2:4 (using 20mm graded crushed stone aggregate) as in coping, benching etc. of path including necessary form work, complete all as specified and directed.
41Excavating in post holes each n.exc 0.5 cum getting out and removing surplus soil to a distance n.exc 50 m and making good surface, complete all as specified and directed.
42M & L for plain cement concrete 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) as in post/strut foundation, complete all as specified and directed.
43M&L for MS work conforming to Fe-410-0 of Fe-310-0 Grade for fencing posts and struts in fencing including cutting bending top to shape as directed drilling holes matching for barbed wire, including fillet on back side of fencing post and all necessary drilling work, complete and all as specified and directed.
44Supply only chain link MS galvanisd fencing, any size or type, complete all as specified and directed. Note :Actual weight of the fencing shall be ascertained by board of officers to be convened by GE.
45Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provission of binding wire and dismantling of old unserviceable fencing/members, compete all as specified and directed.
46S & F flat iron of size 40mmx5mm thick as in fixing clamps or support to chain link fencing, stifners etc fixed with nut and bolts including making necessry holes, complete all as specified and directed.
47S & F Mild steel round bars 8mm dia horizontally woven in chain link fencing, complete all as specified and directed.
48Mild steel screw bolts (machine made) 5 ot 10mm dia of shank with hexagonal or square heads at one end and screwed the othere, each screw end to be fitted with washers and one hexagonal or square nut exc 5cm but n exc 10cm long, complete and all as specified and directed.
49S&F for Framed brackets of angles or tees with web and flanges, tubular pipes cut to shape,drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc., conforming to Fe.290.Gde-E-165 incl Dismantling wrought iron or mild steel work of any description complete all as specified and directed.
50M&L for preparation of new steel surfaces of any description over 10 cm width or girth and applying two coats of synthetic enameled paint over a coat of red oxide primer, complete all as specified and directed.
51Notes :-An amount of Rs 37,700.00 on account of Credit Schedule for Schedule 'A' Part-II shall be deducted from total quoted amount of BOQ to arrive at the contract sum. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57451901
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 43.67 Lakhs
LAST DATE 01-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender For Shifting And Replacement Of Existing Lt Panel And Lt Cables With Connected Accessories In Upper Block Of 92 Base Hospital At Bb Cantt, Srinagar.
Basic Detail
Tender No 864/WS-88(T)/2026-27
Bidding Type Tender
Location
City srinagar
State Jammu and Kashmir
Key Dates
Publish Date 16 Sep 2026
Submission Date 01 Oct 2026
Open Date 01 Jan 0001
Finance
Tender Value 43.67 Lakhs
Tender Fee 500
EMD 87400
Exemption Available
Document List
BOQ_884208.xls
da987af3-3406-4547-804f-129d7b5cc639.html
Tender88_merged.pdf
Tendernotice_1 (10).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 16, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 01, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 12 days
Oct 01, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 12 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_884208.xls

html

da987af3-3406-4547-804f-129d7b5cc639.html

pdf

Tender88_merged.pdf

pdf

Tendernotice_1 (10).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders