Tender For Renovation Of Land & Building Department, B & C-Block, Vikas Bhawan, Ip Estate, New Delhi (Sh:- Electrical Work).
Tender Value
1.60 Crore
Estimated cost
Bid Submission
16 Sep 2026
1 days left
EMD
3.21 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Renovation Of Land & Building Department, B & C-Block, Vikas Bhawan, Ip Estate, New Delhi (Sh:- Electrical Work).
BOQ
| Sl. No. | Item Description |
| 1 | SH:I (Electrical Installations Work)Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.(a) Group C |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 3 | (b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 4 | (c) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | (d) 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 6 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.(a) 25 mm |
| 7 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.(a) 1 run of cable |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 10 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.(a) 1 or 2 Module (75 mmX75 mm) |
| 11 | (b) 6 Module (200mmX75mm) |
| 12 | (c) 12 Module (200 mmX150 mm) |
| 13 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(a) 15/16 A switch |
| 14 | (b) 6 pin 15/16 A socket outlet |
| 15 | (c) Telephone socket outlet |
| 16 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)(a) 8 way (4 + 24), Double door |
| 17 | (b) 4 way (4 + 12), Double door |
| 18 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) Single pole |
| 19 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board / MCB DB including drilling holes, making connections, etc. as required.(a) 100 A, 16 KA, TPMCCB |
| 20 | (b) 125 A, 16 KA, TPMCCB |
| 21 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required |
| 22 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 23 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 24 | LED Panel light 2x2 ft. (System lumen efficacy =105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5°C to 40°C, internal surge protection of 2. 5 KV with Short & Open circuit protection, THD < 10%, P. F. =0. 95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1. 5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy =105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0. 50 mm) (a) 36 Watt |
| 25 | LED Down lighter (SMD Type) (System lumen efficacy >135lm/Watt) Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round /square/Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range - 5 degree C to 40 degree C internal surge protection of 2. 5 KV with Short & Open circuit protection, THD < 10%, P. F. =0. 95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5%), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/ 4000°K /5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1. 5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim. (a) 12 -15 watt |
| 26 | Brush Less Direct Current (BLDC) MotorSupplying, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as required.(a) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 27 | Supplying, Installation, Testing and Commissioning of 400 mm Sweep wall Fan suitable for 230 V 50 Hz Ac Supply complete with all accessories on existing wall etc. complete as required. |
| 28 | Supplying, Installation, Testing and Commissioning of 300 mm Sweep 900 RPM Heavy Duty ISI Marked Exhaust fan with louvers & shutters in the existing opening, including making good the same, connection, testing, commissioning etc. as reqd. |
| 29 | Supplying, laying and fixing of following size PVC insulated and PVC sheathed/ XLPE aluminum conductor armoured power cable of 1.1 KV grade on surface etc. as required.(a) 4 x 25 sq.mm |
| 30 | (b) 3.5 x 70 sq.mm |
| 31 | Supplying, installation, testing and commissioning of 250 mm sweep fresh air fan working on 230 +/- 10 V single phase 50 Hz Frequency complete with shutter in existing hole of suitable size making good the same i/c connections, interconnections etc. complete as required. |
| 32 | SH-II (Air-Conditioners)Supply, Installation, Testing and Commissioning of Air Cooled HI Wall split type Air conditioners complete with Indoor unit (IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cut off and50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll /rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS694 or IS 9968 temperature sensing control IS/ International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS :1391 Part II 2023. The system shall be able to operate up to 50 Degree C (out door ambient temperature).Inverter Type - Cooling only(a) 2.0 TR with 5 Star BEE Rating |
| 33 | (b) 1.5 TR with 5 Star BEE Rating |
| 34 | Supply, Installation, Testing and Commissioning of Window type Air conditioners complete with copper power cable upto 3 Mtr, wireless Remote, suitable for working between 180- 260V with low & high voltage cut off and 50 hz, 1 phase AC supply capable of performing, cooling, dehumidification, air circulation, R-32/R-410A /R-407B Green Refrigerant with Scroll/ rotary compressor with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB), antifreeze thermostat on the coil as a safety feature, complete with fixing including T&P & labour etc. as required complete in all respect as specified of following capacity. Sound level of up to50dB inside the room is acceptable. The unit shall be in confirmation with IS 1391 Part-I 2023 and CPWD Specification. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. The system shall be able to operate upto 50 Degree C (out door ambient temperature).Inverter Type1.5 TR with fixed speed 5 Star BEE rating |
| 35 | Supplying and fixing of M.S. outdoor, floor/ wall mounting powder coated stand suitable for 1.5/2.0 Ton capacity split type A.C. outdoor unit complete as required. |
| 36 | Supplying, installation, testing and commissioning of 5 KVA (170v-270v), copper wounded, wall mounted voltage stabilizer with LED display, surge indicator, automatic reset complete etc. as required. |
| 37 | Providing &Laying of refrigerant copper piping of size 1/4\\" or 3/8\\" & 5/8\\" diameter from indoor unit to outdoor unit of split type Air Conditioner unit along with 4 core 2.5 sq.mm PVC insulated and PVC sheathed flexible copper conductor cable including 20 mm size of cotton thread ribbed PVC flexible pipe from drip tray of Air Conditioner unit to drain pipe along with necessary support complete etc all as per Direction of Engineer-in-charge. |
| 38 | Supplying & Drawing of 3x4 sqmm size of PVC insulated &pvc sheathed copper conductor round multicore flexible cable for indoor to outdoor and upto nearest power point i/c providing suitable copper lugs connection etc as required. |
| 39 | Providing & fixing of 25 mm dia (Schedule-40) UPVC/heavy duty PVC white colour drain pipe of with necessary fitting such as nipple, reducer, clamp on surface / recess i/c cutting the wall and making good the same complete as required. |
| 40 | SH-III (UPS)Online UPS- Input supply: Three Phase, Output supply: Three Phase Supplying, installation, Testing & Commissioning of of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 deg C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swappable(allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS)system with N+1 modules (N denotes total number of modules required for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction.The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier &inverter(3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC (inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1), however UPS shall be suitable to take load at 0.7 lagging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC :3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage:3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120%for 10 mins, Sine wave output. |
| 41 | Non condensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery overcharging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved asper EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accessories are inclusive of the cost).This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more LC Display / LED ) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current. d)Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage.f)Temperature: STS, Inverter, PFC. g) Event Logging &Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i)Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load / UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms: Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Over Load and short-circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual, Geo-Tag of manufacturing location etc.(a) 60 KVA (Each Power module shall be ≤ 25 KVA) |
| 42 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. (a) 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 43 | Supplying and fixing Four Pole sheet steel enclosure on surface/ recess along with 100 Amp. 16-18kA Breaking capacity 415 V TP MCCB complete with connections, extended spreader link for connections, testing and commissioning etc. as required. |
| 44 | SH-IV (CCTV /LAN System)Supplying Installation Testing and Commissioning of 8 MP IP IR Dome Camera having following specifications and features etc :-1) Type of Camera: Dome Camera2) Image Sensor: 1/2.8\\" or better progressive Scan CMOS get color image even at night condition3) Signal System: PAL/NTSC4) Minimum Illumination: 0.006 Lux@ F1.4, AGC ON, 0 lux with IR or better 5) Imaging: 1/3s to 1/30000s, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking.6) On Screen Display: Camera should display Camera title, Date & Time in live & recorded video both.7) Signal to Noise Ratio: > 50 dB8) Day & Night: True Day & Night High Performance Mechanical IR cut filter with auto switch, IR Source- Inbuilt IR LED's with effective distance upto 50 Mtrs integrated IR and 30 meter for colour view in night.9) Video Compression (Minimum): H.265 or better, H.265, H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.72310) Wide Dynamic Range: WDR (120db or more)11) Digital Noise Reduction: DNR (2D/3D) On/Off12) Streaming: Triple streaming, configurable13) Video Streaming & Frame Rates: Triple streaming, configurable Main stream: 8MP (3840 × 2160)@20 fps, Sub streams: 4MP (2688×1520)@25/30 fps & D1@25/30 fps;14) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser15) Profile Management: User configuration import, export16) Security: User Authentication, Water Marking |
| 45 | 17) On board Storage: Camera should support built-in Micro SD/SDHC/SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card.18) Recording Management: Format SD, overwrite, storage management, video to NAS device,19) Edge Analytics: Tripwire, Intrusion, Motion Detection20) Alarm Trigger: Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection21) Alarm Support: It should have 1/1 Alarm In/ Out Port22) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out Port for external Mic. and Speaker (As per site requirement) with G.711U/A/ G.711Mu/ AAC/ G.726 audio compression23) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast, 24) System Capability: ONVIF25) VMS: Camera shall support open source VMS 26) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, account lockout, video encryption, IP/MAC filtering, HTTPS, trusted upgrade.27) Ethernet: 1 RJ 45 10/100 Ethernet port28) Power Input: The camera should support simultaneous dual power input - 12 VDC (via power adapter) and PoE-to ensure continuous operation in the event of a failure in one power source.29) Power Requirement: 12VDC/24 VAC/PoE (802.3af)/ePoE30) Enclosure: IP67 weather proof, IK1031) Operating Condition: Ambient Temperature:- (-)05°C to 50°C, humidity 95% (max) (non-condensing)32) IR life: 40000 hours or higher33) Video Bit rate: 32 KBPS - 8 MBPS or better34) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS(a) 8 MP (3840 × 2160)@20 fps or better IP IR 2.7mm ~13.5mm Motorized lens, Vari Focal Dome Camera, Angle of View: H: 104°–32°, V: 54°–18°, D: 125°–36° or better |
| 46 | Supplying, installation, Testing and commissioning of following capacity 8 port Layer 2 indoor Network Switch having features and specifications etc. as mentioned here under: Minimum 8 X RJ-45 Gigabit Ethernet Ports and additional 2 X 1G SFP Ports with non-blocking architecture by having Switching capacity of minimum 20Gbps and packet forwarding rate of 14Mpps or higher, 8K MAC table. Internal dual AC Power supply with operating temperature of -5 0C to +50 0C. Jumbo frame: 10KB or higher, IGMP Snooping, IGMP snooping querier and support for IGMP Snooping Fast Leave, Should create 250 or more MLD groups, MLD Snooping, Per VLAN MLD Snooping C MLD Snooping Fast Leave, STP, RSTP, MSTP, Loopback detection, Multicast filtering, VLAN Tagging, ǪOS: 8 Ǫue per port, WRR, IPv4/IPv6 Interface : minimum 100 IPv4 static route entries and minimum 50 IPv6 static route entries, 700 Acess Control entries, SSH CSSL for IPv4 and IPv6, 802.1x, ARP Spoofing, DHCP Snooping and server screening, IP+MAC+Port Binding, Per Port Bandwidth Control, 802.1X Authentication (Supports local/RADIUS database, Port-based Access Control and EAP, OTP, TLS, TTLS, PEAP Support) Cable Diagnostic feature, LLDP, LLDP-MED, SNTP/NTP, RMON, SNMP v1,v2c, v3 and SNMP Traps. Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required.(a) 8 port PoE Layer 2 Network Switch with PoE Support of 130W or higher with each copper port supporting 802.3at PoE+. |
| 47 | Supplying, installation, Testing and commissioning of following capacity 24 port Layer 2 indoor Network Switch having features and specifications etc. as mentioned here under: At least 24 X RJ-45 Gigabit Ethernet Ports and additional 2 X 10G Base -T with 4 X SFP Ports with non-blocking architecture by having Switching capacity of min. 168Gbps and packet forwarding rate of 125Mpps or higher, 16K MAC table. Console Port, USB port, Stacking support of min. 8 units per stack. Internal dual AC Power supply, STP, RSTP, MSTP, BPDU Filter, BPDU Restriction, Min. 9K Jumbo Frame, LBD, IGMP Snooping V1/V2/V3, MLD Snopping V1/V2. IGMP /MLD Groups 1K or more, IPv4/IPv6 Loopback Interface, 16 L3 IP Interface, Ipv6 ND, VRRPv3, UDP Helper, ECMP. VLAN: 802.1Ǫ, Port based, Ǫ-in-Ǫ, Multicast VLAN, Protocol VLAN, VLAN Trunking, DHCP Snopping, Server, server Screening. RADIUS , TACACS+ Authentication, ǪoS: 802.1P, 8 queues per port, ǪoS : WRR, Strict+WRR, WRED, 802.1p. ACL: MAC based, IPv4C IPv6, TCP/UDP Port number, time based ACL, TFTP Client, SNMP V1, v2c, v3, SNMP traps, RMON, DHCP server, relay, client, LLDP, LLDP-MED, OAM, Dying Gasp, 802.3ah, sflow, RIP, OSPF v2/v3, policy based route, SSL, SSH. 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45 access ports. Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required.(a) 24 port PoE Layer 2 Network Switch with PoE Support of 370W or higher with each copper port supporting 802.3at PoE+ min. |
| 48 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required.(a) 6U Rack |
| 49 | (b) 9U Rack |
| 50 | LED DisplaySupplying, Installation, Testing and Commissioning of following size LED display (LED monitor) industrial grade with3840x2160 resolution or better, USB playback, Bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+,brightness: 500-nits or better, Video wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing angle (H/V):170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc.as required.(a) 55 inch or larger |
| 51 | Supplying Installation Testing and Commissioning of following Channel Network Video Recorder (NVR) with camera licenses to record for all channels having specifications and features etc as mentioned below : 1) Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses to record per NVR and to provide a live view, storage and simultaneously Multi-channel playback of all IP camera or more and must be ONVIF with minimum support of 384 Mbps incoming Bandwidth. 2) NVR should support video compressions : H. 265 or better, H. 264, MJPEG. 3) Must support 1 channel RCA Input, 2 channel RCA Output for Two-way Talk with G. 711U/A, G. 711u, PCM, G726 audio compressions. 4) Intelligent auto power on when power resumes after power outage.5) Storage: It should support minimum 8 SATA Slots with 20TB capacity/ Slot and RAID support of RAID 0/1/5/6/10.6) Connectivity Interface : 2 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x RS485, 1x RS232, 1x eSATA Port 7) Backup Interface :Its should have 4 Nosx USB port (2x USB3. 0, 2xUSB2. 0) 8) Video Output Ports: 2x HDMI and 2 VGA 9) Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various type of external sensors and output devices like hooter/ Siren etc. 10) Email & SMS Altert options: Option for SMS/ Email Alerts to minimum 5 designated mobile number for power failure, HDD failure, vandalism, tempring, network disconnection and panic 11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad, Android Phone) for alerts and viewing. 12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6, UDP, DHCP, DNS, SMTP, UPnP, IP Filter, PPPoE, FTP, DDNS, Alarm Server, IP Search, Multicast, Auto Registration, ONVIF (Profile T, Profile S, Profile G), CGI, SDK and OEM Cloud for remote monitoring without any public IP need. 13) Standards: CE, FCC, RoHS, BIS Certified 14) Power Supply : Should support AC100-240V, 50/60Hz Power supply. 15) Operating Condition : -5°C to 50°C, humidity 90% (max) (non-condensing) 16) The VMS application shall support all the features & functionalities of the offered cameras. 17) VMS should consist Licenses for all channels to record Cameras with General, motion detection, intelligent, alarm and POS recording modes. VMS should be provided with Camera Licenses, with no dependency of VMS licenses by binding with the MAC address of the cameras to achieve the functionality. 18) The NVR OEM shall be responsible for providing a mobile application compatible with both Android and iOS devices, enabling remote monitoring and playback of cameras/NVR footage. 19) The OEM must provide its own DDNS server hosted in India, eliminating the need for a public IP address for remote monitoring over the Internet. 20) Must support Continuous, Alarm, Motion, Instant, Panic Recording Mode 21) It should support Resolution: 32MP; 24MP; 16MP; 12MP; 8MP; 5MP; 4MP; 1080p; 720p; D1; CIF; QCIF 22) When alarm recording is enabled and an event occurs, you can click the alarm icon on monitoring page to view the alert details. The snapshot function is supported on monitoring and playback page |
| 52 | 23) The Network Video Recorder (NVR) shall be configured to send email whenever a system message is created or an alarm event occurs. The email server shall be a valid SMTP server. Each recipient email address shall be configured to receive any combination of critical, warning, or informational messages or alarm notifications. When an alarm occurs, the email message includes the NVR name, time of alarm and a list of camera that is configured to record upon alarm 24) It should have Web and GUI interface. 25) Built-In Artificial Intelligence: NVR should have built-in AI :- - 2 Channel face detection and recognition, - Minimum 4 Channel perimeter protection, - Minimum 8 Channel Smart Motion Detection 26) Face Recognition Database Capacity: It should support total Blacklist and Whitelist capacity of Minimum 20, 000 Faces or more with Face Detection speed of 12 face images/sec and facility to add Name, gender, birthday, address, credential type, credential No., countries & regions and state to each face image. 27) Face & Human Attributes Search: Search Pictures/ Video by Gender, age group, glasses, expressions, face mask, beard, Top color, top type, hat, bag, age, gender and umbrella. 28) ANPR Capability: It should support ANPR Camera with License plate, plate color, vehicle body, vehicle model, vehicle logo, calling, seatbelt, vehicle registration location etc vehicle attributes. 29) Alarm Notifications based on: Motion detection, video tampering, video loss, scene changing, PIR alarm, Camera external alarm, Face detection, face recognition, perimeter protection (intrusion and tripwire), ANPR, people counting, stereo analysis, crowd distribution, heat map, Disk Full, Storage Error, IP Conflict and abnormal behavior of fan, cybersecurity exception 30) Alarm Notification should be linked with Recording, snapshots, Camera external alarm output, buzzer, logs, presets and email. 31) General AI Based Search: Search Pictures by channel, time, event type, target classification (Fall Detection, People Approach Detection, People No. Exception Detection, People Staying Detection, Violence Detection.32) Smart playback function: Should support smart search for the selected area in the video and smart playback to improve the playback efficiency 33) VCA (Video Content Analytic): Should support multiple video contented analytics based on camera analytics34) Analytics by NVR: Perimeter protection and face recognation32 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16/25/32 (36), 2nd screen: 1/4/8/9/16 |
| 53 | Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3. 5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. (a) 8 TB (Terabytes) |
| 54 | Supplying, Installation, Testing and commissioning of CAT6 Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568. 2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required. |
| 55 | Supplying and fixing 24U Rack with 4 inch Castor wheels and front brake Floor Standing Rack with Main Frame Pillar of 1. 25mm Powder Coated CRCA Sheet with removable side panels, L- Shape adjustable Vertical Mounting Rail of 2mm with U'Marking completely knocked-down condition (CKD) Shape, fitted with 4 number cooling fans, minimum 5nos two line cable entry/exit provision at top and bottom with rubber protection, Front door 5mm Toughened Glass with MS frame or MS perforated with lock, Rear MS vented or perforated door, Powder coated Color- RAL- 7035 or black, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. |
| 56 | SH:V (Audio Video System)Supply, Installation, testing & commissioning of High performance Digital Wired Desktop Delegate/chairman Unit with High-directivity gooseneck condenser micro phone with red LED indicator ring, Microphone stem length not more than 300mm, Low-voltage DC24V operation for enhanced safety, Signal to Noise ratio ≥65dB, TFT display screen showing real-time meeting data, Third-party system integration via RS-232, enabling camera tracking and remote microphone control, Optimal speaking distance: 10 - 40 cm; intelligent noise suppression effective up to 1 meter, etc completed as required. |
| 57 | Supplying, Installation, testing & commissioning of High performance digital wired conference controller unit Directly connects up to 60 units, expandable to 100 units with extension modules, Maximum power consumption 120W, RS-232 control support for third-party central control integration (camera tracking, microphone management, and meeting modes), 4-in/1-out seamless HDMI switcher, supporting 4 cameras at 1080p@60Hz with zero switching delay, PELCO-D, PELCO-P, VISCA via RS-485 interface, etc completed as required. |
| 58 | Supplying, Installation, testing & commissioning of Two way full range coaxial ceiling speaker with 5.25” Polypropylene woofer with rubber surround for extended low frequency response, 0.75” Polycarbonate tweeter with swivel mount for high frequency directivity, Driver Power Handling 30W RMS / 60W Program / 120W Peak, High performance 100V LMT inbuilt – 15W and 10W selectable via switch, Calculated Max SPL 104dB Continuous / 107dB Program / 110dB Peak, etc. as required. |
| 59 | Supplying, Installation, testing & commissioning of Mixer amplifier 4-16 ohm,with 120W RMS output power, 70V/100V output,USB/FM/Bluetooth Media player, 2 Aux and 3 microphone inputs,Frequency Response: 35Hz to 20 kHz, Total Harmonic Distortion: 0.05%, Intermodulation Distortion: <0.35%(60Hz and 7kHz at 4:1, from full rated output to-30dB, Signal-to Noise Ratio: >75dB, Crosstalk: >80dB (below rated power, 20Hz to 1kHz), toroidal transformer, 1.4’’ TS Jack , RCA, etc complete as required. |
| 60 | Supplying, Installation, testing & commissioning of High Performance Digital Wireless dual handheld microphone system, 200 selectable frequencies, RF Carrier Frequency Range - CH1: 612.000 - 651.600 MHz (100 Selectable Frequencies) CH2: 652.000 - 691.600 MHz (100 Selectable Frequencies), Audio Frequency Range - 30Hz ~ 20 kHz, Signal-to-noise (A-weighted) - 120dB(A) , RF output - 50 mW max, Oscillation Mode -Inside the chip VCO oscillation True Diversity dual reciever, Two receivers in 1U rack mount frame, Two Dynamic wireless handheld transmitter microphones, Long range low power consumption, etc complete as required. |
| 61 | Supplying, Installation, testing & commissioning of 75'' Interactive Touch Display with Panel Technology - IPS/ Direct - LED, Aspect Ratio -16:9, Resolution - 3840 x 2160 - 4k UHD, Brightness* - 350 cd/m2, Inbuilt Memory 4 GB RAM & 32 GB memory, Android: v11.0, CPU : Quad Core, Estimated Life Time: 50000 Hrs (Typical), Viewing Angle (HxV) - 178x178, Touch Technology: Infrared, Touch Point: 20, Response Time: 8ms, Surface Protection: 4mm Thick Touchened Glass, Touch Tools: Finger, Stylus, Glove, Opaque objects, Inputs: 1 x mini AV / 1 x HDMI 2.0, Output: 1 x Coax, 1 x Mini AV, 1 x Earphone Out / 1 x USB-B, 1 x USB-A 2.0, 1x USB-A3.0, 3x USB-A 3.0, 1x USB-B 3.0, 1xUSB-C, 1x RJP45 Input, 1x RJP output, 1 x RS232C, 3 +1 (WiFi + Bluetooth), Expansion: Windows OPS: Intel Statandard 80 Pin OPS - Optionals, etc complete as required. |
| 62 | Supply Installation testing & Commissioning of 4x2 matrix Switcher with Supports resolutions up to 4K 60Hz, with additional support for HDR, Extract audio from HDMI® to Toslink (Optical) and 3.5mm audio, Supports ARC as well as a Downscaler-Function via HDMI® Out B, etc complete as required. |
| 63 | Supply Installation testing & Commissioning of 70m Cat.6 HDMI 4K30 & IR Extender with PoC & Loop Out, Extends HDMI® & IR Signals up to 70m using a single Cat.6 Cable, Supports resolutions up to 3840x2160@30Hz 4:4:4 8bit, etc complete as required. |
| 64 | Supply, Installation, Testing & Commissioning of Pop-up Cable Cubby having 1 no. HDMI, 1 RJ45 and 1 no. power socket etc. as required. |
| 65 | Supply Installation testing & Commissioning of Wireless presentation device along with 1 nos. dongle, Operating system Windows 10 and higher macOS 11 (BigSur) and higher., Android v9 and higher (ClickShareApp)*, iOS 12 and higher (ClickShareApp)*, Video outputs 4K UHD (3840*2160) @ 30Hz. HDMI 1.4b, Audio output HDMI, USB 1 X USB-A, 1 X USB-C, ClickShare Buttons 0, ClickShare App Desktop & Mobile, Native protocols Airplay, Google Cast, Miracast, Maximum number of simultaneous connections (with Buttons and/or App) 32, Noise Level Max. 25dBA @ 0-30°C, Max. 30dBA @ 30-40°C, Authentication protocol WPA2-PSK in stand alone mode WPA2-PSK or IEEE 802.1X using the ClickShare Button in network integration mode, Wireless transmission protocol IEEE 802.11 a/g/n/ac and IEEE 802.15.1, Reach Adjustable with signal strength modulation; max. 30m (100 ft) between ClickShare Button and ClickShare Base Unit, Frequency band 2.4 GHZ and 5 GHz, Frequency band 2.4 GHZ and 5 GHz (DFS channels supported in select number of countries), Connections 1x Ethernet LAN 1Gbit 1x USB Type-C 2.0 (front); 1x USB Type A 2.0 (front), Temperature range Operating: 0°C to +40°C (+32°F to +104°F), Max: 35°C (95°F) at 3000m, Storage: -20°C to +60°C (-4°F to +140°F), Humidity Storage: 0 to 90% relative humidity, non-condensing, Operation: 0 to 85% relative humidity, non-condensing, etc as required. |
| 66 | Supply, Installation, Testing & Commissioning of HDMI to HDMI cable 20 Mtr etc. as reqd. |
| 67 | Supply, Installation, Testing & Commissioning of HDMI to HDMI cable 1.5 Mtr etc. as reqd. |
| 68 | Supply, Installation, Testing & Commissioning of 18U pre-wired Audio Equipment’s Rack front lockable glass door, fan tray for cooling, caster wheels base, main panel with spike buster, individual fuse power supply unit, including all internal wiring, etc as required. |
| 69 | Supply, Installation, Testing & Commissioning of shieled 2 Mtrs CAT 6, STP cable along with compatible connectors in the existing surface / recessed steel / PVC as required. |
| 70 | Supply, Installation, Testing & Commissioning of shieled 15 Mtrs CAT 6, STP cable along with compatible connectors in the existing surface / recessed steel / PVC as required. |
| 71 | Supply Laying & Fixing of of Microphone lines high grade, professional low-noise, 2 crore high conductivity PVC insulated in PVC jacket, shielded copper cable with Di- electric insulator both end with XLR m/f connector as required. |
| 72 | Supply Laying & Fixing of speaker of 2 core, 1.5 sq mm high defintion speaker cable, PVC insulated in PVC jacket laid in existing conduits as reqd. |
| 73 | Supply installation, testing and commissioning of Video Conferencing System complete with codec is a modular video conferencing engine built for enterprise-grade large meeting environments, supporting both H.323 and SIP up to 6 Mbps bandwidth with IPv4/IPv6 dual-stack networking. It delivers people video resolutions up to 4K Ultra HD at 30 fps and 1080p at 60 fps, with support for H.264 AVC, High Profile, H.265 (HEVC), SVC, H.263, and RTV video standards. Content sharing is enabled via HDMI input and USB-C, with resolutions supported up to UHD (3840×2160). The codec integrates advanced audio processing, including automatic gain control, adaptive echo cancellation, noise suppression, NoiseBlockAI, Acoustic Fence, keyboard noise reduction, and Active Lip Sync. It supports a wide range of audio codecs, such as Siren 22, G.719, G.722.1 Annex C, G.722, G.711, and G.729A. Connectivity includes 2× HDMI outputs, 1× HDMI input, 1× USB-C, 2× USB-A, 1× line-in and line-out (3.5 mm), 1× RJ-45 for network (PoE+ IEEE 802.3at class 4/5/6), and an auxiliary LLN port for peripherals. The device is managed via the Poly Lens cloud and supports remote APIs (REST/CLI). The smart PTZ camera integrates seamlessly with the codec and features a 4K UHD (3840×2160) 8 MP image sensor, 12× optical zoom, and 16× digital zoom. It offers a wide field of view of up to 107° (diagonal), with motorized pan (±170°) and tilt (±30°) functions. Intelligent framing is enabled, supporting Presenter Tracking and Group Framing for automated meeting experiences. The camera provides flexible connectivity through USB-B and Ethernet (PoE+ 802.3at), with optional 12 VDC input. A dual-microphone beamforming array is integrated for localized audio pickup. The camera includes wall mount accessories and remote control, and it is certified for Microsoft Teams and Zoom Rooms. The Touch controller complements the system with a 10-inch high-resolution interactive display for meeting scheduling, room control, and call management. It includes multi-colored LED indicators for room status and a simplified single-cable installation for both power and data over Ethernet (PoE). Together, the codec, camera, and controller deliver a complete modular video conferencing solution, providing 4K video, enterprise-grade audio, AI-powered intelligent camera tracking, and intuitive room control, making it suitable for medium-to-large conference rooms requiring reliable, scalable, and future-proof collaboration infrastructure etc. as reqd. |
| 74 | Supply, installation, testing and commissioning of 8 analog input 8 analog output Digital Signal Processor, Complete matrix routing of all inputs and outputs, High-performance ADSP SHARC 21489 40-bit floating-point processor optimised for audio processing, 24bit/48kHz sampling rate for exceptional audio quality and performance, Frequency Response 20Hz – 20kHz, ±0.3dB, THD + Noise < -94dB @17dBu, Comprehensive metering with 16 user presets, Input channels: Signal generator (sine wave, White noise and Pink noise), expander, compressor, AGC, PEQ, feedback suppression and 48V phantom power, Automixer with gain sharing and mic priority setting, Acoustic Echo Cancellation (AEC) 8×8 for local and remote inputs, Output channels: Low pass & high pass filters – Bessel, Butterworth, Linkwitz-Riley slopes from 6-48dB/oct, 8 Parametric equalizer (PEQ) – PEQ, low shelf, high shelf, low pass, high pass, Delay (up-to 408m/1200ms) and limiter on output channels, In-built USB sound card for USB recording, playback and soft video conferencing codec, 8-way GPIO (General purpose input output) configured as inputs or outputs, allowing for flexible control of digital signals, Camera tracking with look at me feature via voice control, Ethernet, RS232/485 control interface for third-party control, Full feature control software, etc complete as required. |
| 75 | Supplying, installation, Testing and commissioning of following capacity 24 port Layer 3 Network Switch having features and specifications etc. as mentioned here under: At least 20 X RJ-45 Gigabit Ethernet Ports and additional 4 combo 10/100/1000base-t/SFP Ports with additional 4 SFP+ ports non-blocking architecture by having Switching capacity of min. 128Gbps and packet forwarding rate of 95Mpps or higher, 16K MAC table. Console Port, USB port, Internal AC Power supply with operating temperature of 0 to +50 degree Celsius. Stacking port with stacking support of minimum 8 units per stack. 48KMac address, 9K or more Jumbo frame, ERPS with enabling ring to converge in less than 50 ms from node or link failure, Static routing, Static, 6to4, ISATAP and GRE, IPv6 Neighbor Discovery (ND), BGP, ISIS, MPLS, VRRP v2, OSPFv2/v3,PBR, Route Redistribution, RIPv1/v2/ng, IP Helper all L3Protocols should support from day 1 for both IPv6 and IPv4,802.1x, Port security , Radius C TACACS+ authentication C accounting, DAD, DAI, DoS attack prevention, SSH, Guest VLAN, IP Access List, MAC Access List. Multicast: VLAN, PIMSM,PIM-DM, PIM- SDM, PIM-SMv6, DVMRP v3 and MSDP,IGMP C MLD Snooping, Flow mirroring, IGMP C MLD Snooping Ǫuerier, Per-VLAN IGMP C MLD Snooping. SNMP, Dual configurations, Multiple images, RMON, LLDP/LLDPMED, sFlow, DHCP/BOOTP Client, IPv4/IPv6, Syslog server, Debug command, 802.3ah Ethernet Link OAM, 802.1agConnectivity Fault, Y.1731 OAM, 802.1Ǫbb Priority- based Flow Control (PFC), Dying Gasp, Cable Diagnostics , 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45 access ports. Certifications: UL, CE, FCC, RoHS, MTCTE,OEM/Product must be on Trusted Telecom Portal of Department of Tele communication, Government of India etc. complete as required. |
| 76 | Supply of 24 port Cat6 Patch Panel loaded. Must be of 1Uheight with clear label holders and white label with the panel.24 Ports Cat-6 Patch Panel should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D |
| 77 | Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D(a) Copper Patch Cords of length 1m (3ft) |
| 78 | (b) Copper Patch Cords of length 3m (10ft) |
| 79 | Supply and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U' Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required.(a) 9U Rack |
| 80 | SH:IV (FIRE DETECTION AND ALARM SYSTEM)Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. (a) Two Loop Panel. |
| 81 | Supplying, installation, testing & commissioning of repeater panel with 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required |
| 82 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 83 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 84 | Supplying, installation, testing & commissioning of intelligent addressable programmable sounder complete as required. |
| 85 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 86 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required. |
| 87 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 88 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. |
| 89 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 90 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 91 | Supplying, installation, testing & commissioning of addressable strobe complete as required. |
| 92 | SH : VII Public Address SystemSupplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP4 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. |
| 93 | Supplying, installation, testing & commissioning of 1. 5/3/6W ceiling speaker complete as required. |
| 94 | Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
| 95 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
| 96 | Supplying & laying of 2x1. 5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 97 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. (a)speaker cable Two pair, 2-core, 1. 5 sqmm |
| 98 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 99 | SH VIII : EPABX /IPABXSupply,Installation,Testing & commissioning of IP PBX systems configured CPU ,Power supply ,8 P&T ,8 Digital Extension & 32Analog extensions with 1 SIP trunk, 30 IP Extension ,19 \\" Rack mountable expandable upto 256 Port Completeaccessories ,connection etc as req. |
| 100 | Supply,Installation,Testing & commissioning of IP phone with HD Voice Dual Gigabit Ethernet Ports,16 SIP Accounts,4.3\\" 480x272 Pixel Colour Display with backlight*,5 Way Conference, PoE Supported ,1 x USB 2.0 ,Built-in Bluetooth 4.2,Built-in dual band Wi-Fi-2.4G/5G Complete accessories ,connection ex etc as req. |
| 101 | Supplying, Installation, Testing & Commissioning of Analog phones having standard features like 16 digit LCD display, 2 way speaker, caller ID and number storage facility etc. complete as required. |
| 102 | Supplying and drawing 20 Pair 0. 5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC Conduit etc. complete as required. |
| 103 | Less for credit of old dismantle material i.e. copper wire, light fittings, fans, Air conditioner, rack & speaker under buyback arrangement etc. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 09, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 16, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 daySep 16, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 1 dayTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender