Tender For Supply, Fixing Installation And Testing Of Materials For Internal Electrical Works Of Office Building Of Baleshwar Municipality
Tender Value
11 Lakhs
Estimated cost
Bid Submission
23 Sep 2026
10 days left
EMD
11005
Bank guarantee accepted
Document Fee
6000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Baleshwar → Odisha
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Supply, Fixing Installation And Testing Of Materials For Internal Electrical Works Of Office Building Of Baleshwar Municipality
BOQ
| Sl. No. | Item Description |
| 1 | INTERNAL ELECTRICAL WORKS : Recessed wiring to light point/ fan point/ exhaust fan point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked (Make- Finolex/ Anchor/ Polycab/ Havells/ RR Kable/ Kei/ V-guard) with 20 mm dia HMS FRLS PVC conduit ISI marked (Make- Akg/ Bec/ Precision/ Norpack/ Anchor/ Kinjal) 6A modular type (anti bacterial & flame retardant type) switch ISI marked (Make- Schneider(Zencelo)/ legrand( Myrius-Next gen)/ Panasonic (vision)) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) (anti bacterial & flame retardant type) Make- Schneider(Zencelo)/ legrand( Myrius-Next gen)/ Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistranded copper conductor as earth wire including all accessories and connection. All the switches & sockets should be warrantied for a replacement period of 2 years against defects with necessary test report & Warranty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials. |
| 2 | Supplying, fixing of 6A switch socket on the same board in existing switch board with complete fitting by 01 no of 6A switch & socket (modular type)( (anti bacterial & flame retardant type)) & other required accessories of ISI marked. Make- Schneider (Zencelo)/ legrand (Myrius-Next gen)/ Panasonic (vision). (Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a replacement period of 2 years against defects with necessary test report & Warranty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 3 | Supplying, fixing of 6A switch socket on the separate board with complete fitting by 01 no of 6A switch & universal socket(modular type)( (anti bacterial & flame retardant type)) with suitable size modular box & cover(anti bacterial & flame retardant type) including supplying of all required accessories of ISI mark. Make- Schneider (Zencelo)/ legrand (Myrius-Next gen)/ Panasonic (vision). (Maximum 02 nos point in one circuit). All the switches & sockets should be warrantied for a period of 2 years against manufacturing defects against which necessary test report & Warranty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials. |
| 4 | Modular base & cover for 8 module |
| 5 | Supply, installation, testing & commissioning of 6 / 16 Amp Plug Boards consisting of 2nos 16 Amp clip-in type modular switch with indicator and 2nos 6/16 Amp clip-in type modular shuttered plug socket fixed on metallic concealed box including interconnections and making good the damages caused complete as required.Make of Switches & Socket: Legrand/ Panasonic/ Havells/ ABB (For equipment power)All the switches & sockets should be warrantied for a replacement period of 2 years against defects with necessary test report & Warranty certificate to be submitted to this office for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 6 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/ Anchor/ Polycab/ Havells/ RR Kable/ Kei/ V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make- Akg/ Bec/ Precision/ Norpack/ Anchor/ Kinjal as required: 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuity conductor. In 20 mm dia non metallic heavy duty conduit (Primary Light point to Secondary Light Point in Same Circuit) (2X1.5+1X1.5) |
| 7 | 2 nos single core 2.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuity conductor in 20 mm dia non metallic heavy duty conduit. (Lighting DB to LSB/ LIGHT CKT/ 5A PLUG) (2X2.5+1X1.5) |
| 8 | INDOOR AND OUTDOOR FIXTURES:Supplying, installation, testing and commssioning of 1200 mm sweep white/milky colour BLDC copper winding ceiling fan with aluminium blades having wattage not more than 28W and air delivery ≥215m3/min Make-Crompton Energion Groove /Havells Efficiencia Neo/Usha Technix/Bajaj Turbo Pro 12DC5 including wiring the down rod of standard length (upto 30 cm) with 1.5 sq mm PVC insulated, copper conductor, single core cable etc. as required,Replacement Warranty will be 4 years.(With fan Regulator) |
| 9 | S/F of 5 step type Modular electronic Fan Regulator ISI Marked with all connection complete in all respect. Make-Schneider(Zencelo)/legrand( Myrius-NEXT GEN)/Panasonic (vision) |
| 10 | SITC of energy efficient LED tube light fittings with decorative aluminium batten and LED tube light having power rating not more than 20 watt and lumen output not less than 2200 lumen complete with electronic driver and all other accessories with diffuser having 2 years warranty i/c connection etc as required. Make: Panasonic/ LT/ Havells/ Philips/ Wipro/ Crompton/ Bajaj. The luminaire should be Replacement Warranty will be 2 years. |
| 11 | 3 PHASE MAIN PANEL: S/I/Commissioning of LT indoor floor mounted cubical type electrical main panel (for both light circuit) made out by 2mm CRCA steel sheet duly derusted & painted by siemens grey powder coat paint. Warranty period of replacement of panel & accessories must be 1 year & complete test certificate must be submitted along with panel board including component list.. 20X6MM Separate copper Earth bus bar should be installed. All the feeders shall have ON/OFF/TRIP indication.Provision of type 2 3P+N 40kA SPD alongwith 63A, 4P, MCB, C series, 10kA shall be installed in all the incomers. |
| 12 | One (1) - Incomer (1no from Energy Meter outgoing panel - 200A 4P Icu=100%Ics, 25KA MCCB with adjustable Thermal Magnetic Release with Ics=100% Icu. (make- (Make- Legrand-DPX3 / Siemens-3VA Model/ Schneider- CVS/ ABB Formula) with shunt trip.with axullary for BMS with 3 Nos Phase indicating lamps with control fuse/ MCB Digital Voltmeter and Ammeter with selector switch with required other accessories. |
| 13 | 250 Amp Switch Disconnector Fuse Unit with ISI marked HRC Fuse (Panel mounted) |
| 14 | Three (3) - Outgoing Feeders for (3 Nos to MCB DB of 3 buildings): 100 Amp 4P, Icu=100%Ics, 25KA MCCB with adjustable Thermal Magnetic Release with Ics=100% Icu.Make- Legrand-DPX3 / Siemens-3VA Model/ Schneider- CVS/ ABB Formula with shunt trip |
| 15 | MCBs, RCCB, DB: Supplying and fixing of following mentioned way, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ ABB Itus. The Distribution boards should be Replacement Warranty will be 3 years.: 8Way(8+(4x3)+(8x3)) Way TPN MCB DD 7 Segment DB Horizontal Type as per IEC 61439-3 with configuration of incoming I-8 modules,sub incommer-12 module & out going-24 modules,suitable for Flush mounting and Surface mounting with Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door Warranty on DB is 3 years ( DG Power DB) |
| 16 | 12Way(12+(4x3)+(8x3)) Way TPN MCB DD 7 Segment DB Horizontal Type as per IEC 61439-3 with configuration of incoming I-8 modules,sub incommer-12 module & out going-24 modules,suitable for Flush mounting and Surface mounting with Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door Warranty on DB is 3 years ( DG Power DB) |
| 17 | Supplying and fixing 6-32 Amps rating, C series,10KA breaking capacity,SP, 230 volts, MCB . Make- LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB200 in the existing MCB DB complete with connections, testing and commissioning etc. as required. The MCB should be Replacement Warranty will be 1 year. |
| 18 | Supplying and fixing 40 Amps rating,C series,10KA breaking capacity, 2P, 230 volts, RCCB 30mA . Make- Legrand-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ ABB FB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. The RCCB should be Replacement Warranty will be 1 year. (For Light DB and Emergency Light DB) |
| 19 | Supplying and fixing 32amps rating,double pole mcb type changeover 240 volts, C series,10KA breaking capacity, of Make-LEGRAND/ Siemens/ Schneider/ABB the existing MCB DB complete with connections.Warranty on MCB is 1 year. |
| 20 | EARTHING : Earthing with GI Pipe 40mm dia and 3m long ISI marked including accessories and providing masonary with cover plate having locking arrangement and watering pipe etc (with charcoal and salt) as required. |
| 21 | Providing and fixing 8 swg GI wire 4mm dia on surface or in recess for loop earthing as required. |
| 22 | LIGHTNING PROTECTION : Supply and fixing of Lightning finial, 25 mm dia x 300 mm long G.l. Conductor.Tested as per IEC 62561.Make-OBO/Dehn/ABB |
| 23 | POWER CABLES: Supply, installation, testing & commissioning of 50 sq mm 4 core PVC Armoured underground cables ISI marked.Make- Finolex/ Anchor/ Polycab/ Havells/ RR Kable/ Kei. All the cables should be warrantied for a replacement period of 2 years against defects with necessary test report & Warranty certificate to be submitted to this office for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 24 | Supply, installation, testing & commissioning of 10 sq mm 4 core PVC Armoured underground cables ISI marked.Make- Finolex/ Anchor/ Polycab/ Havells/ RR Kable/ Kei .All the cables should be warrantied for a replacement period of 2 years against defects with necessary test report & Warranty certificate to be submitted to this office for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 25 | MISCELLANEOUS: 200mm x 150 mm M.V. danger notice plate as required |
| 26 | GI Nut, thimble, bolt, washers etc. as required Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 09, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 23, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysSep 24, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓