Defence Statutory Bodies & Commissions/Committees Closing in 21 days TDR #57386029

Tender For Provision Of Deficient Type-Ii Defence Civilians Married Accommodation At Nad Sunabeda

Issued by Statutory Bodies & Commissions/Committees · Koraput, Odisha
Tender Value
24.24 Crore
Estimated cost
Bid Submission
14 Oct 2026
21 days left
EMD
15 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Koraput → Odisha
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Provision Of Deficient Type-Ii Defence Civilians Married Accommodation At Nad Sunabeda

BOQ

Name of Work:- PROVISION OF DEFICIENT TYPE-II DEFENCE CIVILIANS MARRIED ACCOMMODATION AT NAD SUNABEDA
Sl. No. Item Description
1SCHEDULE 'A' PART-I to SCHEDULE 'A' PART-XVINote: Schedule 'A' Part-I to Part-XVI are prepriced by MES. Bidders shall insert their lump sum amount in green coloured field under Column 6 only.
2Lump Sum price worked out by the contractor for (BUILDINGS & STRUCTURES), as listed in SCHEDULE 'A' PART-I
3Lump Sum price worked out by the contractor for 'Site Clearance/Area Development/Earth Work/Excavation', as listed in Schedule 'A' Part-II
4Lump Sum price worked out by the contractor for 'INTERNAL WATER SUPPLY', as listed in Schedule 'A' Part-III
5Lump Sum price worked out by the contractor for 'ROAD, PATH AND CULVERT', as listed in Schedule 'A' Part-IV
6Lump Sum price worked out by the contractor for 'SEWAGE DISPOSAL', as listed in Schedule 'A' Part-V
7Lumpsum price worked out by the contractor for 'AREA DRAINAGE', as listed in Schedule 'A' Part-VI
8Lump Sum price worked out by the contractor for 'FENCING', as listed in Schedule 'A' Part-VII
9Lump Sum price worked out by the contractor for 'Retaining Wall', as listed in Schedule 'A' Part-VIII
10Lump Sum price worked out by the contractor for 'PVC Conduit', as listed in Schedule 'A' Part-IX
11Lump Sum price worked out by the contractor for 'EXTERNAL WATER SUPPLY', as listed in Schedule 'A' Part-X
12Lump Sum price worked out by the contractor for 'INTERNAL ELECTRIFICATION', as listed in Schedule 'A' Part-XI
13Lump Sum price worked out by the contractor for 'EXTERNAL ELECTRIC SUPPLY', as listed in Schedule 'A' Part-XII
14Lump Sum price worked out by the contractor for 'LIGHTENING PROTECTION', as listed in Schedule 'A' Part-XIII
15Lump Sum price worked out by the contractor for 'FIRE FIGHTING SYSTEM', as listed in Schedule 'A' Part-XIV
16Lump Sum price worked out by the contractor for 'FIRE ALARM & DETECTION SYSTEM', as listed in Schedule 'A' Part-XV
17Lump Sum price worked out by the contractor for 'Demolition/ Dismantling', as listed in Schedule 'A' Part-XVI
18SCHEDULE 'A' PART-XVII: (MISCELLANEOUS ITEMS):
19Internal Water supply
20S&F fancy type chromium plated bib cock long body 15mm size with wall flange, as directed by the Engr-in-Charge.
21S&F fancy type brass chromium plated center hole basin mixer 15mm size for mixing Hot and Cold Water screwed down for CPVC pipe and fixed.
22S&F fancy type brass chromium plated wall mixer \\"L\\" bend 15mm size with wall flange with provision for overhead shower for mixing Hot and Cold Water screwed down for CPVC pipe and fixed.
23S&F ABS Round shower with SS Arm and Flange complete.
24S&F Liquid soap Dispenser 400ml of ABS Body fixed with and including Chromium plated brass screws and wooden/plastic cleats (Minimum weight 105gms) complete all as specified and directed.
25S&F Tubular towel rail, Brass chromium plated, 20mm dia, D type, 60cm long between flanges complete all as specified and directed.
26S&F Health faucet (ABS Body) mild steel chromium plated suitable for 15 mm dia pipe with 1 metre long flexible tube and ABS wall hook including making connections and fixed in position complete in all respect as specified.
27S&F Angle stop valve of chromium plated 15mm with flange and fixed complete all as specified and directed.
28ROAD, PATH AND CULVERT
29M&L for Reinforced concrete pipes, class NP3 600mm dia, laid and jointed complete with collars including bedding with PCC 1:3:6 type C2 (using 40mm graded stone aggregate) as in concrete bed to drain pipes including packing under and haunching against the sides of pipes for 600mm dia bore all as specified
30SEWAGE DISPOSAL
31M&L for construction of RCC Septic tank for 400 Users designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:2:4 below foundation , brickwork in CM 1:4, RCC M-30 Design Mix in walls, Base slab, baffle walls and Roof slab including beams etc with vent shaft, manhole openings with cover connection etc, complete all as specified and as directed.(Ref Drg No. TD-389 (S), Sheet No. 1/3 - 3/3)
32M&L for construction of Soakage well of 400 users capacity, excavation , in any type of soil, foundation in PCC 1:4:8 walls of honey combed masonry with RCC cover slab in M30 cover, interconnecting pipes of RCC complete filled with brick bats complete all as specified and as shown in drawings and as directed of size 4.20 m dia X 4.25 m depth complete all as specified and as directed.(Ref Drg No. TD-318 (S), Sheet No. 1/1)
33PVC Conduit
34Supply and fix factory fabricated GI metal flush boxes suitable for 1-2 module complete all as specified and as directed.
35Supply and fix TV co-axial socket 1 module with cover plate with frame complete with all accessories all as directed.
36Supply and fix RJ 45 jack internet/telephone model socket 1 module with cover plate with frame complete all as specified and as directed.
37EXTERNAL WATER SUPPLY
38M&L for Cutting existing CI/ DI/ MS pipe line of 150 mm dia for alterations or additions necessarily done in position without taking down and inserting Tee of 150 x 150 x 100 mm and for tapping all as specified and directed.
39Supplying and laying ductile pipe with spigot and socket type centrifugally cast(spun) class K-9 of 100 mm dia pipe conforming to IS-8329 including testing and commissioning complete all as directed.
40M&L for valve chamber of internal size 1.0 x 1.0 x 1.0 m comprising of 50 mm thick PCC 1:5:10 type E2 foundation, 200mm thick brick wall in CM 1:6, 15mm thick plastering in CM 1:4 internally and externally up to 50mm below GL, 100mm thick PCC 1:3:6 type B1 as in copings, 3mm thick MS sheet cover with suitable hinges and locking arrangement, painting steel surfaces with two coats of synthetic enamel paint over a coat of primer including necessary earth work and excavation in any type of soil complete all as directed.
41INTERNAL ELECTRIFICATION:
42M&L for Point wiring with 1.5 sqmm PVC insulated and unsheathed copper conductor cable multistranded 1100 volts grade, FRLS, ISI marked drawn through and including non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre-fabricated Gl terminal box of suitable size made out of 1.2 mm thick sheets, for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, including one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed for the following:-
43All as per item No. 34 here-in-before but for One light point controlled by one switch complete all as specified and directed.
44All as per item No. 34 here-in-before but for One bell point controlled by one bell push complete all as specified and directed.
45All as per item No. 34 here-in-before but for One Ceiling fan point controlled by one switch complete all as specified and directed.
46All as per item No. 34 here-in-before but for One Exhaust fan point controlled by one switch complete all as specified and directed.
47All as per item No. 34 here-in-before but for One 3 Pin socket outlet 6 amps socket on same board with other switches complete all as specified and directed.
48All as per item No. 34 here-in-before but for One light point controlled by two number of, 2 way switches complete all as specified and directed.
49M&L for Point wiring with 2.5 sqmm PVC insulated and unsheathed copper conductor cable multistranded 1100 volts grade, FRLS, ISI marked drawn through and including non-metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre-fabricated Gl terminal box of suitable size made out of 1.2 mm thick sheets, for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, including one run of 2.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed for the following:-
50All as per item No. 41 here-in-before but for One 3 Pin socket outlet 6 amps socket on independent board complete all as specified and directed.Note: One circuit with maximum 4 Points Socket outlet 6Amp independent shall be provided
51All as per item No. 41 here-in-before but for One 3 pin socket outlet, 16 Amps on independent board complete all as specified and directed.Note: One circuit of one Socket outlet 16Amp independent shall be provided
52Supply and fixing LED adore lamp for AC 230 Volt supply, B22 type, CDS five star, 07/09 watts of five star rated complete all as specified and as directed.
53Supply and fixing ceiling fan, AC single phase 230 V of size 1200 mm sweep, copper wound with complete set and fixtures such as canopy, down rod etc. 5 Star rating, with brushless direct current motor (BLDC) min air delivery 210 cubic meter per minute with service value 6.0 BEE including making necessary electric connection from ceiling rose to fan connected with twin core flexible copper wire all as specified and directed.
54S&F Exhaust fan of size 250 mm sweep made of sturdy Engineering plastic complete with louvers, shutter, voltage 230 V, 50 Hz, 1200 RPM, Copper winding, fixed on wall, making opening, fixing and making good the disturbed surfaces etc complete with and inclusive of making necessary electric connection from ceiling rose to fan with twin core flexible wire all as specified and as directed.
55S&F Exhaust fan of size 300 mm sweep, Steel body, complete with blades, frame and louvers suitable for operation on 230 V AC single phase supply, 50 Hz fixed on wall including making of necessary opening, fixing and making good the disturbed surfaces etc complete with and inclusive of making necessary electric connection from ceiling rose to fan with twin core flexible wire all as specified and as directed.
56Supply and fixing Energy efficient LED tube light fitting with tube 10 watts or nearest size, 240V, 50 Hz surface mounted, decorative ultra slim LED lighting fixture with extruded polycarbonate environmental friendly, not less than 100 lumens per watt PF greater than 0.9 IP rating 20 energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed
57Supply and fixing Energy efficient LED tube light fitting with tube 6 watts or nearest size ,240V, 50 Hz surface mounted, suitable for fixed above mirror , energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed
58Supply and fixing Energy efficient LED tube light fitting with tube 20 watts or nearest size ,240V, 50 Hz surface mounted, decorative ultra slim LED lighting fixture with extruded polycarbonate environmental friendly, not less than 100 lumens per watt PF greater than 0.9 IP rating 20 energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed
59S&F LED bldg Security light fitting 25W outdoor type with high pressure die cast aluminium housing and heat resistant luminaire complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics of IP 65/66 pre wired with 1.5 Sq mm copper conductor cable upto connector including not less than 1.5 Mtr long Gl Tubing Med grade not less than 25 mm dia bend to shape fixing on wall with suitable MS brackets complete all as specified and as directed.
60Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclusive of 25mm dia medium grade PVC rigid conduit concealed to wall, and PVC wire of size 2x2.5 sqmm for phase and neutral duly colour coded and 1x2.5 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note: Three runs of cable along with PVC conduit shall be measured as one RM
61Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclusive of 25mm dia medium grade PVC rigid conduit concealed to wall, and PVC wire of size 2x4 sqmm for phase and neutral duly colour coded and 1x4.0 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note: Three runs of cable along with PVC conduit shall be measured as one RM
62Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclusive of 25mm dia medium grade PVC rigid conduit concealed to wall, and PVC wire of size 2x6 sqmm for phase and neutral duly colour coded and 1x6 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note: Three runs of cable along with PVC conduit shall be measured as one RM
63Supply and fixing concealed in wall Vertical MCCB DB double door type, VTPN 6 way 415V, 50Hz , IP 43 protection , including provision for fixing MCCB FP as incomer and outgoing circuits MCB SPN/SP/DP/TP complete, fill empty way with blanking plates complete all as specified and directed.
64Supply and fixing concealed in wall Vertical double door type, TPN DB 6 way 415V, 50Hz , IP 43 protection , including provision for fixing MCCB FP as incomer and outgoing circuits MCB SPN/SP/DP/TP complete, fill empty way with blanking plates complete all as specified and directed.
65S&F MCB TPN 4 pole 415V, 50Hz, 16KA of capacity 40 Amp complete all as specified and directed.
66S&F electric water heater storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litres BEE 5star rating complete all accessories such as safety valves thermostat NRV steel Braided connection hose complete all as specified ad directed
67S&F Metal clad socket with male and female socket 3 pin 230v 50 Hz with MCB 20 A MCB all as specified and directed
68Supply install testing and commissioning integrity of smart meter single phase as per BIS 16444 with communication technology including cellular /RF / hybrid (cellular +RF) AC whole current smart energy meter of rating 10-40 A complete as per specification meter shall have the ability to communicate with complete as per specification, meter shall have the ability to communicate with HES on any one of the communication technologies mentioned in IS 16444 part I (RF/ cellular)in a secure manner in case of cellular based meter the meter shall accommodate e-SIM /SIM of any service provider the smart meter shall have a dedicated sealable slot for accommodating plug-in-type bi directional communication module which shall integrated the respective communication technology (RF/PLC/cellular) with the smart meter leading to easy adaptability for network interfaces the plug - in module shall be field swappable/replaceable complete all as specified and directed.Note: (i) Meter specification may please be read in co-junction with PS clauseii) 15 min instantaneous data for voltage for voltage current PF power cumulative energy and frequency monthly billing survey for cumulative energy and max demand of software.iii) Smart Pre-paid energy meters shall be provided to each quarter as per IS-16444 and IS-15959 amended upto date and to be integrated in Central Smart meter server of MES.
69M & L for LT Feeder pillar Box made of CRCA sheet 3.15 mm thick outdoor pedestal type totally enclosed with front and back opening hinged doors with projected as raised platform of suitable size weather and water proof with necessary licking arrangement along with lugs cables glands of various sizes for cables danger notice plate stickering of switch gears about termination of switch gears and the nuts bolts etc used are to be made of rust proof materials incl as per IS 8623 Al bus bar 200 A 04 Nos with insulators suitable for phase and neutral LT AC 50 HZ 415 V complete with powder coating necessary internal electrification connections as requiredINCOMING:a) MCCB 415V 50HZ 4 pole 100Amps 25 KA with thermal magnetic setting -01 Nob)LED indicating lamp for three phases intelligent panel meter to measure voltage current frequency PF KWH etc all as specifiedOUTGOING :a) MCCB 415V 50HZ 3 pole 63Amps 16 KA with thermal magnetic setting -02 Nos
70EXTERNAL ELECTRIC SUPPLY
71Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following cross sections:
72a) 3.5 core 300 sqmm
73b) 3.5 core 95 sqmm
74c) 3.5 core 35 sqmm
75d) 4.0 core 10 sqmm
76Supply, installation, testing and commissioning of Distribution Transformer, Step down 315 kVA, 11 kV/433 V, 3 Phase, 50 Hz, Outdoor Type, Oil Immersed, Naturally Air Cooled (ONAN), Copper Wound ,vector group Dyn11, complete with radiator cooling, conservator tank, off-circuit tap changer, marshalling box, all accessories and fittings, conforming to IS 1180 (Part-1): 2014 and latest amendments, Energy Efficiency Level-2 (BEE Star-2 or latest applicable rating), suitable for continuous outdoor operation under tropical climatic conditions, complete in all respects including first filling of transformer oil, transportation, erection, testing, commissioning, earthing connections, foundation works and all incidental works, as specified and as directed by the Engineer-in-Charge.a) Off Circuit Tap Changer (OCTC), Tapping range +5% to -10% in a steps of 2.5% per step (7 positions)b) Temp. Rise Shall be 40/45 Deg. C for Oil/Winding respectively Over an ambient of 50Deg.C Tempc) Insulation Class: Class Ad) Losses (Subject to IS 1180 Efficiency Level 2/ Star 2 as per latest Amendment 4) e) Percentage Impedance shall be 5.00% at rated current (Subject to tolerance specified in IS 1180)f) Rating & Diagram (R&D) Plate (Fitted on Transformer)g) Oil Temp. Indicator (OTI) with alarm and trip contacth) Winding Temp. Indicator (WTI) with alarm and trip contacti) Rated temp Class of Transformer Compartment K10 upto 1000kVAj) Lifting lugs/ hooks for transformer. Please Enable Macros to View BoQ information
77Supply, installation, testing and commissioning of Distribution Transformer, Step down 315 kVA, 11 kV/433 V, 3 Phase, 50 Hz, Outdoor Type, Oil Immersed, Naturally Air Cooled (ONAN), Copper Wound ,vector group Dyn11, complete with radiator cooling, conservator tank, off-circuit tap changer, marshalling box, all accessories and fittings, conforming to IS 1180 (Part-1): 2014 and latest amendments, Energy Efficiency Level-2 (BEE Star-2 or latest applicable rating), suitable for continuous outdoor operation under tropical climatic conditions, complete in all respects including first filling of transformer oil, transportation, erection, testing, commissioning, earthing connections, foundation works and all incidental works, as specified and as directed by the Engineer-in-Charge.a) Off Circuit Tap Changer (OCTC), Tapping range +5% to -10% in a steps of 2.5% per step (7 positions)b) Temp. Rise Shall be 40/45 Deg. C for Oil/Winding respectively Over an ambient of 50Deg.C Tempc) Insulation Class: Class Ad) Losses (Subject to IS 1180 Efficiency Level 2/ Star 2 as per latest Amendment 4) e) Percentage Impedance shall be 5.00% at rated current (Subject to tolerance specified in IS 1180)f) Rating & Diagram (R&D) Plate (Fitted on Transformer)g) Oil Temp. Indicator (OTI) with alarm and trip contacth) Winding Temp. Indicator (WTI) with alarm and trip contacti) Rated temp Class of Transformer Compartment K10 upto 1000kVAj) Lifting lugs/ hooks for transformer. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57386029
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 24.24 Crore
LAST DATE 14-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Provision Of Deficient Type-Ii Defence Civilians Married Accommodation At Nad Sunabeda
Basic Detail
Tender No 85479
Bidding Type Tender
Location
City Koraput
State Odisha
Key Dates
Publish Date 07 Sep 2026
Submission Date 14 Oct 2026
Open Date 21 Oct 2026
Finance
Tender Value 24.24 Crore
Tender Fee 3000
EMD 15 Lakhs
Exemption Available
Document List
72cfdbb9-c26a-429f-9ccf-f71cefc63c8b.html
BOQ_883421.xls
Schedule.pdf
Tender.pdf
Tendernotice_1 (10).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 07, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 14, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 21 days
Oct 21, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 28 days

Tender Documents

Download All (ZIP) ↓
html

72cfdbb9-c26a-429f-9ccf-f71cefc63c8b.html

xls

BOQ_883421.xls

pdf

Schedule.pdf

pdf

Tender.pdf

pdf

Tendernotice_1 (10).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders