Housing Urban and Rular Development Government Departments Closing in 7 days TDR #57395668

Tender For Electrification, Fire Fighting & Allied Work For Examination Hall & Multiskill Development Centre At Govt Degree College Doiwala (Dehradun)

Issued by Government Departments · Dehradun, Uttarakhand
Tender Value
1.52 Crore
Estimated cost
Bid Submission
21 Sep 2026
7 days left
EMD
3.04 Lakhs
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Dehradun → Uttarakhand
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Electrification, Fire Fighting & Allied Work For Examination Hall & Multiskill Development Centre At Govt Degree College Doiwala (Dehradun)

BOQ

Name of Work:- Electrification, Fire Fighting & Allied work for Examination Hall & Multiskill Development Centre at Govt Degree College Doiwala (Dehradun)
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
2Group C
3Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
4Group C
5Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cableetc. as required.
6Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
7Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
82 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire.
92 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire.
102 x 10 sq.mm. + 1 x 6 sq.mm. Earth wire
114 x 6 sq.mm. + 2 x 6 sq.mm. Earth wire
124 x 10 sq.mm. + 2 x 6 sq.mm. Earth wire
13Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.(20)
142 Pair
15Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.(40)
16Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
17Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
185/6 A switch
192 way 5/6 A switch
203 pin 5/6 A socket outlet
21Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
22Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
231 or 2 Module (75 mmX75 mm)
243 Module (100 mmX75 mm)
254 Module (125 mmX75 mm)
266 Module (200 mmX75 mm)
278 Module (125 mmX125 mm)
2812 Module (200 mmX150 mm)
29Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
301 or 2 Module
313 Module
324 Module
336 Module
348 Module
3512 Module
36Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
37Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
38Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
39Installation, testing and commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/ LED lamps per fitting, complete with all accessories including connections etc. as required.
40Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
41Providing and fixing plain 16/0.20mm (0.50sqmm) twin flat flexible, FRLS PVC insulated, copper cable, in PVC sleeve of suitable size on the floor/ wall, or side of the table/ door etc. as required.
42Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc., including supplying and fixing ball and socket arrangement, 2 Nos. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
43Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
44Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed steel/ PVC conduit as required.
451 run of cable
462 run of cable
473 run of cable
48Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
49Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required
50Supplying and fixing PVC batten/ angle holder including connections etc. as required
51Supplying and fixing following way prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FRLS PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/ Isolator)
524 way (4 + 12), Double door
536 way (4 + 18), Double door
548 way (4 + 24), Double door
55Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
56Single pole
57Single pole and neutral
58Triple pole and neutral
59Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
60Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
61Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
62Supplying and Fixing Following way, Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
636 Way (4 + 18), Double Door
648 Way (4 + 24), Double Door
65Supplying and fixing following way, Single Pole and Neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
668 way , Double door
6712 way , Double door
68Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
6940 Amps
7063 Amps
71Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
7240 Amps
73Supplying and Fixing Following Modular Switch/ Socket on The Existing Modular plate & Switch Box including connections But Excluding Modular Plate etc. as required.
74Telephone Socket outlet
75TV antenna socket outlet
76Supply &Installation of Rj45 Cat 6 Information outlet
77Supply of Surface Mounted Energy Efficient, LED Luminaires 12W LED DOWN LIGHT (Round/Square) complete with with all accessories as required.
78Supply of Surface Mounted Energy Efficient, LED Luminaires 18W LED Down Light Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc.as required. As Per LUKER Cool Day Light Aluminium Circular LED surface ceiling Light
79Supply of LED Luminaires BATTEN 20W LED Tube Light complete with with all accessories as required. As Per havells 20 Watt/2000 lumen 5700 K LED Tubelight
80Supply of LED Luminaires Batten 36 Watt led tubelight suspension of material Aluminium with PMMA Diffuser of IP20. Supply all complete driver circuit for connection.
81Supply of Bulk Head Luminaire, heat resistant Glass cover . suitable for 10W to 15W LED
82Supply of 9W LED BULB with all accessories as required. As Per JAILUX Self Ballasted LED Lamps for General Lighting Service 9 Watts 3 Star
83supply of wall light (down lighter )complete in 18 watt
84Supply of Linear & Compact 10W Mirror Light with Decorative Grey Caps, Polycarbonate Body & Ribbed Opal Diffuser. (Technical Data - System power 10W, CRI ≥80, Power Factor ≥0.95, System Luminous Efficacy ≥100).
85Supply of 40W LED Recessed Light Fixture Aesthetically designed 2x2 LED Flat panel light which provides soft-light and glare free symmetrical illumination complete with all accessories as required.
86Supply of Following sweep exhaust fan with guard suitable operation on single phase 230 V, 50Hz. AC Supply, with lowers /shutters in the existing opening.
87300 mm Sweep 900 rpm
88Supply, installation, testing and commissioning of Interactive Flat Panel Display, minimum 75 inch diagonal size, 4K UHD resolution, multi-touch capability, inbuilt Android operating system, inbuilt speakers, necessary input/output ports (HDMI, USB, LAN etc.), complete with OEM wall mounting bracket, standard accessories and firmware/software,
89Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
90Installation, testing and commissioning of pre-wired, fluorescent fitting /compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as Required.
91Installation of Exhaust fan in the existing opening, including making good the damage, Connection, Testing, Commissioning etc. as Required.
92Upto 450 mm sweep
93Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes.
94Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing
95Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts, 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
96INCOMER : 160 AMP FP MCCB
97BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp.
98The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature.
99OUT GOINGS :
1006 No 63 AMP 4P MCB (DB's)
1013 No 40 AMP DP MCB (DB's)
1021 No 63 AMP 4P MCB (Lift)
10310 No 40 AMP 4P MCB (3 Phase Points)
1042 No 63 AMP 4P MCB (Spare)
1052 No 40 AMP DP MCB (Spare)
106complete panel as above and complete
107Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code
1083.5 C X 50 Sq.mm Al. XLPE arm.
1093.5 C X 95 Sq.mm Al. XLPE arm.
1103.5 C X 120 Sq.mm Al. XLPE arm.
1113.5 C X 185 Sq.mm Al. XLPE arm.
1124.4 C X 10 Sq.mm Al. XLPE arm.
113Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
114Supply, Install and commissing of UPS 30KVA/30KW ,High performance UPS, fully digitaland DSP with following key features,Supplly installation & commissioning of microprocessor controlled true online doubleconversion 3phase input 3 phase output 400V ,UPS consisting of following,• IGBT Rectifier• Input PF >0.99 and iTHD<3%• Wide input voltage range +20 to -15% andwide frequency 45Hz. To 65Hz.• Rated at Output PF 1( 30KVA @ 30KW)• Inbuilt dust filters.• Inbuilt Phase sequence corrector.With EXIDE (12V-65 AH-32 Nos ) SMF batteriesfor 30 minutes backup ..Battery Racks, Interlinks, DC Cable & DCBreakerNumeric LEGRAND UPS 30KVA/30KW ,Model,High performance UPS, fully digitaland DSP with following key features,Supplly installation & commissioning of microprocessor controlled true online doubleconversion 3phase input 3 phase output 400V ,UPS consisting of following,• IGBT Rectifier
115• Input PF >0.99 and iTHD<3%• Wide input voltage range +20 to -15% andwide frequency 45Hz. To 65Hz.• Rated at Output PF 1( 30KVA @ 30KW)• Inbuilt dust filters.• Inbuilt Phase sequence corrector.With (12V-65 AH-32 Nos ) SMF batteriesfor 30 minutes backup ..Battery Racks, Interlinks, DC Cable & DCBreaker
116Supply or fabrication, installation and commissioning of Indoor Panel Board with Switch gear ). Send all necessary like 400 Amp FP MCCB 36 ka, 250 Amp FP MCCB 36 ka, 62 AMP & 32 Amp MCB etc.
117Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required.
118Above 35 sq. mm and upto 95 sq. mm
119Above 95 sq. mm and upto 185 sq. mm
120Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.
1213½ X 50 sq. mm (35 mm)
1223½ X 95 sq. mm (95 mm)
1233½ X 120 sq. mm (120 mm)
1243½ X 185 sq. mm (185 mm)
125Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
126Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
127Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
128Supplying, installation, testing and commissioning of Silent Type DG Sets of 58.5 KVA confirming to latest CPCBIV+ Emission norms.High water temperature Low lube oil pressure Emergency stop push button outside the enclosure.EGRCold Start feature (Optional) Specially designed Standard Control Panel is mounted inside enclosure itself. In-built draw in type fuel tank of suitable capacity. With UV resistant powder coating, can withstand extreme environments The walls of the enclosure are insulated with the fire-retardant & noise absorbent foam/rockwool so asto comply with the noise level of 75 dB(A) at distance of 1 mtr. in open free field environment as perISO 8528 part 10 specified by ministry of Environment & Forest.Fluid drains for lube oil and fuel.
129A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS: 1520(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.(D) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads.450 Lpm at 35m Head
130Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required:INCOMING250A, 50kA 4 Pole MCCB, Ics=100% Icu ratingDigital Voltmeter 0-500V with selector switch Digital Ammeter (0-250 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lampsSet of Copper Bus Bar 300A
131OUTGOING(Note: All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)MAIN FIRE PUMP125 Α, 50ΚΑ ΤPN MCCB, Ics 100% icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.JOCKEY PUMP63 Α, 50ΚΑ ΤPN MCCB, Ics 100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing, type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operationDIESEL ENGINE CONTROL
132Control for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/Low Lub. Oil pressure, High Water Temp and Engine on indicationBattery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine
133SYSTEM CONTROLLERDesigning. Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification
134Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.
135150 mm dia
136Providing, laying, testing&commissioningof 'C' class heavy dutyMSpipe conforming to IS3589/IS123 includingWelding, fittings like elbows, tees, flanges, tapers,nutsbolts,gasketsetc.andfixingthepipeonthe wall/ceiling with suitable clamp/support frame andpaintingwithtwoormorecoatsofsyntheticenamelpaint of required shade complete as required :
13725MM DIA
13880 MM DIA
139100 mm. Dia
140150 mm. Dia
141Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel couplingof63mmdiawithcast ironwheel ISImarked conforming to IS 5290 (Type-A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel
142Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as requiredSingle headed stainless steel
143Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 80 mm dia
144Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 100 mm dia
145Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 150 mm dia
146Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required: 100 mm dia
147Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required: 150 mm dia
148Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
149Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
15080mm dia
151100 mm dia
152150mm dia
153Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6mm thickstainlesssteel,Grade304, sheetwith3mmdia holes with stainless steel flange
154100mm dia
155150mm dia
156Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel (Grade 304)
157Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 METER
158Supplying&fixing63mmdiagunmetalshortbranch pipewith20mmnominal internaldiametersize nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required
159Stainless Steel (Grade 304)
160Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required:4 way-150 mm dia M.S. Pipe
161Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
162Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
163Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 150mm dia
164Providing, fixing, testing & commissioning ofinstallation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 150mm dia
165Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Circular tank
166Supplying, installation, testing & commissioning of heat detector operating at 54°C/57°C with rate of rise cum fixed tempreature (dual thermistor) type with mounting base complete with all connection etc. as required.
167Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required.
168Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
169Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered complete with all connections, interconnections as required.6 zone
170Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required
171Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required
172Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
173Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.speaker cable Single pair, 2-core, 1.5 sqmm
174Providing and fixing of 9 liter GALVANIZED MILD STEELFIRE BUCKET (Fire suppression handtools) complete in all aspects as per directions of Engineer-in-Charge
175Providing and fixing of AAAG FRP Double Door with lockingarrangment(4) Fire Hose Cabinet,Warranty 1 Year AAAG (FRP HOSE BOX (900X600X250) WITHSTAND MOUNTED) complete in all aspects as per directions of Engineer-in-Charge
176Providing and fixing of Portable Fire Extinguishers as per IS15683 (2018) Low PressureExtinguisher (Service Pressure ≤19bar) Powder Based (as per IS 4308 )Class -A : ABC complete in all aspects as per directions of Engineer-in-Charge
177Supply and fixing of pressure gauge on MS pipe line.
178Supply and fixing of starter panel with suitable starter for terrace pump complete as required with auto manual selector switch.
179Providing and fixing of Fireman axe, Length 50-60 cm complete in all aspects as per directions of Engineer-in-Charge
180LAN work
181Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required
1821 or 2 Module (75mmX75mm)
183RJ-45 Data Socket outlet
184Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.1 run of cable
185Supply Installation testing and commissioning of 24 port L2 UnManaged switch having port density 24 No.of 10/100/1000Mbps/4 1 G SFP Ports.
186SITC of UTP CAT 6 UTP Patch Cord 1 Mtr.
187SITC of UTP CAT 6 UTP Patch Cord 3 Mtr.
188Supply and Fixing of 6 U wall mounting Networking Rack
189Supply Punching and Fixing of 24 ports Patch Panel
190Supply,Laying of UNI Tube Single Mode 6 F Armored Fiber Optic Cable
191Labour chagres for optical fiber cable splicing and jointing with Termination.
192Supply and Fixing of 12F port LIU box fully Loaded
193Supply and Fixing of 12F port LIU box fully Loaded.
194Supply and Fixing of Single Mode Patch cord SC to LC 3mtr.
195Supply Installations Testing and Commissioning of Gigabite Uplink 8/10/100 Mbps 8 PORT POE Switch Complete in all respect.
196Supply, Installation, Testing & Commissioning of 1200 Gigabit WiFi Router.
197Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required
19825 mm
199Supply Installation Testing and commissioning of 2 MP, IP Based indoor Dome Camera. (1920x1080 pixel) or better , IR illumination 20-30 Mts, focus mode- auto,Vandal Resistant Housing (IK 10),Day/Night Capable,Built-in microphone Complete in all respect.
200Supply Installation Testing and commissioning of 2 MP, IP Based out door type Bullet Camera. (1920x1080 pixel) or better , IR illumination 20-30 Mts, focus mode- auto,Vandal Resistant Housing (IK 10),Day/Night Capable,Built-in microphone Complete in all respect.
201Supply Installations Testing and Commissioning of 16 channels NVR with 4 Number of Hard Disks supported & Maximum Recording Resolution supported4K (3840 × 2160) Complete in all respect
2024 TB HDD servilance storage drive
203Supply Installations Testing and Commissioning of 43 \\" 4K ultra HD Smart /Google Display, HDMI Port, Compon+B193ent Video Inputs, 1 Digital Audio Out, Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57395668
AUTHORITY Government Departments
TENDER VALUE 1.52 Crore
LAST DATE 21-09-2026
Authority
Authority Name Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited
Work Description Tender for Electrification, Fire Fighting & Allied Work For Examination Hall & Multiskill Development Centre At Govt Degree College Doiwala (Dehradun)
Basic Detail
Tender No 1370/BRIDCUL/1088/26 Dated 27.08.2026
Bidding Type Tender
Location
City Dehradun
State Uttarakhand
Key Dates
Publish Date 07 Sep 2026
Submission Date 21 Sep 2026
Open Date 21 Sep 2026
Finance
Tender Value 1.52 Crore
Tender Fee 5900
EMD 3.04 Lakhs
Exemption Not Available
Document List
BOQ_117769.xls
e52813c1-44a3-4d4b-878e-c58a13eee819.html
sbdeletdoiwalaf.pdf
Tendernotice_1 (24).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 07, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 21, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 7 days
Sep 21, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 7 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_117769.xls

html

e52813c1-44a3-4d4b-878e-c58a13eee819.html

pdf

sbdeletdoiwalaf.pdf

pdf

Tendernotice_1 (24).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail