Tender For Repair/Replacement Of Flood Light And Ceiling Lights In Observation-Cum-Special Home & Place Of Safety, Sector 25 Chandigarh.
Tender Value
63513
Estimated cost
Bid Submission
18 Sep 2026
5 days left
EMD
1300
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Chandigarh → Chandigarh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Replacement Of Flood Light And Ceiling Lights In Observation-Cum-Special Home & Place Of Safety, Sector 25 Chandigarh.
BOQ
| Sl. No. | Item Description |
| 1 | 1.14 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 2 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 3 | DSR Item No.1.24 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 4 | 5/6 A switch |
| 5 | 3 pin 5/6 A socket outlet |
| 6 | 15/16 A switch |
| 7 | 6 pin 15/16 A socket outlet |
| 8 | DSR Item No.1.28 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. |
| 9 | 6 Module |
| 10 | 12 Module |
| 11 | DSR Item no. 8.6 LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver& electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till lifeends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 12 | 36 watt |
| 13 | DSR 8.10 LED Batten light (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV withShort & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 14 | 18-22 watt |
| 15 | DSR 8.16 LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt) Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement deg, suitable tilt able fitting, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 16 | 150 watt |
| 17 | DSR item no.2.2Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 18 | 100 A,30KA,FPMCCB |
| 19 | Supply and erection of sheet metal bus-bar chamber on existing surface with required No. of bus-bar strips of suitable length and cross-sectional area, made of copper strips of suitable length and cross-sectional area enclosure made of M.S. sheet 1.6mm thick with detachable cover fitted with dust excluding gasket and secured with sufficient No. of cadmium plated iron screws and of given overall dimensions and to be fixed with G.I. bolts and nuts/Rag bolts and nuts etc., complete with all accessories including connections with suitable size tin coated copper thimbles, bonding to the existing earth and painting etc. as desired by the Engineer-in-charge. |
| 20 | Sheet metal bus-bar chamber suitable for 125 Amp. 415 Volts capacity with 4 copper strip Bus-bars each of length 600 mm and enclosure having overall dimensions 680 mm X 400 mm X 150 mm nominal. |
| 21 | Disconnecting and reconnecting charges for existing main cable, Sub main cables outer remove the joints in the main nitch of ground floor. The cables are to be disconnected by making own suitable arrangement and connect in original finish as required to complete the job to the entire satisfaction of EIC. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 10, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 18, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysSep 18, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender