Tender For Electrical Panel Up-Gradation Of Opd Building, Old Hospital Building, Mcc Panel Of Bmt Hvac, And Replacement Of Main Cables Of Chillers At Dr. B. Borooah Cancer Institute, Guwahati- 16.

Issued by Boards / Undertakings / PSU · Kamrup Metro, Assam
Tender Value
34.30 Lakhs
Estimated cost
Bid Submission
26 Sep 2026
12 days left
EMD
80956
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Kamrup Metro → Assam
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Electrical Panel Up-Gradation Of Opd Building, Old Hospital Building, Mcc Panel Of Bmt Hvac, And Replacement Of Main Cables Of Chillers At Dr. B. Borooah Cancer Institute, Guwahati- 16.

BOQ

Name of Work:- Electrical Panel Up-Gradation of OPD building, Old Hospital Building, MCC Panel of BMT HVAC, and replacement of main cables of chillers at Dr. B. Borooah Cancer institute, Guwahati- 16.
Sl. No. Item Description
1OPD Building Panel-1
2Supply, Installation, Testing & Commissioning of L.T Panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket, IS 8623 etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. The panel shall be suitable for receiving Cable / Bus duct to the incomer of source. Panel shall have potential free contacts to interface with BMS in future..
3Incomer
4800A,4P, 50kA, microprocessor based MCCB electrical operated, with overload, instantaneous SC, delayed SC, and ground fault protection with necessary communication port, shunt trip coil, U/V release etc - 1 nos.
5Busbar
61000 A TPN, 50kA busbars of high conductivity electrolytic quality Aluminium alloy and suitable size earthing conductor through out the panel for its earthing. Bus Bar Shall have 100% neutral.
7Instruments
82A, C curve SP MCB - 4 set
9RYB indication lamp, LED type - 4 set
10On/Off, Trip indication lamp, LED type - 4 set
111 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWH, Acc class 1 and with necessary communication port (Backnet/Modbus/RS:485) suited for BMS system
12800/5A 15VA class 1 resin cast CT - 1 set
13Outgoing.
14Supply and Installation of 400A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 2 nos.
15Supply and Installation of 250A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 1 no.
16Supply and Installation of 160A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 1 no.
17Supply and Installation of 125A 3P 25kA MCB - 1 nos.
18Supply and Installation of 100A 3P 25kA MCB - 09 nos.
19OLD Hospital Building Panel-1
20Supply, Installation, Testing & Commissioning of L.T Panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket, IS 8623 etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. The panel shall be suitable for receiving Cable / Bus duct to the incomer of source. Panel shall have potential free contacts to interface with BMS in future..
21Incomer
22250A,4P, 50kA, microprocessor based MCCB electrical operated, with overload, instantaneous SC, delayed SC, and ground fault protection with necessary communication port, shunt trip coil, U/V release etc - 1 nos.
23Busbar
24400 A TPN, 35kA busbars of high conductivity electrolytic quality Aluminium alloy and suitable size earthing conductor through out the panel for its earthing. Bus Bar Shall have 100% neutral.
25Instruments
262A, C curve SP MCB - 4 set
27RYB indication lamp, LED type - 4 set
28On/Off, Trip indication lamp, LED type - 4 set
291 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWH, Acc class 1 and with necessary communication port (Backnet/Modbus/RS:485) suited for BMS system
30250/5A 15VA class 1 resin cast CT - 1 set
31Outgoing.
32Supply and Installation of 160A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 1 nos.
33Supply and Installation of 125A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 2 nos.
34Supply and Installation of 63A 3P 10KA MCB- 03 nos.
35Supply and Installation of 40A 3P 10kA MCB - 04 nos.
36OLD Hospital Building Panel-2
37Supply, Installation, Testing & Commissioning of L.T Panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket, IS 8623 etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. The panel shall be suitable for receiving Cable / Bus duct to the incomer of source. Panel shall have potential free contacts to interface with BMS in future..
38Incomer
39400A,4P, 50kA, microprocessor based MCCB electrical operated, with overload, instantaneous SC, delayed SC, and ground fault protection with necessary communication port, shunt trip coil, U/V release etc - 1 nos.
40Busbar
41500 A TPN, 35kA busbars of high conductivity electrolytic quality Aluminium alloy and suitable size earthing conductor through out the panel for its earthing. Bus Bar Shall have 100% neutral.
42Instruments
432A, C curve SP MCB - 4 set
44RYB indication lamp, LED type - 4 set
45On/Off, Trip indication lamp, LED type - 4 set
461 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWH, Acc class 1 and with necessary communication port (Backnet/Modbus/RS:485) suited for BMS system
47400/5A 15VA class 1 resin cast CT - 1 set
48Outgoing.
49Supply and Installation of 250A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 2 nos.
50Supply and Installation of 160A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 2nos.
51Supply and Installation of 125A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 2nos.
52Supply and Installation of 100A 3P 35kA MCCB with microprocessor based release with adjustable OL, SC and EF protection - 1nos.
53Supply and Installation of 63A 3P 10KA MCB- 05 nos.
54Supply and Installation of 63A DP 10KA MCB- 02nos.
55Supply and Installation of 40A DP 10KA MCB- 02nos.
56Supply, Installation, Testing and Commissioning (SITC) of Automatic Motor Control Centre (MCC) Panel for Chiller UnitsSupply, installation, testing and commissioning of floor-mounted, front-operated, indoor, free-standing, cubicle type Automatic Motor Control Centre (MCC) Panel, fabricated from CRCA sheet steel of minimum 2.0 mm thickness for frame and 1.6 mm for doors and covers, powder coated after seven-tank pretreatment process, suitable for operation of 02 Nos. Chiller Units (01 Duty + 01 Standby).The panel shall be designed for 415 V ±10%, 3 Phase, 4 Wire, 50 Hz AC supply, complete with adequately rated copper busbars, colour coded and supported on non-hygroscopic SMC/DMC insulators. The panel shall have a short-circuit withstand capacity of minimum 50 kA for 1 second and shall comply with IS 8623/IEC 61439.
57Incommer
58450A,4P, 50kA, microprocessor based MCCB electrical operated, with overload, instantaneous SC, delayed SC, and ground fault protection with necessary communication port, shunt trip coil, U/V release etc - 1 nos.
59Busbar
60450 A TPN, 35kA busbars of high conductivity electrolytic quality Aluminium alloy and suitable size earthing conductor through out the panel for its earthing. Bus Bar Shall have 100% neutral.
61Instruments
622A, C curve SP MCB - 4 set
63RYB indication lamp, LED type - 4 set
64On/Off, Trip indication lamp, LED type - 4 set
651 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWH, Acc class 1 and with necessary communication port (Backnet/Modbus/RS:485) suited for BMS system
66450/5A 15VA class 1 resin cast CT - 1 set
67Control ckt. MCB SP for indication/ metering circuit-6A
68Chillar
69MPCB TP (S/C protection)-100A
70Aux. contact
71Extended Handle
72Contactor,Power contactor, AC-3 with 2NO+2NC-140
73Relay,Overload relay (thermal)
74Indication,Red lamp for On indication
75Indication,Amber lamp for Trip indication
76Indication Green lamp for Off indication
77Button Start, Stop Push Button
78Button NO, NC Contacts
79Control ckt. MCB SP for control circuit-6A
80Control ckt. Neutral link
81Pump-1
82MCB TP- 63A
83MPCB TP (S/C protection)-63A
84Aux. + Trip contact
85Contactor,Power contactor, AC-3 with 2NO+2NC-70A
86Contactor,2NO+2NC
87Indication,Red lamp for On indication-230V AC
88Indication,Amber lamp for Trip indication-230V AC
89Indication,Green lamp for Off indication-230V AC
90Button,Start, Stop Push Button
91Button,NO, NC Contacts
92Control ckt,MCB SP for control circuit- 6A
93Control ckt,Neutral link
94Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)
95Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
96Pump-2
97MCB TP-63A
98MPCB TP (S/C protection)-63A
99Aux. + Trip contact
100Contactor,Power contactor, AC-3 with 2NO+2NC-70A
101Contactor,2NO+2NC
102Indication,Red lamp for On indication-230V AC
103Indication,Amber lamp for Trip indication-230V AC
104Indication,Green lamp for Off indication-230V AC
105Button,Start, Stop Push Button
106Button,NO, NC Contacts
107Control ckt,MCB SP for control circuit -6A
108Control ckt,Neutral link
109Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)
110Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
111Air Exhaust Fan,
112MCB TP-63A
113MPCB TP (S/C protection)-63A
114Aux. + Trip contact
115Contactor,Power contactor, AC-3 with 2NO+2NC-70A
116Contactor,2NO+2NC
117Indication,Red lamp for On indication-230V AC
118Indication,Amber lamp for Trip indication-230V AC
119Indication,Green lamp for Off indication-230V AC
120Button,Start, Stop Push Button
121Button,NO, NC Contacts
122Control ckt,MCB SP for control circuit-6A
123Control ckt,Neutral link
124Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)+B125
125Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
126Air Exhaust Fan,
127MCB TP-63A
128MPCB TP (S/C protection)-63A
129Aux. + Trip contact
130Contactor,Power contactor, AC-3 with 2NO+2NC-70A
131Contactor,2NO+2NC
132Indication,Red lamp for On indication-230V AC
133Indication,Amber lamp for Trip indication -230V AC
134Indication,Green lamp for Off indication -230V AC
135Button,Start, Stop Push Button
136Button,NO, NC Contacts
137Control ckt,MCB SP for control circuit -6A
138Control ckt,Neutral link
139Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)
140Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
141Air Handling Unit(AHU)
142MCB TP-63A
143MPCB TP (S/C protection)-63A
144Aux. + Trip contact
145Contactor,Power contactor, AC-3 with 2NO+2NC-70A
146Contactor,2NO+2NC
147Indication,Red lamp for On indication -230V AC
148Indication,Amber lamp for Trip indication-230V AC
149Indication,Green lamp for Off indication-230V AC
150Button,Start, Stop Push Button
151Button,NO, NC Contacts
152Control ckt,MCB SP for control circuit -6A
153Control ckt,Neutral link
154Accessories,Busbar-Aluminium500A main bus, (dropper bus as per feeder rating)
155Accessories,Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger
156Air Handling Unit(AHU)
157MCB TP-63A
158MPCB TP (S/C protection)-63A
159Aux. + Trip contact
160Contactor,Power contactor, AC-3 with 2NO+2NC-70A
161Contactor,2NO+2NC
162Indication,Red lamp for On indication-230V AC
163Indication,Amber lamp for Trip indication-230V AC
164Indication,Green lamp for Off indication-230V AC
165Button,Start, Stop Push Button
166Button,NO, NC Contacts
167Control ckt,MCB SP for control circuit-6A
168Control ckt,Neutral link
169Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)
170Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
171Air Handling Unit(AHU)
172MCB TP-63A
173MPCB TP (S/C protection)-63A
174Aux. + Trip contact
175Contactor,Power contactor, AC-3 with 2NO+2NC-70A
176Contactor,2NO+2NC
177Indication,Red lamp for On indication-230V AC
178Indication,Amber lamp for Trip indication-230V AC
179Indication,Green lamp for Off indication-230V AC
180Button,Start, Stop Push Button
181Button,NO, NC Contacts
182Control ckt,MCB SP for control circuit-6A
183Control ckt,Neutral link
184Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)+B179
185Accessories,Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger
186Air Handling Unit(AHU)
187MCB TP-63A
188MPCB TP (S/C protection)-63A
189Aux. + Trip contact
190Contactor,Power contactor, AC-3 with 2NO+2NC-70A
191Contactor,2NO+2NC
192Indication,Red lamp for On indication-230V AC
193Indication,Amber lamp for Trip indication-230V AC
194Indication,Green lamp for Off indication-230V AC
195Button,Start, Stop Push Button
196Button,NO, NC Contacts
197Control ckt,MCB SP for control circuit-6A
198Control ckt,Neutral link
199Accessories,Busbar-Aluminium-(500A main bus, dropper bus as per feeder rating)
200Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
201Heater
202MCB TP-63A
203MPCB TP (S/C protection)-63A
204Aux. + Trip contact
205Contactor,Power contactor, AC-3 with 2NO+2NC-70A
206Contactor,2NO+2NC
207Indication,Red lamp for On indication-230V AC
208Indication,Amber lamp for Trip indication-230V AC
209Indication,Green lamp for Off indication-230V AC
210Button,Start, Stop Push Button
211Button,NO, NC Contacts
212Control ckt,MCB SP for control circuit-6A
213Control ckt,Neutral link
214Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating))
215Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
216Heater
217MCB TP-63A
218MPCB TP (S/C protection)-63A
219Aux. + Trip contact
220Contactor,Power contactor, AC-3 with 2NO+2NC-70A
221Contactor,2NO+2NC
222Indication,Red lamp for On indication-230V AC
223Indication,Amber lamp for Trip indication-230V AC
224Indication,Green lamp for Off indication-230V AC
225Button,Start, Stop Push Button
226Button,NO, NC Contacts
227Control ckt,MCB SP for control circuit-6A
228Control ckt,Neutral link
229Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)
230Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
231Heater
232MCB TP-63A
233MPCB TP (S/C protection)-63A
234Aux. + Trip contact
235Contactor,Power contactor, AC-3 with 2NO+2NC-70A
236Contactor,2NO+2NC
237Indication,Red lamp for On indication-230V AC
238Indication,Amber lamp for Trip indication-230V AC
239Indication,Green lamp for Off indication-230V AC
240Button,Start, Stop Push Button
241Button,NO, NC Contacts
242Control ckt,MCB SP for control circuit-6A
243Control ckt,Neutral link
244Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)
245Accessories,(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
246Heater
247MCB TP-63A
248MPCB TP (S/C protection)-63A
249Aux. + Trip contact
250Contactor,Power contactor, AC-3 with 2NO+2NC-70A
251Contactor,2NO+2NC
252Indication,Red lamp for On indication-230V AC
253Indication,Amber lamp for Trip indication-230V AC
254Indication,Green lamp for Off indication-230V AC
255Button,Start, Stop Push Button
256Button,NO, NC Contacts
257Control ckt,MCB SP for control circuit-6A
258Control ckt,Neutral link
259Accessories,Busbar-Aluminium(500A main bus, dropper bus as per feeder rating)
260Accessories(Wiring (Power & control cable)Lugs (Power & control cable)InsulatorFRPDoor Limit switch in cable alleyHeater in cable alleyThermostat in cable alleyIllumination lamp in cable alleyName plats and tagsBase channelFabrication (with painting)Nut, bolt, washer, Gasket, Sleeves etcLabour Charger)
261Supply,and laying 50sq.mm,4core,flexible copper conductor,non-armoured,PVC insulated
262Supply,and laying 16sq.mm,4core,flexible copper conductor,non-armoured,PVC insulated
263Supplying and installing following size of perforated Hot DippedGalvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
264100 mm width X 50 mm depth X 1.6 mm thickness
265150 mm width X 50 mm depth X 1.6 mm thickness
266300 mm width X 50 mm depth X 1.6 mm thickness
267Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
268100 mm width X 50 mm depth X 1.6 mm thickness
269150 mm width X 50 mm depth X 1.6 mm thickness
270300 mm width X 50 mm depth X 1.6 mm thickness Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57394790
AUTHORITY Boards / Undertakings / PSU
TENDER VALUE 34.30 Lakhs
LAST DATE 26-09-2026
Authority
Authority Name Tata Memorial Centre
Work Description Tender for Electrical Panel Up-Gradation Of Opd Building, Old Hospital Building, Mcc Panel Of Bmt Hvac, And Replacement Of Main Cables Of Chillers At Dr. B. Borooah Cancer Institute, Guwahati- 16.
Basic Detail
Tender No SITC of Electrical Panel Up-Gradation work in Dr BBCI
Bidding Type Tender
Location
City Kamrup Metro
State Assam
Key Dates
Publish Date 07 Sep 2026
Submission Date 26 Sep 2026
Open Date 28 Sep 2026
Finance
Tender Value 34.30 Lakhs
Tender Fee Ref. Documents
EMD 80956
Exemption Not Available
Document List
3dcc595b-35a8-4b22-9c51-9a225c7bf86b.html
BOQ_972126.xls
detailtender.pdf
Tendernotice_1 (10).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 07, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 26, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 12 days
Sep 28, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 14 days

Tender Documents

Download All (ZIP) ↓
html

3dcc595b-35a8-4b22-9c51-9a225c7bf86b.html

xls

BOQ_972126.xls

pdf

detailtender.pdf

pdf

Tendernotice_1 (10).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders