| Sl. No. | Item Description |
| 1 | Supply, laying and testing cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 sq mm x 3.5 core |
| 2 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded Copper conductor of size 50 sq mm x 3.5 core |
| 3 | Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in hard / dense soil complete all as specified and directed. |
| 4 | Supplying and laying of following size DWC HDPE pipe of 100 mm dia for cable protection ISI marked along with all accessories conforming to IS 16205, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 5 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed. |
| 6 | Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 7 | Supply, install, test and commissioning of servo controlled Voltage stabiliser for automatic operation, three phase naturally oil cooled out door type with latest amendments and digital Volt meter, Ammeter and Frequency meter suitable CT's for ammeter, Voltage adjustment for increment and decrement etc with the following specifications:(a) Rated Capacity 100 KVA Out door type with IP-55 grade of protection.(b) System 03 Phase , 50Hz, AC Supply.(c) Input Voltage 360V to 480V(d) Out put voltage Set 415V(+/-)1.0% speed of correction 6V/Sec(e) Operating Line Frequency : 50 Hz (f) Type of Cooling Naturally Oil Cooled(g) Type of System Unbalanced(h) Operating Temp 20 to 50⁰ C |
| 8 | (i) High/Low Voltage cut off feature(j) Protection Under Voltage, Over Voltage, Phase Failure, Over Load/Short Circuit protections.(k) Efficiency > 98%and shall be free from wave form distortions(l) High/Low Voltage cut off (m) Auto/Manual Switch(n) Two digital Volt meters (For Incoming and out going) with inbuilt selector switch(o) One digital Ammeter(inbuilt selector switch) with suitable CTs of Class 1.0(p) Bypass arrangement in case of emergency (q) End Terminations with suitable bus bar for terminating 3.5 Core x 95 Sqmm with the end termination box along with suitable glands for cables complete.(r) Wheels for unit directional movement(s) First Filling of oil in servo stabiliser is included.(t) Incl.1:3:6 PCC foundation 1800 x 1400 x 20 mm thick |
| 9 | M&L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 32×6mm 7.5 meter by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion all as specified and directed by Engr-in-ChargeNote: GI strip more than 7.5m shall be measured and paid separately under relevant item of the work |
| 10 | Supply and fix 25 x 4 mm galvanised iron strip for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required |
| 11 | Supply, installation, testing and commissioning of 80 kVA, three phase, four wire, true online double-conversion UPS system, complete with high frequency IGBT based rectifier and inverter, Space Vector Modulation technology, static bypass arrangement, manual maintenance bypass, inbuilt output isolation transformer, advanced battery management system, phase sequence protection/correction, forced cooling by internal fans and all accessories required for satisfactory operation.UPS shall be suitable for 400/415 V AC, 3Ø + N, 50 Hz input and output, with input voltage tolerance of ±15%, output voltage regulation within ±1%, output frequency regulation of ±0.1 Hz and output voltage THD not exceeding 1.5% for linear load and 5% for non-linear load. UPS shall be capable of handling overload of 110% for 60 minutes, 125% for 10 minutes and 150% for 1 minute and shall have AC/AC efficiency up to 93% at full load. |
| 12 | Supply and installation of Amaron Quanta/ Exide make 12 V, 150 AH SMF batteries, suitable for providing 30 minutes backup time for the above 80 kVA UPS system, complete with necessary interconnections. |
| 13 | Supply and installation of MS rack holding 150AH 32 number of batteries along with interconnecting cables and all necessary accessories required for proper installation and connection of the battery bank to the UPS system, complete in all respects. |
| 14 | Supply, installing, testing and commissioning, factory made , outdoor type LT panel board, approved manufacturer weather, vermin proof, cubical type, platform mounted, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated bus bar 400 Amps rating in 3 Phase and neutral fashion, the panel should be dust proof and made out of 3.15mm thick CRCA mild steel sheet with 50x50x6mm angle iron frame with necessary earth work excavation incl PCC Foundation of Cement Concrete 1:3:6 (20mm Graded Stone Aggregate), hinged doors, front and rear opening and locking arrangement, Mild Steel Angle Iron Frame and 600 mm above the Normal Ground and duly powder coated on the out side and inside, cable glands and lugs for incoming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories |
| 15 | INCOMING 1. RYB Phase Indication Lamps with fuse set - 1No's2. 3-Phase LED Ammeter - 1 No's3. 3-Phase LED Voltmeter - 1 No's4. 4 Pole 160A 36KA Micro processor MCCB - 2 No's5. 4 Pole, 160 A Motorized changeover with Inbuilt micro-processor based ATS controllerOUTGOING:6. 63A 16 KA MCCB (Outgoing feeder) - 4 No's |
| 16 | Supply and Fix 4 pole off load change over of capacity 200 amps with enclosure. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 08, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysOct 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 27 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender