Tender For Upgradation Of Fire Fighting System Fire Alarm System At Gmch Jammu Including Sir Col Chopra Nursing Home
Tender Value
1.85 Crore
Estimated cost
Bid Submission
17 Sep 2026
7 days left
EMD
3.70 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jammu → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Upgradation Of Fire Fighting System Fire Alarm System At Gmch Jammu Including Sir Col Chopra Nursing Home
BOQ
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer, Mechanical & Hospital Division GMCH Jammu. Upgradation of Fire Fighting System/Fire Alarm System at GMCH Jammu including Sir Col. Chopra Nursing Home MHDJ/e-NIT: 190 of 2026-27 Dated: 08.09.2026 Due : 17.09.2026 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Item Code / Make Quantity Units Estimated Rate Addition / Deduction Rate including GST to be quoted by the bidder Rs. P Currency Convertion against each Item Quoted Currency in INR / Other Currency Rebate on old parts in Percentage (%) if any Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category Net Cost of item Rs. P TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | PART A FIRE HYDRANT SYSTEM:SITC of over ground M.S Pipes (C class) IS:1239 including cutting holes & chases in bricks or RCC wall/slab/extraction of the damaged pipe below the ground, replacing the same with new MS Pipe above the ground. Painting with one coat of primer and two coats of synthetic enamel of approved shade of following sizes. Make:TATA/JINDAL/PARKASH/SURYA 150 mm dia |
| 3 | 100 mm dia |
| 4 | 80 mm dia |
| 5 | Providing/fitting of new Hydrant valve Stainless Steel IS:13039:1991 for external Hydrants and IS:3844:1989 for internal Hydrant System in place of totally damaged ones. Make: Minimax, Newage Fire, Safetap, Kartar. |
| 6 | Providing/fitting of new Jockey pump, 90 mtr head in place of old pump. SITC of horizontally mounted centrifugal pump complete for delivery 180 ltr/min against a total head of 90 mtrs with three phase motor having speed of 2900 rpm with bronze impeller and coupling, base frame and AVM pads complete as required. The pump shall be provided with mechanical seal. (The existing pump is more than 15 years old). The job also includes dismantling the old pump, other allied works as per site requirement and as per directions of site Engineer. Make: Kirloskar, KSB, Mather & Platt. |
| 7 | Providing/fitting of new pumpset 90 mtr head, 1650 LPM. SITC of horizontally centrifugal end suction pump complete for delivery 1650 ltr/min against a total head of 90 mtrs with three phase motor with speed of 2900 rpm with bronze impeller and coupling, base frame and AVM pads complete as required. The pump shall be provided with mechanical seal. (The said pump is more than 15 years old and have outlived its useful life). The job also includes dismantling the old pump, other allied works as per site requirement and as per direction of site Engineer. Make: Kirloskar, KSB, Mather & Platt. |
| 8 | SITC of the AUTOMISATION CONTROL PANEL in place of old Panelin the main pumproom. The panel consist of a cubicle fabricated with sheet steel suitable for floor mount and for 3 phase, 4 wire, 50 hz system incorporating suitable isolating main switches, bus bars, relays, contactors, indication lamps of required amperage and sizes, fuses, instruments automatic isolator and auxillary switch including connectors complete as required for 1 main electric pump , 1 jockey pump and one spare setof the sameis required for the system. The job also includes dismantling the old Panel, other allied works as per site requirement and as per direction of site Engineer.Make: Schneider, Siemens, L&T, Legrand, ABB |
| 9 | Providing/ fitting of Glycerine filled Pressure gaugesin each floor so as to check main line pressure. Make: WIKA, Baumer, Akari, H Guru |
| 10 | SITC/ replacement of cast iron double flanged Butterfly valve ISI marked IS: 13095:2020 complete with rubber insertion, nuts, bolts, washers etc. of following sizes: 150 mm dia Make: KSB, Emerson, L&T, Zoloto |
| 11 | 100 mm dia Make: KSB, Emerson, L&T, Zoloto |
| 12 | 80 mm dia Make: KSB, Emerson, L&T, Zoloto |
| 13 | Repairing of Hose boxes with drums by means of denting, painting, welding and replacement of locking arrangement complete as required |
| 14 | Providing/ fitting of New First Aid Hose reel in place of damaged Hose reel. Make: KSB, Emerson, L&T, Zoloto |
| 15 | P/f of clear glass (min 5 mm thick) with sealing putty for hose boxes complete as required. |
| 16 | FIRE ALARAM SYSTEM SITC of Intelligent Analogue Optical Smoke Detector with base mounting with advanced optical chamber and smoke inlet design to provide resistance to entry of dust to provide immunity to false alarms, programmable multiple smoke sensitivity level setting, bi-directional in-built short circuit isolator to protect against cable faults, dual bi-colour LED's with 360o view of status, auto-addressable/electronically addressed, utilizes fully digital communication addressable protocol with high noise rejection. Approved by LPCB for EN 54-7 & EN 54-17 Make: - GST/Honeywell/Apollo/ Ceasefire/Halma |
| 17 | SITC of Intelligent Analogue Manual Call Point with resettable operating element, with in-built bidirectional short circuit isolator. Bi-Colour LED for local indication of device status, single action operation, reset to normal condition using special reset key, clearly visible alarm flag in the activated state. Approved by LCPB for EN 54-11 standard5dBm (3mW), enabled with 7 operating frequency channels for bi-directional wireless communication, operating frequency range 865MHz, IP 65 rated. Make:- GST/Honeywell/Apollo/ Ceasefire/Halma |
| 18 | SITC of Intelligent Sounder Interface Module allows to connect conventional Sounder or Sounder Beacon to addressable loop Beacon to addressable loop, with in-built short circuit isolator, allows for two stage alarm capability, addressed through auto and manual options. Approved by LPCB for EN 54-17 & EN 54-18 Make: - GST/Honeywell/Apollo/ Ceasefire/Halma |
| 19 | Supplying, installing, testing and commissioning Isolator Module for Isolating short/dewired/loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Make:- GST/Honeywell/Apollo/ Ceasefire/Halma |
| 20 | SITC of 1 Loop Analogue Addressable Fire Alarm Control Panel expandable up to 2 Loop, loop current 500mA maximum per loop, dual flash based microprocessor, supports to connect 240 addressable devices one each loop via fully digital communication protocol, equipped with a white backlit display (240x64 pixel resolution) graphical LCD Display with at least 6 lines of information, 200 fire zones (soft zones), fully programmable via alphanumeric keypad or configuration software, dedicated USB and RS-232 serial port for direct or PC connection. 5500 events storage, loop current 500 mA, panel shall be equipped with in-built multimeter for live monitoring of loop current, earth voltage, loop voltage etc., installer's logo application, can be networked to compatible addressable panels and repeater panels by adding a network card, features battery charger status and temperature, supports programmable cause/effect on outputs, panel housing meets IP30 ingress protection classification.Make: - GST/Honeywell/Apollo/Ceasefire/Halma |
| 21 | SITC of 10 Loop Analogue Addressable Fire Alarm Control Panel expandable up to 2 Loop, loop current 500mA maximum per loop, dual flash based microprocessor, supports to connect 240 addressable devices one each loop via fully digital communication protocol, equipped with a white backlit display (240x64 pixel resolution) graphical LCD Display with at least 6 lines of information, 200 fire zones (soft zones), fully programmable via alphanumeric keypad or configuration software, dedicated USB and RS-232 serial port for direct or PC connection. 5500 events storage, loop current 500 mA, panel shall be equipped with in-built multimeter for live monitoring of loop current, earth voltage, loop voltage etc., installer's logo application, can be networked to compatible addressable panels and repeater panels by adding a network card, features battery charger status and temperature, supports programmable cause/effect on outputs, panel housing meets IP30 ingress protection classification.Make: - GST/Honeywell/Apollo/ Ceasefire/Halma |
| 22 | Providing/fitting of control module loop powered as per site requirement Make: - GST/Honeywell/Apollo |
| 23 | Providing/laying of cat 6 outdoor cable 305 mtr/ bdl directly on surface / ceiling as per site requirement.Make: Honeywell/Caledonian/Notofire |
| 24 | Providing/laying of 2 core 1.5 sqmm copper armoured FRLS cable on surface/ceiling as per site requirement.Make: Polycab/Havells/KEI |
| 25 | Providing/laying of 4 core 1.5 sqmm copper armoured FRLS cable on surface/Ceiling as per site requirement. Make: Polycab/Havells/KEI |
| 26 | P/f of 2 KVA online Ups for Panel room as required with Battery Bank of minimum one hour backup and trolleys of standard make i.e Luminious, APC,Exide, Microtech, Su-Kam |
| 27 | Shifting of existing Fire Alarm Control Panels from different locations of GMCH, Jammu viz Emergency wing and other wards to the Fire Officer Room/Security Incharge Room/ Main Control Room of GMCH Jammu. Job includes the cable required for shifting and commissioning of the complete system. The job includes complete dismantling of the panel, safe disconnection of power supply and loops, and careful relocation without causing any damage to system components. The scope further includes extension of fire-resistant cables, re-termination of all circuits, and proper mounting of the panel at the new site. After relocation, the entire fire alarm system shall be reprogrammed, including configuration of all devices, zones, address loops, logic sequences, sounder circuits, and interface modules, ensuring integration with existing infrastructure. The job includes complete testing and commissioning including device-wise loop testing, simulation of fire and fault conditions, and full functionality checks. The technician ensures that each device communicates properly with the panel, clears any loop faults, adjusts sensitivity levels where applicable, and restores all event logs and system parameters. Reprogramming of the Fire Alarm Control Panel and all connected devices must be done as per OEM guidelines, using authorised configuration software/tools, including updating of addresses, zones, loop mapping and cause-and-effect logic. After completing the reprogramming, the entire fire alarm system is tested device-wise to confirm proper operation, communication, and alarm response. The complete job includes cost of dismantling and shifting the existing Fire Alarm Control Panel, cost of replacement of batteries, extension offire-resistant cables, re-termination and mounting at the new location, complete system reprogramming, and full testing and commissioning, required materials, consumables, labour charges, and taxes |
| 28 | Comprehensive Annual Maintenance Contract (CAMC) of complete system(Wet Hydrant System and Fire Alarm System)after DLP of 2 years. (Monthly Mock Drills during DLP Period are in scope of work).Comprehensive Annual Maintenance Contract (CAMC) for the complete fire protection infrastructure, including all components of the fire fighting system of Govt. Medical College & Hospital including College Block and outer Hydrant Points—main pumps, jockey pumps, diesel pumps, valves, hydrants, piping, supports, and associated accessories—as well as the fire alarm system comprising control panels, smoke/heat detectors, manual call points, alarm sounders, cabling, and interfaced devices. Consumables i.e M-oil, coolant, batteries, filters required for diesel pump are within the scope of contractor and M oil, filers to be changed after every 6 months. CAMC of smoke/heat detectors also include monthly cleaning of all the detectors for any dusty/carbon particles. The job includes conducting a monthly fire system drill to test the functionality of pumps, hydrants, alarms, and evacuation procedures. The drill covers activation of the fire alarm, operation of fire pumps and hydrantsand safe evacuation of occupants. Observations shall be recorded, deficiencies noted, and a report submitted with corrective recommendations to ensure the system and personnel remain fully prepared. The scope of work covers routine preventive maintenance, quarterly/half-yearly inspections, functional testing, calibration, cleaning, lubrication of moving components, minor repairs, replacement of worn-out or defective parts (including pump bearings, mechanical seals, gaskets, valves, sensors, relays, and detector modules), checking and maintaining pressure in jockey pump systems, and ensuring all pumps deliver the designed flow and head. For the fire alarm system, the scope includes checking panel programming, inspecting wiring and terminations, testing detectors and alarm devices, replacing batteries, fuses, and faulty modules, functional verification of all zones, and system reset/commissioning after maintenance. The contractor shall maintain detailed logbooks of all activities, prepare and submit inspection and maintenance reports, and provide emergency support as required. The CAMC shall include careful removal of dust, dirt, debris, and corrosion from the smoke detectors as per requirement, testing of pumps under load conditions, verification of pressure switches, control panel functionality, operation of NRVs/PRVs, and coordination with the authority having jurisdiction for statutory compliance. All labour, skilled and semi-skilled technicians, tools, tackles, consumables, replacement spares (excluding major pumps or panels unless specified), transportation, and applicable taxes are included to ensure that the fire protection and alarm systems remain fully operational and compliant throughout the contract period. |
| 29 | Providing and fixing of Emergency Acrylic LED Exit Sign Boards of double-sided type, fabricated from high-quality acrylic sheet with clear and uniform illumination using energy-efficient LEDs of size(12\\"x6\\"). The unit shall include an in-built rechargeable battery pack providing a backup of more than 45 minutes in case of power failure. The job includes supply of complete fixture with mounting brackets, and all associated accessories. The job also includes supply and fitting of electrical cable required for installation, Installation shall include fixing at the specified locations as per direction of Engineer in charge, making termination, testing of charging and discharging cycle, and commissioning of the unit. All labour, materials, tools and consumables required for the complete and satisfactory installation shall be included in the scope of work. Make: Honeywell / Prolite / Ceasefire/Crompton/legrand |
| 30 | PART B PORTABLE FIRE EXTINGUISHERS Providing & fixing of ISI marked (IS:15683),Capacity 4.5 kg portable fire extinguisher, carbon dioxide type flat base including valve, discharge hose of not less than 10 mm dia. complete in all respects including initial fill with CO2 gas confirming to IS:15683 and I.S 7285 filled to a filling ratio of not more than 0.667 and wall suspension bracket. The extinguishers should have: following specifications: 1. Service pressure and Maximum service pressure of extinguisher should be 70 bar and 155 bar respectively. 2. Discharge time should not less than 13 Secs. 3. Fire Extinguisher must have controllable discharge mechanism to provide flexibility of releasing extinguishing agent on targeted fire location. 4. Bulk range throw should be minimum 3.5Meters. 5.Applicable on Class B Fire. 6. Fire rating should be class B: 55 B. Certification 1. The current and valid BIS certification IS: 15683 2. The vessel should be PESO Approved. 3. The product should be CE marked & the cylinder should be certified to PED 2014/68/EU4. The product should be CE marked & assembly should be certified to PED 2014/68/EU5. The carbon dioxide gas shall conform to IS 15222 with latest amendment.6. Discharge valve shall be conform to all the requirement given in IS 3224:2002 or latest version thereof.7. The Co2 Cylinder shall be conform to all the requirement given in IS 7285:2004.8. The firm should submit the product performance test report from NABL accredited Labas per IS 15683.Extinguishers should have a minimum shelf life of 10 years. Certificate for the same to be enclosed are within the scope of work. |
| 31 | Providing and fixing of 6 Kg. MAP 90 ABC Powder type fire extinguishers manufactured and marked to Indian standard IS: 15683 and I.S. 7285 Suitable first aid appliance for fighting fires in Class A, B & C fire that is wood, textile, flammable liquids & gases. The extinguishers should have following specifications: Performance1. Each vessel needs to be checked for tensile strength upto 35 kgf/cm² and Manufacturer has to submit Hydrostatic pressure testing certificate for the same.2. Service pressure and Maximum service pressure of extinguisher should be 15bar and 17.2bar respectively.3. Minimum burst pressure of extinguisher shall not be less than 55bar and crack should not occur at welding upto 80bar. Actual burst pressure should be above than 110bar with no crack at welding seam. 4. In-house Helium Leak Detection Testing is must to ensure maintenance of Stored Pressure in the cylinder over a period of 5 years and provide certificate for the same.5. The fire extinguisher must have a Magnetic Pressure Gauge to enable the checking of pressure gauge’s correct working without dismantling or opening the cylinder.6. Discharge time should not less than 21 Seconds.7. Fire Extinguisher must have controllable discharge mechanism to provide flexibility of releasing extinguishing agent on targeted fire location.8. Bulk range throw should be minimum 4.5meters.9. As per IS: 15683, Fire rating should be for class A: 6A and class B:183B10. As per EN3-7, Fire rating should be for class A: 27A and class B:183B11. Applicable on Class A, B, C and electrically started Fire. Certification1. The current and valid BIS certification IS 15683:20182. The Product should be certified by any EN notified body as per EN 3-7, EN 3-8, EN 3-9.3. Dry Chemical powder used as extinguishing agent should be Mono Ammonium Phosphate (MAP) 90% concentration.4. The product should be CE marked & the cylinder should be certified to PED 2014/68/EU, ANNEXIII (MODULE H).5. The product should be CE marked & assembly should be certified to PED 2014/68/EU, ANNEXIII (MODULE H).6. The extinguisher should be pressurized using high grade Dry Nitrogen as per IS 1747 standard. OEM declaration should be submitted.7. The firm should submit the product performance test report from NABL accredited Labas per IS 15683.Extinguishers should have a minimum shelf life of 10 years. Certificate for the same to be enclosed are within the scope of work. |
| 32 | Portable All in One Fire Extinguisher Capacity 6Ltrs. Having following technical specifications:1. Fire extinguishing agent should be Fluorine Free Synthetic Foam. 2. The extinguisher should have a fire rating of 4A, 144B & 25F as per IS15683:2018. 3. The extinguisher should be tested for Class C fires 4. The extinguisher should be tested & certified for electrical non conductivity as per Dielectric test of IS 15683:2018. 5. The extinguisher should be CE marked & the cylinder should be certified to PED 2014/68/EU6. The product should be CE marked & assembly should be certified to PED 2014/68/EU Extinguishers should have a minimum shelf life of 10 years. Certificate for the same to be enclosed are within the scope of work. |
| 33 | Fire Extinguishers Wheeled low pressure compressed air Multimax Fluorine free foam system 45ltrs SS with cartridge(All Fire Extinguisher Compressed Air Trolley Type 45 Ltrs) having following technical specifications:1. Stored Pressure/Cartridge: Cartridge Type (Compressed Air Cylinder, MS, 6ltrs capacity) and Trolley mounted 2. Agent: Fluorine Free Synthetic Foam 3. Certification Standards: IS 16018, PED 4. CE Marked: Yes 5. Gross Weight (approx.:) 96 Kg 6. Net Contents (approx.): 45 Ltr7. Cylinder Material of construction: Stainless Steel (SS 304) 8. Approx. Height of Fire Ext.: 1180 mm 9. Discharge Mechanism: Squeeze Grip 10. Applicable on Fires: Class A,B, C, ESF 11. Fire Rating to EN3-7/IS16018: 15A, 233B 12. Can Construction: Deep Drawn & MIG Welded 13. Valve / Cap Construction: Machining 14. External Coating: Epoxy Polyester Powder 15. Working Pressure: 8 Bar 16. Throw (approx.): 14 m 17. Min. Discharge Time: 120 sec 18. Dia. Of Shell (OD): 74.5 mm 19. Operating Temperature: 5°C to 60° C 20. Hydrostatic Test Pressure: 30 BarThe extinguisher should be tested & certified for electrical non conductivity as per Dielectric test of IS 15683:2018. The extinguisher should be PED certified to PED 2014/68/EU & CE marked. Fire extinguishing agent should be Fluorine Free Synthetic Foam.Extinguishers should have a minimum shelf life of 10 years. Certificate for the same to be enclosed are within the scope of work. Total in Figures 23 0.0 23 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 08, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 17, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysSep 18, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents