Tender For B.O.Q Of Establishment Of Workshop For Repair Of Damaged Transformer At Shopian B.W.O Providing Electrification Facility, Cabling,30 Kva Servostabilizer And Allied Electric Works At Newly Constructed Workshop Building At Shopian.
Tender Overview
Project Description
Tender for B.O.Q Of Establishment Of Workshop For Repair Of Damaged Transformer At Shopian B.W.O Providing Electrification Facility, Cabling,30 Kva Servostabilizer And Allied Electric Works At Newly Constructed Workshop Building At Shopian.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2X 1.5 sq.mm FRLS PVC insulated copper conductor ( Havell/Polycab/ Fenolex/ Anchor/eq. standard make as desired by engineer incharge ) single core cable in surface / recessed medium class PVC conduit,(cutting the wall and making good the same in case of recessed conduit including painting as required with cement plaster, wall putty , paint, complete) with modular switch ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /ABB Tvisha make.), modular plate,suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Wiring for light/ power plug with 2X4 sq. mm + 1X 4 sq. mm earth wire , FRLS PVC insulated copper conductor ( Havell/Polycab/ Fenolex/Anchor/ equivalent as directed by engineer incharge.) single core cable in surface/recessed medium class PVC conduit.(cutting the wall and making good the same in case of recessed conduit including painting as required with cement plaster, wall putty , paint, complete) |
| 3 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch,modular plate, suitable GI box , connections etc. as required. Modular Switch & Socket:- ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Leiva /ABB Tvisha make make.) |
| 4 | Wiring for lighting circuits/ 6- 10 amp power plugwith 2X2.5 sq. mm FRLS PVC insulated copper conductor ( Havell/Polycab/ Fenolex/Anchor/ equivalent as directed by engineer incharge.) single core cable in surface/recessed medium class PVC conduit (cutting the wall and making good the same in case of recessed conduit including painting as required with cement plaster, wall putty , paint, complete)alongwith 1 No. 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). Modular Switch & Socket:- ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /ABB Tvisha make.) |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 7 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP M.C.B, \\"C\\" curve including connections, painting etc. as required. |
| 8 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor ( Havell/Polycab/ Fenolex/ Anchor/ equivalent as directed by engineer incharge.), single core cable in surface/ recessed medium class PVC conduit as required.(cutting the wall and making good the same in case of recessed conduit including painting as required with cement plaster, wall putty , paint, complete) |
| 9 | (a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 10 | ( b ) 2 X6 sq. mm + 1 X 6 sq. mm earth wire |
| 11 | ( c )2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 12 | (d) 2 X 16 sq. mm + 1 X 6 sq. mm earth wire |
| 13 | Supplying and fixing of following sizes of medium class PVC conduit( Anchor/ Ravindra/ Eq. make)along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required, with cement plaster, wall putty , paint, complete |
| 14 | Providing and fixing of 6-16mm Cu thimbles duly cramped at cable ends. |
| 15 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 16 | Supply installation testing and commissioning of Indicator of Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /Crabtree athena make.) including GI box along with modular base & cover plate in recess etc. as required. |
| 17 | Sub Head-2 - Fixtures and Fittings |
| 18 | Supply installation testing and commissioning of 18 W + LED Surface/recess, square or round Mounted light luminary fitting shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium body and Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Philips/ Havell/Wipro/LT /Helonix make / sample to be approved before installation.. |
| 19 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan ( USHA/havell /Bajaj/Crompton/equivalent make as directed by engineer incharge,) with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS: 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise-75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 20 | Supply and fixing of 6 amp/250 V A.C fan dimmer step type 2 module with cover plate Anchor roma plus/Legrand Mylinc /ABB Tivsha/schneider Livia /Havell Coral make. |
| 21 | Supply installation testing and comm. Of 200mm -250mm sweep exhaust fan Shutter type of havell /USHA/Crompton/equivalent make as directed by engineer incharge, including making of space in wall/ window as per site requirement and necessary connections. |
| 22 | Supplying and fixing following way, Triple pole and neutral, sheet steel, MCB distribution board,( legrand/ Shinider/Hager make) 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) |
| 23 | 4 way (4 + 12), Double door |
| 24 | S/F testing and comm. Of MCB's 10 K of the below mentioned capacities in sub main controls legrand C curve/ Schinider/ ABB ./equivalent make as directed by engineer incharge. |
| 25 | a) 6-32 Amp SP MCB |
| 26 | b) 40-63amp DP MCB |
| 27 | S/L , testing and commissioning of PVC XLPE insulated alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size. |
| 28 | a)95 sq.mm 3.5 core |
| 29 | b)50 sq.mm 3.5 core |
| 30 | c) 16 sq.mm 4 core |
| 31 | Supply installation testing and comm. of High bay flood light 50 W ( warm, white ) with minimum system lumen efficacy of 120 lm/W , Epoxy powder coated die-cast aluminium housing (LM24) with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin-loopout class 1, IP66, IK 07, , with high power LED's as light source with Built-In Potted IP67 electronic LED driver with APFC,lower THD, toughned glass and secondary lens,Open Circuit Protection, Over Voltage Protection, Surge Voltage Protection upto 10kV With Built In SPD & other safety test as per IS 15885 Part-2/Sec 13, IEC60598-1. Preferred make: Philips/ LT /Wipro make. ( sample to be approved before installation) the job also includes the angle iron stand of suitable size to be grouted in cement concrete with hold fasteners complete job. |
| 32 | Design, Fabrication, Supplying, Installation, Testing and Commissioning of following panel, duly manufactured from CPRI approved manufacturer, made out of 2mm thick M.S. sheet steel , floor/wall mounted, vermin and dust proof, indoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly painted with provision for fixing of following switch gears, , Aluminium Bus Bar of various ratings after taking Derating factor into account, and other allied accessories etc. as required.( As per approved design,size may vary as per site requirement) |
| 33 | Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required. |
| 34 | Normal INCOMING: |
| 35 | a)250A 4P MCCB 36 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make. |
| 36 | b) 4 No. of Aluminium Bus Bar of 400 Amp. |
| 37 | c)Digital meters and phase indicators -1 set. |
| 38 | d) onload Change over switch 160 Amp for generator.Front operated. |
| 39 | e) 4 No. of Aluminium Bus Bar of 300 Amp. |
| 40 | c)Digital meters and phase indicators -1 set. |
| 41 | OUTGOING: |
| 42 | a)160A 4P MCCB 25 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make. |
| 43 | b) 40-63amp TPN MCB 10KA |
| 44 | b) 40-63amp DP MCB 10KA |
| 45 | c) space for 12 way MCB's |
| 46 | Supplying and fixing 20 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 amps \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 47 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 48 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 49 | S/I testing and comm. Of three phase 30 KVA 50HZ oil cooled(Transformer oil is to be provided with stabilizer conforming to IS 335,IEC296)) unbalanced type servo voltage stabilizer(A.E / Cosco/ chinar/ Electricfield make) having an input voltage ranging from 156V to 415 V ( phase to phase) and balanced output voltage of 415V, +/- 1%. ( Test certificate to be provided by the manufacturer) The unit incorporate |
| 50 | a) 0-500V digital voltmeter with selector switch. |
| 51 | b) A three phase change over switch to read voltage on incoming and output side |
| 52 | c) indicating lights 6 No two numbers for each of the motorised units, one for lower limit and other for higher limit. |
| 53 | d) six push button control for movement operation of three motorised dimmer units two for each unit i.e one for raise operation and one for lower operation under the conditions of adjustment of auto/mannual selector switch (DPDT) |
| 54 | e) Single phase Preventer ( contactor Switch of required rating) Legrand make. |
| 55 | f) six potential meter resistance with lock meter two for each phase control, one for sensitivity and other for level control. |
| 56 | g) two sets of indication lamps three numbers each to indicate output and input indication |
| 57 | h) 20 % over load bearing capacity for one hour. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender