Tender For Repair /Maint Of Lt Feeder Pillar Boxes, Lt Ug Cables And Connected Works Of Lt Distribution System Including Attending Fuse Of Call At Map Naraina, 5 Sikh Li, Dgbr, Narainabaugh, Sanjevani Enclave, Me Line, Dental Offr Mess, 505 Jco Encla
Tender Overview
Project Description
Tender for Repair /Maint Of Lt Feeder Pillar Boxes, Lt Ug Cables And Connected Works Of Lt Distribution System Including Attending Fuse Of Call At Map Naraina, 5 Sikh Li, Dgbr, Narainabaugh, Sanjevani Enclave, Me Line, Dental Offr Mess, 505 Jco Enclave, 505 Unit Line Area, Cod Area, 1811 Pnr Coy, 226 Supply Depot, Fol Depot, Kirby Map Accn, Kirby Offr Accn, Lao, Esd, Cicg, Subramaniyam Line & Bor Under Age E/M No-I Of Ge (U) Elect Supply Delhi Cantt-10
BOQ
| Sl. No. | Item Description |
| 1 | Material and labour for excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and leveling of bottom surface to required level complete all as specified and directed by Engineer- in- Charge. |
| 2 | Material and labour for returning filling in, including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by Engineer- in- Charge. |
| 3 | Material and labour for removing excavated material (i.e. soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 4 | Material and labour for Sand cushioning/sand covering for underground cable protection complete all as specified and directed by Engineer- in- Charge. Note: Note : Measurement shall be taken after punning down. |
| 5 | Supply and laying for sub class 'B' bricks of old size (approved size locally available) laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer- in- Charge. |
| 6 | Material and labour for GI pipe light grade 50 mm dia for cable protection on road crossings /plinth protection/ lamps post etc with fixed to the pole wall etc. suitable fittings for cable protection complete all as specified and directed by Engineer- in- Charge. |
| 7 | Material and labour for GI pipe light grade 80 mm dia for cable protection on road crossings /plinth protection/ lamps post etc with fixed to the pole wall etc. suitable fittings for cable protection complete all as specified and directed by Engineer- in- Charge. |
| 8 | Material and labour for Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable complete all as specified and directed by Engineer- in- Charge. |
| 9 | Material and labour for PCC 1:3:6 type C-2 (using 40 mm graded aggregate) for foundation, filling and mass concrete or similar works complete all as specified and directed by Engineer- in- Charge. |
| 10 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade 3.5/4 core XLPE , armoured, electric power cables (heavy duty) with aluminium conductor of the following size including dismantling old one complete all as specified and directed by Engineer- in- Charge. Make : Havells/KEI/Polycab/Paragon |
| 11 | 10 Sqmm 4 Core |
| 12 | 16 Sqmm 4 Core |
| 13 | 25 Sqmm 4 core |
| 14 | 35 Sqmm 3.5 core |
| 15 | 50 Sqmm 3.5 core |
| 16 | 70 Sqmm 3.5 core |
| 17 | 95 Sqmm 3.5 core |
| 18 | 120 Sqmm 3.5 core |
| 19 | 150 Sqmm 3.5 core |
| 20 | 185 Sqmm 3.5 core |
| 21 | 240 Sqmm 3.5 core |
| 22 | 300 Sqmm 3.5 core |
| 23 | Supply and fix in repairs ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 800 Amps complete all as specified and directed by Engineer- in- Charge. |
| 24 | Supply and fix in repairs MCCBs of following current carrying capacity complete all as specified and directed by Engineer- in- Charge. |
| 25 | 3 Pole MCCB 630 Amps, Adjustable type,415V, 50KA rating |
| 26 | 3 Pole MCCB 400 Amps, Adjustable type,415V, 36KA rating |
| 27 | 3 Pole MCCB 315 Amps, Adjustable type,415V, 3KA rating |
| 28 | 3 Pole MCCB 250 Amps, Thermal release type, 415 V, 25KA rating |
| 29 | 3 Pole MCCB 200 Amps, Thermal release type, 415 V, 25KA rating |
| 30 | 3 Pole MCCB 160 Amps, Thermal release type, 415 V, 16KA rating |
| 31 | 3 Pole MCCB 125 Amps, Thermal release type, 415 V, 16KA rating |
| 32 | 3 Pole MCCB 100 Amps, Thermal release type, 415 V, 16KA rating |
| 33 | 4 Pole MCCB 630 Amps, 415 V, Adjustable type with breaking capacity 50 KA |
| 34 | 4 Pole MCCB 400 Amps, 415 V, Adjustable type with breaking capacity 36 KA |
| 35 | 4 Pole MCCB 315 Amps, 415 V, Adjustable type with breaking capacity 36 KA |
| 36 | 4 Pole MCCB 250 Amps, 415 V, Thermal release type with breaking capacity 25 KA |
| 37 | 4 Pole MCCB 200Amps, 415 V, Thermal release type with breaking capacity 25 KA |
| 38 | 4 Pole MCCB 160 Amps, 415 V, Thermal release type with breaking capacity 16 KA |
| 39 | 4 Pole MCCB 100 Amps , 415 V, Thermal release type with breaking capacity 16 KA |
| 40 | Supply and fix in repairs Isolator 415 Volts of following current carrying capacity complete all as specified and directed by Engineer- in- Charge. |
| 41 | 4 Pole 63 Amps |
| 42 | 4 Pole 100 Amps |
| 43 | 3 Pole 63 Amps |
| 44 | 3 Pole 100 Amps |
| 45 | 4 Pole 40 Amps |
| 46 | Material and labour for heat shrinkable straight through joint for LT UG cable including jointing kits complete for making joints suitable for aluminium conductor cable of size 3.5/ 4 core 25 to 50 sq.mm complete all as specified and directed by Engineer- in- Charge. |
| 47 | All as per Item No.14 herein before but for cable of size 3.5 core 95 to 120 sq.mm complete all as specified and directed by Engineer- in- Charge. |
| 48 | All as per Item No. 14 herein before but for cable of size 3.5 core 150 to 185 sq.mm complete all as specified and directed by Engineer- in- Charge. |
| 49 | All as per Item No. 14 herein before but for cable of size 3.5 core 240 to 300 sq.mm complete all as specified and directed by Engineer- in- Charge. |
| 50 | Disconnecting, dismantling of existing feeder panel and supply, fabricate, install, testing and commissioning of LT feeder panel board of suitable size, out door type double door, dust and vermin proof made out of 3.15 mm thick MS sheet mounting on suitable size foundation with 150 mm thick PCC (1:3:6) type C 2 with 100 mm offsets and panel board with front and back opening and locking arrangement compete two coats of finishing powder coated paint of approved shade over one coat of red oxide primer including horizental busbar of aluminium strip of size 1.5 times of incoming MCCB for three phase 4 wire including the following accessories and fitted in complete all as specified and directed by Engineer- in- Charge. : -(a) Incoming: MCCB high breaking capacity 4 pole 415 volt 36 KA breaking cap adjustable thermal release range 630 amp -01 No(b) Outgoing: (i) MCCB 3 pole 415 volt 25 KA breaking cap thermal release range 160 amp – 06 No (iv) Multifunnction Meter, Phase Indicator (R, Y & B) with selector switch |
| 51 | Disconnecting, dismantling of existing feeder panel and supply, fabricate, install, testing and commissioning of LT feeder panel board of suitable size, out door type double door, dust and vermin proof made out of 3.15 mm thick MS sheet mounting on suitable size foundation with 150 mm thick PCC (1:3:6) type C 2 with 100 mm offsets and panel board with front and back opening and locking arrangement compete two coats of finishing powder coated paint of approved shade over one coat of red oxide primer including horizental busbar of aluminium strip of size 1.5 times of incoming MCCB for three phase 4 wire including the following accessories and fitted in complete all as specified and directed by Engineer- in- Charge. : -(a) Incoming: MCCB 4 pole 415 volt 25 KA breaking cap adjustable thermal release range 250 amp -01 No(b) Outgoing: (i) MCCB 3 pole 415 volt 16 KA breaking cap thermal release range 63 amp – 04 No (ii) MCCB 3 pole 415 volt 16 KA breaking cap thermal release range 40 amp – 02 No(iii) Multifunnction Meter, Phase Indicator (R, Y & B) with selector switch |
| 52 | Supply, installing, testing and commissioning in replacement of factory made and tested Bus bar chamber outdoor type with canopy made out of 3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement of size not less than 400mm x 400mm x 300mm with 4 Nos 630 Amps aluminum bus bar and with 400 Amp MCCB, 4 pole, 36 KA, 415 Volt 50 Hz including excavation, earth work and platform for the Bus bar chamber with suitable size of foundation complete all as specified and directed by the Engg-in-Charge. Please Enable Macros to View BoQ information |
| 53 | Supply, installing, testing and commissioning in replacement of factory made and tested Bus bar chamber outdoor type with canopy made out of 3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement of size not less than 400mm x 400mm x 300mm with 4 Nos 630 Amps aluminum bus bar and with 400 Amp MCCB, 4 pole, 36 KA, 415 Volt 50 Hz including excavation, earth work and platform for the Bus bar chamber with suitable size of foundation complete all as specified and directed by the Engg-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents