Tender For Electrification And Allied Works Of Infrastructure Development Including Setup Of New Smart Classroom At Rangamati North Gov. Primary School At Mathabhanga -Ii Block In The District Of Cooch Behar.
Tender Value
Ref. Documents
Estimated cost
Bid Submission
23 Sep 2026
8 days left
EMD
40000
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Darjeeling → West Bengal
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Electrification And Allied Works Of Infrastructure Development Including Setup Of New Smart Classroom At Rangamati North Gov. Primary School At Mathabhanga -Ii Block In The District Of Cooch Behar.
BOQ
| Sl. No. | Item Description |
| 1 | Supplying and fixing of following ways surface/ recessmounting, vertical type, 415 V, TPN MCB distributionboard of sheet steel, dust protected, duly powderpainted, inclusive of 200 A tinned copper bus bar,common neutral link, earth bar, din bar for mountingMCBs (but without MCBs and incomer ) as required .(Note : Vertical type MCB TPDB is normally usedwhere 3 phase outlets are required.)4 way (4 + 12), Double door(Make: Legrand/Schneider/Siemens as per the choice of EIC) |
| 2 | Providing and fixing following rating and breakingcapacity and pole MCCB with thermomagneticrelease and terminal spreaders in existing cubiclepanel board including drilling holes in cubicle panel,making connections, Ics=100% Icu and OperationalVoltage 690V etc. as required. 100A(Make :Legrand/Schneider/Siemens) |
| 3 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10kA, \\"C\\" curve, miniature circuit breaker suitable forinductive load of following poles in the existing MCBDB complete with connections, testing andcommissioning etc. as required. Triple pole(Make: Legrand/Schneider/Siemens as per the choice of EIC) |
| 4 | Wiring for light point/ fan point/ exhaust fan point/ callbell point with 1.5 sq.mm FRLS/HFFR PVC insulatedcopper conductor single core cable ( Make :Havells/Polycab/Finolex/RR Cabel as per the choice of EIC)in surface/recessed medium class PVC conduit, with modularswitch, modular plate, suitable GI box and earthingthe point with 1.5 sq.mm FRLS/HFFR PVC insulatedcopper conductor single core cable etc. as required. Group C |
| 5 | Supplying and fixing following modular switch/ socket( Make :Legrand Nextgen /Schneider/Siemens as per the choice of EICon the existing modular plate & switch box includingconnections but excluding modular plate etc. asrequired. 5/6 A switch |
| 6 | 3 pin 5/6 A socket outlet |
| 7 | Supplying and fixing suitable size GI box with modularplate and cover( Make: Legrand Nextgen /Schneider/Siemens as per the choice of EIC) in front on surface or in recess,including providing and fixing 3 pin 5/6 A modularsocket outlet and 5/6 A modular switch, connectionsetc. as required. |
| 8 | Supplying and fixing suitable size GI box with modularplate and cover( Make: Legrand Nextgen /Schneider/Siemens as per the choice of EIC) in front on surface or in recess,including providing and fixing 6 pin 5/6 & 15/16 Amodular socket outlet and 15/16 A modular switch,connections etc. as required. |
| 9 | Supplying & fixing suitable size GI box with modularplate and cover in front on surface or in recessincluding providing and fixing 25 A modular socketoutlet and 25 A modular SP MCB, \\"C\\" curve includingconnections, painting etc. as required. |
| 10 | Wiring for circuit/ submain wiring along with earth wirewith the following sizes of FRLS/HFFR PVC insulatedcopper conductor, single core cable ( Make: Havells/Polycab/Finolex/RR Cabel as per the choice of EIC)in surface/recessed medium class PVC conduit as required2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 11 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 12 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 13 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 14 | Supplying and fixing following way, single pole andneutral, sheet steel, MCB distribution board, 240 V,on surface/ recess, complete with tinned copper busbar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthingetc. as required. (But without MCB/RCCB/Isolator)12 way , Double door(Make: Legrand/Schneider/Siemens as per the choice of EIC) |
| 15 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10kA, \\"C\\" curve, miniature circuit breaker suitable forinductive load of following poles in the existing MCBDB complete with connections, testing andcommissioning etc. as required. 32 Amp. DP MCB.(Make Legrand/Schneider/Siemens as per the choice of EIC) |
| 16 | (6-32)Amp. SP MCB. |
| 17 | Supplying and fixing following way, horizontal typethree pole and neutral, sheet steel, MCB distributionboard, 415 V, on surface/ recess, complete withtinned copper bus bar, neutral bus bar, earth bar, dinbar, interconnections, powder painted includingearthing etc. as required. (But withoutMCB/RCCB/Isolator)(Make :Legrand/Schneider/Siemens)6 way (4 + 18), Double door . |
| 18 | Supplying and fixing following rating, four pole, 415 V,isolator in the existing MCB DB complete withconnections, testing and commissioning etc. asrequired. 63 A |
| 19 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10kA, \\"C\\" curve, miniature circuit breaker suitable forinductive load of following poles in the existing MCBDB complete with connections, testing andcommissioning etc. as required. (Make: Legrand/Schneider/Siemens as per the choice of EIC) |
| 20 | Laying and fixing of one number PVC insulated andPVC sheathed / XLPE power cable of 1.1 KV grade offollowing size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 21 | Supplying and making end termination with brasscompression gland and aluminium lugs for followingsize of PVC insulated and PVC sheathed / XLPEaluminium conductor cable of 1.1 KV grade asrequired.i) 4 core X 16 sq.mm. |
| 22 | Installation, Testing and Commissioning of exhaustfan in the existing opening, including making good thedamage, connection, testing, commissioning etc. asrequired. Upto 450 mm sweep |
| 23 | Extra for fixing the louvers/ shutters complete withframe for a exhaust fan of all sizes |
| 24 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt). 120 watt Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till lifeends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external Connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required withMinimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size andCCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).( Make Halonix Model HLSLD-E1-120-CWDL-R01 or equivalent model of Philips/Panasonic/Wipro as per the choice of EIC) Submission of test reports and warranty certificate for atleast five years from OEM is mandatory. |
| 25 | Brush Less Direct Current (BLDC) Fan without Remote :Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al bodyPower Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)(Make: Bajaj/Usha/Orient Electric/Havells as per the choice of EIC) |
| 26 | Supplying and fixing two module stepped typeelectronic fan regulator on the existing modular plateswitch box including connections but excludingmodular plate etc. as required. |
| 27 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |
| 28 | LED Batten light (System lumen efficacy ≥105 <120lm/Watt). Supplying, Installation, Testing & Commissioning ofLED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electricalcircuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder Coated CRCA Sheet Body (Thickness >0.50 mm)18- 22 Watt (Make: Philips/Halonix/Wipro/Panasonic) Submission of test reports and warranty certificate for atleast two years from OEM is mandatory |
| 29 | Installation, Testing and Commissioning of pre-wired,fluorescent fitting / compact fluorescent/ LED fitting ofall types, complete with all accessories and tube/lampetc., including supplying and fixing ball and socketarrangement, 2 Nos. down rods of 20 mm dia X 1.6mm thick steel conduit upto 30 cm length, paintingand wiring the down rods and connections with 1.5sq. mm FRLS/HFFR PVC insulated, copperconductor, single core cable and earthing etc. asrequired. |
| 30 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housingComplete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim 18 watt (Make: Philips/Halonix/Wipro/Panasonic) Submission of test reports and warranty certificate for atleast two years from OEM is mandatory. |
| 31 | HI - WALL SPLIT SYSTEMS:-Supplying , Installation, Testing and Commissioning of AirCooled Hi Wall split type Air conditioners complete withIndoor unit(IDU), Out door unit (ODU), surface / concealedcopper Refrigerant piping with insulation (closed cellelastomeric nitrile rubber tubular pipe section) upto 3 Mtr(IDU to ODU), copper power cable upto 3.5 Mtr (IDU toODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant,wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase ACsupply capable of performing cooling, dehumidification, aircirculation of following capacity with Scroll / rotarycompressor. The system shall be able to deliver 100% ofthe rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressorand Printed Circuit Board (PCB). Must comply : Electricalcable IS 694 or IS 9968 temperature sensing control IS/International Electrotechnical Commission (IEC) 60730,hermetic compressor IS 10617, heat exchanger IS 11329,capacitor IS 2993 and motor IS 12615. Complete as perCPWD specification and IS : 1391 Part II 2023. The systemshall be able to operate up to 50 0C (out door ambienttemperature). Inverter Type - Cooling only2.0 TR with 5 Star BEE Rating (Make Hitachi/Daikin/Mitsubishi Electric/O'General/Voltas as per the choice of EIC) Submission of test reports and warranty certificate for atleast three years from OEM is mandatory. |
| 32 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mmdia including accessories, and providing masonryenclosure with cover plate having lockingarrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 33 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50metre below ground as strip earth electrode, includingconnection/ terminating with G.I. nut, bolt, spring,washer etc. as required. (Jointing shall be done byoverlapping and with 2 sets of G.I. nut bolt & springwasher spaced at 50mm) |
| 34 | Supplying, installation, Testing & Commissioning of the integrated type solar PV lighting system on the existing pole structure, comprising of 30 watt, 6V Mono Passivated Emitter and Rear Contact (PERC) Solar Panel (minimum efficiency 21%), Pulse with modulation (PWM)/Maximum Power point tracking (MPPT) charge Controller in the box with a sleek appearance and a sturdy structure, is weather-proof, and is simple to install, With Lithium- Iron Phosphate Battery (LiFePO4), charging time 8-10 hours, Battery backup time 12 hours (minimum), LED fixture watt 30 watt, Input voltage: 12V DC , Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, IP-66,IK-08, CRI >70 , under voltage and over voltage protection, Electro Magnetic Interference (EMI) Electro Magnetic Compatibility (EMC) As per CISPER 15 A, lenses for beam angle as per Illuminating Engineering Society of North America (IESNA) type I/II/III as per the width of the road and the project requirement, Correlated Colour Temperature (CCT) 5700°K (As per American National Standard Institute (ANSI Bin)) , life time (LED,Driver & electrical circuitary) of 50K hours lamp buring hours till the 70 % of initial Lumen maintained as per LM80 extrapolation IES TM-21-11 report, automatic swich on/off, Alliuminium or Acrylonitrile Butadiene Styrene (ABS body), can be installed on a pole or wall. System lumen efficacy >120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. All as per pre approved by Engineer in-charge complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required, complete with mounting structure for the battery and accessories suitable for withstand wind storm speed as per the site location. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 30 Watt (System lumen efficacy >120 lm/Watt) |
| 35 | Supplying and fixing of 32 mm dia X 2.00 metres longG.I. pipe (medium class) bracket for mounting offluorescent / HPMV / HPSV street light fitting on poleincluding bending the pipe to the required shape, 2nos 40 mm X 3 mm flat iron clamps with nuts, boltsand washer, painting the flat iron with primer and finishpaint etc. as required. |
| 36 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. Above 6.5 Meter and upto 8.0 Meter |
| 37 | Fixing only bulk head /ceiling fitting on wall /ceiling by screws etc. |
| 38 | Supplying and fixing 415V, 125A TPN SFU with sheetsteel enclosure on flat iron/angle iron frame on wallwith nuts bolts etc incl. S & F 3 nos. DIN type HRCfuse on flat iron frame. |
| 39 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts &washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20PVC insulated flexible copper wire 0.5 mt. length |
| 40 | Supply 1.1 KV grade PVC Armoured XLPE insulated AL conductor cable .(Make: Havells/Polycab/Finolex/RR Cabel as per the choice of EIC)i) 4 core X 16 sq.mm. |
| 41 | Supply & delivery of 230 V, 50 Hz, single phase, 40 watts , 9\\" (230 mm) Sweep, speed 1350 rpm (minimum), A.C. Exhaust Fan and class ofinsulation: B, 3 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 650 cmh (minimum) including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. (Make: Bajaj/Usha/Orient Electric/Havells as per the choice of EIC) |
| 42 | Supplying and fixing 240/415 V MCB of Breakingcapacity 10kA & C characteristics on din rail ofexisting DBs and necessary connection. 63 A TP MCB |
| 43 | Supplying & Fixing iron beam fan clamp of two piece type, as per approved specification, fabricated from 40 mm x 9 mm MS sheet flat suitable for beam having flange upto 150 mm wide – (As per Drawing no. 476 of PWD Specification Book – May 1991) |
| 44 | Supply & Delivery of 230 V, 50 Hz, single phase, 85 watts, 18\\" (450mm), speed 1325 rpm (minimum), Bracket Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body with metal back cover. Power Factor not less than 0.9 and minimum air delivery 110 cu.m/min (minimum), including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external Connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. (Make: Bajaj/Usha/Orient Electric/Havells as per the choice of EIC) |
| 45 | Supplying & Fixing GI waterproof type looping cable box size200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, onecompression type brass cable gland for upto 2- core 16 sqmmPVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint. |
| 46 | 7 Mtr. HDG Octagonal Poles in 3mm shaft thickness in MS Condition before Galvanization with Top A/F 70 mm, Bottom A/F 135 mm, Base Plate 225x225x16 mm suitable for wind speed 180 Km/hr. as per IS:875 and 4 Nos. M20x600 “J” Type Foundation Bolts as per EN-8 (Min UTS -600) & Anti -theft locking door arrangement for safety of MCBs, Terminal etc. A)Material grade of shaft shall be of S355 JR as per BSEN 10025 or Equivalent IS: 2062 grade E350 (BR) B)Materials grade of Base Plate shall be E250(BR) as per IS:2062 C)Galvanization as per BSEN ISO:1461 D)Fusion Welding as per ISO 3824 -2:2021 E)All Tests are to done from OEM own -in -house NABL accredited Lab for proper quality control. Valid NABL lab certificate to be uploaded in tender. F) OEM having own in -house galvanization facility for betterment of quality of the product. OEM Factory license to be uploaded in tender. G)Following documents are to be required to process the bills 1)Raw Material Test Certificate of Pole Shaft (IS:2062 grade E -350 BR) Make of HR Coil TATA/ SAIL/ JSW/JSPL/RINL 2)Raw Material Test Certificate of Base Plate (IS:2062grade E -250 BR) Make of Plate TATA/SAIL/JSW/JSPL/RINL 3)Raw Material Test Certificate of bracket Pipe (IS:1239 grade) from any reputed BIS Make. 4) Raw Material Test Certificate of Zinc (Zn) Make Hindustan Zinc (Vedanta)5)Raw Material Test Certificate of Foundation bolts (ENGrade EN 8 and UTS.>600) any reputed BIS ( Make Transrail/Valmont /Bajaj/Skipper ) |
| 47 | 75 Inch- AI lnteractive Flat Panel-Android14Pearl WhiteLED: Type D- LEDAspect Ratio:16:09Resolution: 4K Ultra High Definition with 3840x2160Brightness: 450 nits(Max),350-400nits(Type)Touch: Optical Touch Technology with zero gap writing experience.CPU: 8 CoreRAM : 8 GBROM : 128 GB on boardWi-Fi : Dual Band 2.4 Ghz and 5Ghz (802.11a/b/g/n/ac)Speaker :40 Watts (20 Watts x 2 )Power :75 inch(300W) Make-Ekin or As per direction of E-I-C Warranty 3 Years |
| 48 | AQUAGUARD PRO PURECHILL 80 PSS UV+CUZN. Model : AG PURECHILL 80PSS UV+CuZn.Nanopore Long Life Filters: Provides complete protection from excess chlorine,organic chemicals , bacteria, and viruses-ensuring longer-lasting purity and low maintenance in commercial settings. UV Purification Technology:Effectively neutralizes harmful microorganisms,making water microbiologically safe-ideal for offices, clinics, and institutions.Inbuilt Cooling System with Sturdy Compressor: Delivers instant cold water even during peak usage, making it perfect for shared work spaces, cafeterias, and high-foot fall areas. Durable Steel Body:Built to withstand tough commercial environments while maintaining hygiene and structural strength. PatentedActiveCopperTechnology:Infuses the right amount of copper in every drop,promoting health and making the water suitable for all age groups.CompactAll-in-OneDesign:Combines purification andc ooling in a single unit,eliminating -the need for a separate dispenser- al for space-constraind commrial areas Technology UV Water Storage Tank Capacity 40 L Temperature Option:Ambient,Cold Dimensions MM(WxDxH)660x500x1410 Outer Body Material Front Panel: SS304.and rest CRCA Powder Coated Steel. Storage Tank Material SS304 Number of Purification stages 4 PurificationModule: Sedi-Filter,Chemi Block ,Active Copper Booster Cartridge,Calcium,Magnesium & Zinc & UV e boilling . Netweight 77kg Number of Faucet2(Ambienti &Cold) Water Outlet Temperature at Rated Condition17.C±lC Puification Capacity (Max)120LPH Input Water PressureO.6 to2.0 kg/CM2 Power rating in 'watt(Max)625 ±10 0 to500ppm.(max) Total hardness (max:)300 ppm Turbidity<5NTU Residential Chlorine Content O.2 ppm(max) Iron Content 0.3 ppm(max) SDI(Silt Density Index)<5 Cooling apacity(at Comfort Level) 60LPH Thermal lnsulation for Storage Tank PUF INPUT VOLTAGE 230V AC (50 Hz) Operating Input Voltage 170 230 VAC 50Hz: Operating Temper.10'C to 40'C UV Lamp Power(Watts)8 Watts(2Nos.JRefrigerant Eco-friendly HFCR134 a Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 23, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysSep 25, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender