Tender For S: R & M Of Various Distribution Transformers (Pddss2627100218) At Vaious Locations Of Ed Anantnag Under Ut Capex (Works List Enclosed):1. Renovation And Modernisation Of 630Kva Sub-Station At Dangarpora Anantnag (Atg-409).2. Renovation An
Tender Overview
Project Description
Tender for S: R & M Of Various Distribution Transformers (Pddss2627100218) At Vaious Locations Of Ed Anantnag Under Ut Capex (Works List Enclosed):1. Renovation And Modernisation Of 630Kva Sub-Station At Dangarpora Anantnag (Atg-409).2. Renovation And Modernisation Of 100Kva Sub-Station At Bhat Mohalla Nowathoo (Atg-226).3. Renovation And Modernisation Of 100Kva Sub-Station At Imoh (Atg-87).4. Renovation And Modernisation Of 250Kva Sub-Station At At Mirpora Chinigund.5. Renovation And Modernisation Of 250Kva Sub-Station At Peerpora Lower Munda.6. Renovation And Modernisation Of 63Kva Sub-Station At Reshipora Kapran.7. Renovation And Modernisation Of 100Kva Sub-Station At Lamni Tailwani.8. Renovation And Modernisation Of 100Kva Sub-Station At Poshnari.9. Renovation And Modernisation Of 63Kva Sub-Station At Kandikoot Khalhar.
BOQ
| Sl. No. | Item Description |
| 1 | Substation Part |
| 2 | Dismantling, Loading, Transportation / Carriage and reinstallation of 630 kVA,11/0.433kV, 3-phase Distribution Transformers (Complete Job ) |
| 3 | Dismantling, Loading, Transportation / Carriage and reinstallation of 250 kVA,11/0.433kV, 3-phase Distribution Transformers (Complete Job ) |
| 4 | Dismantling, Loading, Transportation / Carriage and reinstallation of 100 kVA,11/0.433kV, 3-phase Distribution Transformers (Complete Job ) |
| 5 | Dismantling, Loading, Transportation / Carriage and reinstallation of 63 kVA,11/0.433kV, 3-phase Distribution Transformers (Complete Job ) |
| 6 | Supply,installation,testing,commissioning of 11 kV, G.O AB Switch , 3-phase, 3-Pole, 200A |
| 7 | Supply,installation,testing,commissioning of 11 kV Horn Gap Fuse Set 3-Phase, 3-Pole, 200Amp. |
| 8 | Supply,installation,testing,commissioning of Gapless Surge Arrestor,9 kV,10 kA, LA with (polymer) housing, Station Type Heavy Type |
| 9 | Providing and Fixing of G.I.channel Iron ISMC100x50x6mm) with 50X8 mm back clamps without drilling/punching holes in the poles.. |
| 10 | Providing and Fixing of GI channel Iron ISMC 75x40x6 mm) with 50X8 mm back clamps without drilling/punching holes in the poles including transformer belt |
| 11 | Providing and fixing of Al thimbles of 185 sq mm |
| 12 | Providing and fixing of Angle Iron 45x45x5 mm 10 ft long duly painted for Transformer Belt |
| 13 | Supply, laying, testing and commissioning of PVC Cable 185 sq mm of standard make with ISI Insulation |
| 14 | Supplying and installation of sub station earthing by excavation of earth pit of dia 650mm and depth 3000mm, installation of earthing pipe of 40mm nominal bore and 4 mm wall thickness and length 2.5m long as per IS 1239. GI Strip for neutral earthing of size 25mm x 3 mm for connection of Transformer Body, GO Set and Lightning Arrestor as per IS 2629/85, GI Nuts and Bolts, refilled with earth enhancement materials and earth chamber made of brick messonary with RCC Slab cover |
| 15 | Supply,erection, testing, commissioning including Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 9 Mtr. Long ST Poles (410, SP-33) with pit excavation, refilling the pit with soil, boulders. |
| 16 | Supply, Laying Testing and commissioning of PVC Cable 400 mm sq. of standard make with ISI Insulation. |
| 17 | Supply, Laying Testing and commissioning of PVC Cable 240 mm sq. of standard make with ISI Insulation. |
| 18 | Supply, Laying Testing and commissioning of PVC Cable 120 mm sq. of standard make with ISI Insulation. |
| 19 | Supplying and fixing of Galvanized Nuts and Bolts. |
| 20 | Supply and Painting of each Pole 1 coat red oxide paint and 2 or more coats of aluminium paint so as to obtain even finish including Pole Marking ( 6inch x 6 inch in yellow paint and 1 inch Black Marking) |
| 21 | Providing and fixing of Danger Plates. |
| 22 | Providing and fixing of Anticlimbimg devices with Clamps. |
| 23 | Providing and laying of Cement bottoming 1:2:4 mix as per REC standards 0.48 cum for 9 mtr poles muffing 20 cm above ground level ,including plaster and curing of concrete. |
| 24 | Providing & fixing of Earthing Complete for Poles by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm |
| 25 | Providing and Fixing of 11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 26 | Supplying, installation, testing, and commissioning of LT Distribution Box suitable for 100 kVA DTR, 160 Amp MCCB (3P, 16 kA) for incomer and 2 No.s 100 Amp MCCB (3P, 16/10 kA) for outgoing circuits. |
| 27 | Supply and fixing of LT Fuse Set |
| 28 | Supplying, installation, testing, and commissioning of LT Distribution Box suitable for 63 kVA DTR, 100 Amp MCCB (3P, 16 kA) for incomer and 1 No. 100 Amp MCCB (3P, 16 kA) and 1 No. 63 Amp MCCB (3P, 16 kA) for outgoing circuits. |
| 29 | Supplying, installation, testing, and commissioning of LT Distribution Box suitable for 630 kVA DTR, 1000 Amp MCCB (3P, 36 kA) for incomer and 1 No. 250 Amp MCCB (3P, 25 kA) and 1 No. 200 Amp MCCB (3P, 16 kA) for outgoing circuits. |
| 30 | HT/LT Part |
| 31 | Supply,Laying,testing,commissioning including Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, Laying, stringing and binding of 30 sq mm ACSR (WEASEL) conductor including joints with PG clamps of required size. |
| 32 | Supply,Laying,testing,commissioning including Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, Laying, stringing and binding of 50 sq mm ACSR (RABBIT) conductor including joints with PG clamps of required size. |
| 33 | Providing & fixing of Earthing Complete for Poles by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm |
| 34 | Supplying and fixing of Galvanized Nuts and Bolts. |
| 35 | Providing and fixing of LT Shackles with Mukhi Clamps complete with bolts and fittings. |
| 36 | Providing and laying of Cement bottoming 1:2:4 mix as per REC standards 0.40 cum for 8 mtr poles muffing 20 cm above ground level ,including plaster and curing of concrete. |
| 37 | Providing and fixing of Danger Plates. |
| 38 | Providing and Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 39 | Supply,erection, testing, commissioning including Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 8 Mtr. Long ST Poles (410, SP-15) with pit excavation, refilling the pit with soil, boulders. |
| 40 | Providing and fixing of GI Channel Iron V shaped X arms with F top complete and 2 No angle Iron braces with fittings complete (21 Kg each) |
| 41 | Providing and fixing of Anticlimbimg devices with Clamps. |
| 42 | Supply and Painting of each Pole 1 coat red oxide paint and 2 or more coats of aluminium paint so as to obtain even finish including Pole Marking ( 6inch x 6 inch in yellow paint and 1 inch Black Marking) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents