Tender for Maintenance and repair Of Internal Wiring Of Various Buildings Csmc At Zone No.05.

BOQ

Name of Work:- M and R of internal wiring of Various buildings CSMC At zone no.05.
Sl. No. Item Description
1Point wiring for light/fan/bell in 20 mm HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire with flush type switch and required accessories as per specification no. WG-PW/SW DSR No. 1-7-3
2Point wiring for light/bell concealed type in min 20 mm HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification no. WG-PW/CW DSR No.1-7-5
3Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification no. WG-PW/SW DSR NO. 1-7-18
4Wiring for plug on board with switch socket surface/concealed type, copperwiring and earthing and with modular accessories as per specification no. WG- PW/CW DSR No. 1-7-25
5Supplying 230/250 Volts, 50Hz, evaporative air cooler (desert cooler) having normal cooling capacity of 50 cu.m per minute, with 12\\" exhaust, min 40 to 55 litres water capacity tank with galvanised steel sheet with Grade 350 minimum, leak or drip free, front grill shall be made of non-corrosive material, circular opening shall be more than fan sweep but not exceeding more than 25mm, Filter pads shall be made of wood wool or any other substitute placed in non corrosive wire mesh and tightened at places with side panels, noise level should not be more than 65 dBA at 1 m distance, 3 core copper cable minimum 2 m length & metal casing of the electrical components, metal frame or chassis of cooler cabinet and all exposed metallic parts, shall be provided with proper earthing complete as per specification No. AP-ACR/DAC DSR NO. 3-4-1
6Supplying and erecting LED square / circular Max. 14 W down lighter / Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 1500 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs at L70B50 including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with minimum 2 years warranty as per specification No. FG-IDF/LED. DSR NO.2-+1-4
7Supplying and erecting LED Panel Light (600mm X 600mm) Max. 30 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min. 3600 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs at L70B50 including driver, having mounting arrangement with boardfor surface type or spring loaded mounting clips complete with minimum 2 years warranty as per specification No. FG-IDF/LED. DSR NO. 2-1-7
8Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL DSR NO .7-1-28
9Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 16 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL DSR NO. 7-1-29
10Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 25 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL DSR NO.7-1-30
11Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete. DSR No. 1-6-1
12Supplying and erecting ISI mark modular type switch 16A duly erected on provided plate and box with wiring connections complete. DSR No. 1-6-2
13Supplying and erecting modular type 3 pin 6A multi socketwith safety shutter on provided plate and box with wiring connections complete. DSR NO. 1-6-10
14Supplying and erecting modular type3pin6/16Amulti socket with safety shutter on provided plate and box with wiring connections complete. DSR NO. 1-6-11
15Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW DSR No. 1-3-1
16Supplying and erecting PVC trunking (PVCcasing-n-capping) of size 32mm with accessories on wall/ceiling as per specification no. WG-MA/CON. DSR No. 1-2-8
17Supplying and erecting mains with WP 2 x 4 sq. mm. 1.1 kV grade aluminium PVC insulated and PVC sheathed wires on G.I. bearer wire no. 8 SWG complete erected with required size of porcelain reel insulators and 16 SWG G.I. binding wire. DSR NO. 1-4-2
18Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW DSR No. 1-3-2
19Supplying and erecting anodized aluminium light LED fitting (4 feet) Max.22W with high transitivity diffuser with system lumens output of Min.2200 lumens , min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%, THD<20%, p.f. >0.95, operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs at L70B50 including driver with end caps on provided PVC Block/wooded board with minimum 2 years warranty as per specification No. FG-IDF/LED. DSR No. 2-1-18
20Supplying and erecting modular type (two module) electronic dimmer 600/650W on provided plate and box with wiring connections complet DSR No. 1-6-21
21Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module complete. DSR No. 1-6-28
22Supplying and erecting PVC Surfacemodular switch box with double mounting plate for 16/18 module complete. DSR No. 1-6-33
23Supplying and erecting PVC Surface modular switch box with double mounting plate for 6 module complete. DSR No. 1-6-30
24Supplying and erecting PVC Surface modular switch box with double mounting plate for 12 module complete. DSR No. 1-6-32
25Supplying and erecting regular/ standard model ceiling fan of 900 /1050 mm. sweep complete erected in position as per specification no. FG-FN/CF. DSR No. 2-9-2
26Supplying and erecting cabin fan of A.C. 230 V. 50 cycles 400 mm. sweep complete with necessary brackets for fixing cabin fans, wire etc. DSR No. 2-9-12
27Supplying and erecting street light Wall bracket made from 40 mm. dia ‘B’ class G.I. pipe 1.2 m in total length complete as perspecification no. FG-BKT/WB. DSR No. 2-6-4
28Supplying and erecting integrated LED street light fitting 40 to 50W IP65 &IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 4400 Lumens, min. efficacy of 110 lumen/W,CRI>70, CCT upto 6500K,THD<10%, p.f. >0.95, operating range of 140-270V,inbuilt surge protection of 10 kV, Life class of 50,000 Hrs at L70B50 includingdriver complete with minimum 2 Years warranty as per specification No. FG-ODF/SL. DSR No. 2-3-4
29Supplying & erecting 10-12W, 230V integral type LED Lamp suitable for B-22/E-27 base as per specification no. FG-LP DSR No. 2-7-5
30Supplying and erecting ceiling rose/ batten holder/ slanting holder/ hanging cord switch/ hanging bell push/ pendant holder bakelite base 6A erectedon filled polypropylene board or polished double wooden block/ PVC junction box. DSR No. 1-5-5
31Supplying, erecting & marking SP MCB 6A to 32A, C-series with rated short - circuitbreaking capacity (Icn) 10kA in provided distribution board as per specification no.SW-MCB DSR No. 5-3-2
32Supplying, erecting & marking DP MCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB DSR No. 5-3-7
33Supplying, erecting and marking double pole isolator only switch version of miniaturecircuit breaker of 40A with required wiring connections and lugs etc. in provide distribution board DSR No. 5-3-14
34Supplying, erecting and marking four pole isolators only switch version of miniature circuit breakers of 40A in provided distribution board. DSR No. 5-3-18
35Providing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia.G.l. Rodcomplete with all materials as per specification no. EA-EP DSR No. 9-1-4
36Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB DSR No. 5-4-9
37Supplying and erecting exhaust fan heavy duty 230 V, A.C. 50 cycles 375/380 mm. 900 RPM complete erected in position as per specification no. FG-FN/EXF DSR No. 2-9-14
38Supplying & fixing anchor type fastener fan hook, with 2 nos. of 10 mm dia x 75 mm long with necessary materials for ceiling fan. DSR NO 2-10-2
39Supplying and erecting ‘B’ grade G.I. pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire. DSR NO. 2-10-6
40Supplying and erecting modular type blanking plate one module ,on provided plate & box. DSR NO.1-6-24
41Supplying and erecting 25mm dia. corrugated flexible polypropylene conduit DSR NO 1-2-2
42Supplying and erecting HMSPVC conduit 25mm dia.with PVC accessorieson wall /ceiling as per specification no. WG-MA/CON. DSR NO. 1-2-4
43Supplying and erecting mains with WP 4 x 4 sq. mm. 1.1kV. grade aluminium PVC insulated and PVC sheathed wires on G.I. bearer wire no. 8 SWG complete erected with required size of porcelain reel insulators and 16 SWG G.I. binding wire. DSR NO.1-4-6
44Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. DSR NO. 7-6-9
45Providing & erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 2.5 to 16 sq mm., with necessary material as per specification No. CB-JT/LT DSR NO.7-4-1
46Supplyingandlaying(includingexcavationofsuitablewidth&depthupto90cm) 75mm outsidedia. doublewall corrugated pipes (DWC)of HDPEfor enclosing cable below ground/road surface, complete. DSR NO. 7-6-10
47Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mA Lithium ion Battery with charging time of 8-10 Hours and backup time ofMin. 3 Hrs with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20 % having useful life of minimum 25000 Hrs with over heat protection with minimum 2 years as per specification No. FG-IDF/LED. DSR NO.2-1-22
48Supplying and erecting integrated LED flood light fitting Max. 100W IP65 & IK07 class having pressure die-cast aluminium housing, having system lumens output of Min. 12000 Lumens, min. efficacy of 120 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 140-270V, inbuilt surge protection of 4 kV, Life class of 50,000 Hrs at L70B50 including driver with U shaped bracket with minimum 2 Years warranty as per specification No. FGODF/ FL. DSR NO.2-3-15
49Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 4 ways/phase (12 poles), with door, 1.2mm thickness, surface/flush mounted, IP 43protection on provided iron/GI frame (horizontal busbar type) as per specification no. SW-MCBDB. DSR NO.5-4-1
50Providing & erecting 3 Pole MCCB, 415V, up to 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixedmagnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB DSR NO.5-5-1 Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57402871
AUTHORITY Local Bodies
TENDER VALUE 5.98 Lakhs
LAST DATE 16-09-2026
Authority
Authority Name Municipal Corporation Aurangabad
Work Description Tender for Maintenance and repair Of Internal Wiring Of Various Buildings Csmc At Zone No.05.
Basic Detail
Tender No CSMC/EE/Electrical/2026/89
Bidding Type Tender
Location
City Aurangabad
State Maharashtra
Key Dates
Publish Date 08 Sep 2026
Submission Date 16 Sep 2026
Open Date 18 Sep 2026
Finance
Tender Value 5.98 Lakhs
Tender Fee 600
EMD 5990
Exemption Not Available
Document List
5b8194e8-2dbe-4be0-8180-51003cf62441.html
BOQ_2286040.xls
Tendernotice_1 (75).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 08, 2026
11:30 IST

Tender Published

Tender notice published.

Today
Sep 16, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 8 days
Sep 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 10 days

Tender Documents

Download All (ZIP) ↓
html

5b8194e8-2dbe-4be0-8180-51003cf62441.html

xls

BOQ_2286040.xls

pdf

Tendernotice_1 (75).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders