Tender For Construction Of Critical Care Block At Gh Kalpetta - Wayanad
Tender Value
17.13 Crore
Estimated cost
Bid Submission
22 Sep 2026
14 days left
EMD
5 Lakhs
Bank guarantee accepted
Document Fee
17700
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Wayanad → Kerala
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Of Critical Care Block At Gh Kalpetta - Wayanad
BOQ
| Sl. No. | Item Description |
| 1 | CIVIL WORKS |
| 2 | SITE CLERANCE |
| 3 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared |
| 4 | EARTH WORK EXCAVATION WORKS |
| 5 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed,within a lead of 50 m.All kinds of soil |
| 6 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 7 | Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil |
| 8 | Providing and injecting chemical emulsion for PRE-CONSTRUCTIONAL Anti termite treatment and creating a chemical barrier on top surface of plinth filling, junctions of inside walls and floors, soil along external perimetre using the chemical lmidacloprid emulsifiable (IS 6313 (part2:2013) 30.5% SC mixed with water in 1:499 ratio. The emulsion is spread at 5litre/sqm on top surface of plinth filling, at 1litre/linear metre along the junction of wall and floor and at 2.25litres/linear metre of the plinth wall as per the specifications and directions. (Note: plinth area only shall be measured for payment) |
| 9 | PILE WORKS |
| 10 | Boring, providing and installing bored cast-in-situ reinforced cement concrete piles of grade M-30 (Cement content not less than 400 kg/cum ) of specified diameter and length below the pile cap to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring, with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. all complete, including removal of excavated earth with all lifts and leads (Length of pile for payment shall be measured upto bottom of pile cap).600 mm dia piles |
| 11 | Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge. Single pile above 50 tonne and upto 100 tonne capacityInitial test ( Test load 125 to 250 tonne ) |
| 12 | Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge. Single pile above 50 tonne and upto 100 tonne capacityRoutine test ( test load 75 to 150 tonne ) |
| 13 | Chipping and removing top of R.C.C piles to lines and levels carefully, without damaging the remaining portion and removing the debris up to a distance of 150 m |
| 14 | PCC WORKS |
| 15 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 16 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work above plinth level up to floor five level1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size) |
| 17 | Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources). |
| 18 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work above plinth level to floor five level :1:2:4 (cement : 2 coarse sand (zone-III)derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 19 | RCC WORKS |
| 20 | Providing and laying in position machine batched and machine mixed design mix M 30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge.(Note-Minimum cement content is 350kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design).All work upto plinth level. Concrete of M30 grade with minimum cement content of 350kg/cum |
| 21 | Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more |
| 22 | Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more |
| 23 | Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 24 | Providing and laying in position machine batched and machine mixed design mix M 30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. (Note-Minimum cement content is 350kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design).All work above plinthlevel upto floor V level. Concrete of M30 grade with minimum cement content of 350kg/cum |
| 25 | FORM WORK |
| 26 | Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete |
| 27 | Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform |
| 28 | Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 29 | Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers |
| 30 | Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 31 | Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases) |
| 32 | Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide |
| 33 | Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges |
| 34 | STONE WORKS |
| 35 | DRY RUBBLE MASONRY _ Dry rubble without concrete levelling course masonry with good quality blasted rubble including packing to compactness to lines and levels cost and conveyance of all materials labour charges etc. complete as per direction of Departmental officers at site |
| 36 | MASONRY WORK |
| 37 | Solid block masonry using pre cast solid blocks ( factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part 1 of 1979 for foundation and plinth with thickness 20 cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete |
| 38 | Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etc complete. |
| 39 | Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x10 cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level for 10 cm thick wall in : CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding complete |
| 40 | Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete |
| 41 | PLASTERING |
| 42 | 12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand) |
| 43 | 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand |
| 44 | Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof. |
| 45 | 12 mm cement plaster finished with a floating coat of neat cement of mix:1:4 ( 1 cement : 4 fine sand) |
| 46 | Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self – centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge . (Material shall confirm to ASTM 6063).Floor Joint of 150 mm gap. |
| 47 | Providing and fixing of expansion joint system related with wall joint (internal/ external) location as per drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221-02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to ASTM 6063).Wall Joint of 100 mm gap. |
| 48 | STEEL WORK |
| 49 | Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) |
| 50 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes |
| 51 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 52 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade,5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters andtrusses and including cutting to size and shape wherever required. |
| 53 | Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete |
| 54 | Providing and fixing polycarbonate glass sheet (size, color and design as approved by Engineer-in-charge) 3mm. The sheet shall be fixed using self drilling/self tapping screws of size (2440 mm × 1220 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 55 | DOORS AND WINDOWS |
| 56 | Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately), using good quality Anjili wood /jack wood |
| 57 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of I st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick Fixing with hinges of required size and necessary screws (Note: Hinges and necessary screws hall be paid separately) |
| 58 | Extra for providing ISI marked Stainless Steel butt hinges instead of M.S. pressed butt hinges bright finished of required size with necessary screws. ( Shutter area to be measured) |
| 59 | Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc |
| 60 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. |
| 61 | Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:200x10 mm |
| 62 | Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:100x10 mm |
| 63 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm |
| 64 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper |
| 65 | Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer- in- charge. |
| 66 | Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame. |
| 67 | Providing and fixing to existing door frames.30 mm thick Glas Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS : 14856, including fixing to frames. |
| 68 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.25 mm M.S. laths with 1.25 mm thick top cover |
| 69 | Providing and fixing ball bearing for rolling shutters. |
| 70 | Extra for providing mechanical device chain and crank operation for operating rolling shuttersExceeding 10.00 sqm and upto 16.80 sqm in the area |
| 71 | Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded ) (overall area of door shutter to be measured):Rectangular or square |
| 72 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately) |
| 73 | Supplying and fixing of 2mm thick lead sheet on masonry, wooden, RCC surfaces, etc. using specially treated screws. The lead sheet should be covered with 1 mm thick laminated plywood of 8mm thick using necessary adhesive, treated screws, etc. The work should meet the AERB standards, Plated on necessary areas and up o necessary height as per the design or the direction of the engineer in charge. Also the corners, joints are covered with lead strips of necessary width, The rate inclusive of labour, materials, the necessary frame work, strips, studs, adhesives, shifting charges, etc.Area 6*3m = 18 Sqm, Add 5% Wastage= 18.9 Sqm |
| 74 | Providing and fixing 1 mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces |
| 75 | Fixing standard steel glazed doors, windows and ventilators in walls, including fixing of float glass panes with glazing clips and special metal-sash putty of approved make, or metal beading with screws, (only steel windows, glass panes cut to size and glazing clips or metal beading with screws, shall be supplied by department free of cost.Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 ( 1 Cement : 3 coarse sand: 6 graded stone aggregate 20 mm nominal size). |
| 76 | Supply of Glass to glass door lock for toughened glass door of 12mm thick with weight upto 200kg |
| 77 | Supply of stainless steel handle for toughened glass door, H- type of size 450 mm and 25 mm dia with satin finish of reputed make . |
| 78 | Providing and installing in position PROPRIETARY FIRE DOORS of approved make Tata Pravesh or equivalent with Metal frame filled with Rockwool. The shutters shall be of Pressed Metal shutter with or without Vision panels finished with approved Powder coated as per the detail drawings & manufacturers specifications. The fire ratings shall be as called for and confirming to BIS standards as per the detail drawings & manufacturers specifications. This includes providing and fixing all brush finished iron mongery like locks, handles, tower bolts, door closer etc of Geze/Dorma as indicated in the detail drawing, and confirming to BIS standards as per the detail drawings & manufacturers specifications. This includes providing and fixing all brush finished iron mongery like locks, handles, tower bolts, door closer etc of Geze/Dorma as indicated in the detail drawing. Typical Uninsulated Door specifications 120Mins. Un Insulated fire door as per IS 3614 - Powder coated Pressed galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall be tested to IS 3614 part 2/ISO 834-1 Part 1/BS 476 Part 20 & 22, CBRI/Spectra, for maximum rating of 120mins, in latched /unlatched condition (if used with deadbolts and pull handles). Labelled fire doors shall be with fire rated hardware and vision panel (if any) all as a complete assembly. Manufacturer test certificate shall cover sizes of all doors supplied, deviation in sheet thickness other than what is mentioned in the BOQ are not allowed. Door frame must be single rebate grooved profile of size 143 x 58mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be mitered only. Frames shall be field assembled with self tabs. Bolted & butted joints are not acceptable. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frame should be filled with Mineral wool/ Fire rated PUF as recommended by the manufacturer or engineer in charge. Door leaf shall be minimum 46mm thick fully flush double skin door, Un-insulated with or without vision lite. Door leaf shall be manufactured from 1.20mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware of make Geze/Dorma. The infill material shall be resin bonded honeycomb core. The edges should be interlocked with a bending radius of 1.4mm, without any tack welding on edges. Vision lite wherever applicable should be 6mm clear borosilicate fire rated glass of make Saint Gobain/ Schott as per manufacturers recommendation with a clip-on arrangement.Door and frames shall be finished Pure Polyester Powder coated and shall have passed minimum 500 hours of salt spray test. Rate shall include supply and installation of frame and shutter as a complete assembly including hardware. Fire Door of size1*2.1M with Metal frame of size 143x58mm with pressed metal single leaf shutter of size 46mm finished with Powder coated of approved colour and shade as per the Project Consultants approval with 2 Hours Fire rating. Rate of providing ironmongery as mentioned/recommended by manufacturer/engineer in charge. All fittings are of Brushed steel finish of Geze or approved make as per detail drawing. Ball bearing butt hinge, SS304, of size 100 x 75 x 3mm with screws in SSS, Panic Hardware, Door Closer, SSS finish, Vision Panel. |
| 79 | Providing and installing in position PROPRIETARY FIRE DOORS of approved make Tata Pravesh or equivalent with Metal frame filled with Rockwool. The shutters shall be of Pressed Metal shutter with or without Vision panels finished with approved Powder coated as per the detail drawings & manufacturers specifications. The fire ratings shall be as called for and confirming to BIS standards as per the detail drawings & manufacturers specifications. This includes providing and fixing all brush finished iron mongery like locks, handles, tower bolts, door closer etc of Geze/Dorma as indicated in the detail drawing, and confirming to BIS standards as per the detail drawings & manufacturers specifications. This includes providing and fixing all brush finished iron mongery like locks, handles, tower bolts, door closer etc of Geze/Dorma as indicated in the detail drawing. Typical Uninsulated Door specifications 120Mins. Un Insulated fire door as per IS 3614 - Powder coated Pressed galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall be tested to IS 3614 part 2/ISO 834-1 Part 1/BS 476 Part 20 & 22, CBRI/Spectra, for maximum rating of 120mins, in latched /unlatched condition (if used with deadbolts and pull handles). Labelled fire doors shall be with fire rated hardware and vision panel (if any) all as a complete assembly. Manufacturer test certificate shall cover sizes of all doors supplied, deviation in sheet thickness other than what is mentioned in the BOQ are not allowed. Door frame must be single rebate grooved profile of size 143 x 58mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be mitered only. Frames shall be field assembled with self tabs. Bolted & butted joints are not acceptable. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frame should be filled with Mineral wool/ Fire rated PUF as recommended by the manufacturer or engineer in charge. Door leaf shall be minimum 46mm thick fully flush double skin door, Un-insulated with or without vision lite. Door leaf shall be manufactured from 1.20mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware of make Geze/Dorma. The infill material shall be resin bonded honeycomb core. The edges should be interlocked with a bending radius of 1.4mm, without any tack welding on edges. Vision lite wherever applicable should be 6mm clear borosilicate fire rated glass of make Saint Gobain/ Schott as per manufacturers recommendation with a clip-on arrangement.Door and frames shall be finished Pure Polyester Powder coated and shall have passed minimum 500 hours of salt spray test. Rate shall include supply and installation of frame and shutter as a complete assembly including hardware. Fire Door of size 1.2X2.1m with Metal frame of size 143x58mm with pressed metal single leaf shutter of size 46mm finished with Powder coated of approved colour and shade as per the Project Consultants approval with 2 Hours Fire rating. Rate of providing ironmongery as mentioned/recommended by manufacturer/engineer in charge. All fittings are of Brushed steel finish of Geze or approved make as per detail drawing. Ball bearing butt hinge, SS304, of size 100 x 75 x 3mm with screws in SSS, Panic Hardware, Door Closer, SSS finish, Vision Panel. |
| 80 | Providing and installing in position PROPRIETARY FIRE DOORS of approved make Tata Pravesh or equivalent with Metal frame filled with Rockwool. The shutters shall be of Pressed Metal shutter with or without Vision panels finished with approved Powder coated as per the detail drawings & manufacturers specifications. The fire ratings shall be as called for and confirming to BIS standards as per the detail drawings & manufacturers specifications. This includes providing and fixing all brush finished iron mongery like locks, handles, tower bolts, door closer etc of Geze/Dorma as indicated in the detail drawing, and confirming to BIS standards as per the detail drawings & manufacturers specifications. This includes providing and fixing all brush finished iron mongery like locks, handles, tower bolts, door closer etc of Geze/Dorma as indicated in the detail drawing. Typical Uninsulated Door specifications 120Mins. Un Insulated fire door as per IS 3614 - Powder coated Pressed galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall be tested to IS 3614 part 2/ISO 834-1 Part 1/BS 476 Part 20 & 22, CBRI/Spectra, for maximum rating of 120mins, in latched /unlatched condition (if used with deadbolts and pull handles). Labelled fire doors shall be with fire rated hardware and vision panel (if any) all as a complete assembly. Manufacturer test certificate shall cover sizes of all doors supplied, deviation in sheet thickness other than what is mentioned in the BOQ are not allowed. Door frame must be single rebate grooved profile of size 143 x 58mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be mitered only. Frames shall be field assembled with self tabs. Bolted & butted joints are not acceptable. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frame should be filled with Mineral wool/ Fire rated PUF as recommended by the manufacturer or engineer in charge. Door leaf shall be minimum 46mm thick fully flush double skin door, Un-insulated with or without vision lite. Door leaf shall be manufactured from 1.20mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware of make Geze/Dorma. The infill material shall be resin bonded honeycomb core. The edges should be interlocked with a bending radius of 1.4mm, without any tack welding on edges. Vision lite wherever applicable should be 6mm clear borosilicate fire rated glass of make Saint Gobain/ Schott as per manufacturers recommendation with a clip-on arrangement.Door and frames shall be finished Pure Polyester Powder coated and shall have passed minimum 500 hours of salt spray test. Rate shall include supply and installation of frame and shutter as a complete assembly including hardware. Fire Door of size 1.8*2.1M with Metal frame of size 143x58mm with pressed metal single leaf shutter of size 46mm finished with Powder coated of approved colour and shade as per the Project Consultants approval with 2 Hours Fire rating. Rate of providing ironmongery as mentioned/recommended by manufacturer/engineer in charge. All fittings are of Brushed steel finish of Geze or approved make as per detail drawing. Ball bearing butt hinge, SS304, of size 100 x 75 x 3mm with screws in SSS, Panic Hardware, Door Closer, SSS finish, Vision Panel. |
| 81 | ALUMINIUM WORKS |
| 82 | Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 +/- 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh and silicon sealent shall be paid separately) Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Two track two panels sliding window made of (small series) frame 52 x 44 mm & sash 32 x 60 mm both having wall thickness of 1.9 +/- 0.2 mm and single glazing bead of appropriate dimension. (Area of window upto 1.75 sqm) |
| 83 | Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 +/- 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extrudedglazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap betwee frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh and silicon sealent shall be paid separately) Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Two track two panels sliding window made of (big series) frame 67 x 50 mm & sash 46 x 62 mm both having wall thickness of 2.3 +/- 0.2 mm and single glazing bead / double glazing bead of appropriate dimension . (Area of window above 1.75 sqm upto 2.50 sqm). |
| 84 | Providing and fixing casement handle made of zinc alloyed (white powder coated) for uPVC casement window with necessary screws etc. complete. |
| 85 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mmthickness (weight not less than 10kg/sqm) |
| 86 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 87 | For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 88 | Providing and fixing Brass100 mm mortice latch and lock with 6 levers without pair of handles ( best make of approved quality ) for aluminum doors including necessary cutting and making good etc. complete |
| 89 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides |
| 90 | Providing and fixing frosted film in the fixed glass etc. Complete as per the direction of departmental officers |
| 91 | Providing and fixing glazing in door, window, ventilator shutters and partitions etc. with EPDM rubber /neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): toughened glass of 6 mm thickness. |
| 92 | Providing and fixing radiation shielding lead glass of size 1200 × 600 mm, 10 mm thick, having 2.1 mm Pb equivalence, duly tested and certified for use in X-ray rooms, complete with factory-fabricated hardwood frame internally lined with 2.1 mm thick lead sheet to ensure radiation continuity. The work shall include providing a minimum 25 mm lead overlap at all joints with the adjoining lead lining, neoprene gasket packing, necessary fasteners, sealing, finishing with approved polish/paint, and complete installation as per directions of the Engineer-in-charge. |
| 93 | TILE WORKS |
| 94 | Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand):Dark shade pigment using ordinary cement |
| 95 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm. |
| 96 | Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm |
| 97 | Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm |
| 98 | Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete. |
| 99 | Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg). including filling /grouting and finishing complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm |
| 100 | Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in Charge and finished smooth.Granite Stone of approved shade |
| 101 | Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Glazed Vitrified tiles Matt/Antiskid finish of size Size of Tile 600 x 600 mm |
| 102 | Providing and laying C.C pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewatering process and finally finished by floating brooming withwire brush etc. complete as per specifications and directions of Engineer-in-charge (The panel shuttering work shall be paid for separately)(Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately) |
| 103 | Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide |
| 104 | HVAC DUCT-Supply and installation of Fire stop mortar system with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, for openings in floors or slabs after passing service lines like Metal Pipes. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2- 57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration Time- history method and VERTEQII for seismic zone 4. The product shall be age tested as per Dafstb and DIBT standards. The product shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96. The product shall be UL listed & classified and shall bear the UL approval logo on the packing. .Engineering Judgements (EJs) should be used for situations where a tested system is not available. The application to be executed by manufacturer approved firestop contractor.. Assumed 15% Penetrants Occupancy. |
| 105 | FIRE STOP MORTAR SYSTEM-Supply and installation of Fire stop mortar system with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, for openings in floors or slabs after passing service lines like Metal Pipes. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2- 57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time- history method and VERTEQII for seismic zone 4. The product shall be age tested as per Dafstb and DIBT standards. The product shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96. The product shall be UL listed & classified and shall bear the UL approval logo on the packing. .Engineering Judgements (EJs) should be used for situations where a tested system is not available. The application to be executed by manufacturer approved firestop contractor.. Assumed 15% Penetrants Occupancy. |
| 106 | ELECTRICAL/ELV DUCT-Supply and installation of Fire Barrier mortar with minimum 2 (two) hours fire rating when tested in accordance with UL 1479 standards, for fire rated vertical openings in floors or slabs and floors made of concrete, masonry,metal, gypsum partition, after passing service lines like Cable,Cable trays, Bus Duct or Metal pipes. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2 57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time history method and VERTEQII for seismic zone 4. Expanding fire stop foam with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, shall be used to seal areas that are highly dense or are not accessible and cannot be sealed with fire stop mortar properly.The expanding foam shall expand minimum seven times its volume to fill the cavity at the time of dispensing the material and shall fully cure within two minutes after dispensing. The expanding foam shall also be repenetratable. The products shall be age tested as per Dafstb and DIBT standards. The products shall carry test certificate for mold resistance rating of as determined by ASTM G21-96. The products shall be UL listed & classified and shall bear the UL approval logo on the packing.Engineering Judgements (EJs) should be used for situations where a tested system is not available. The application to be executed by manufacturer approved firestop contractor. |
| 107 | MGPS DUCT-Supply and installation of Fire stop mortar system with minimum 2 hours fire rating when tested in accordance with UL 1479 standards for horizontal openings in floor or slabs after passing plastic or metal pipes. The mortar shall be a light weight cementitious products and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing)as per Part 2-57: Test for vibration- Time -history method andVERTEQII for seismic zone 4 with fire intumescent sealants to provide minimum 2 hours fire rating when tested in accordance with UL1479 standards. The products shall be age tested as per Dafstb and DIBT standards. The products shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96. The products shall be UL listed and classified and shall bear the UL approval logo on the packing. The installations shall be done by manufacture certified contractor in accordance with the manufacture guidelins. The contractor needs to provide complete installation report through software for inspection purpose. Engineering Judgements(EJs) should be used for situations where a tested system is not available. |
| 108 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 109 | GLAZING AND CLADDING WORKS |
| 110 | Design supply & installation of suspended Spider Glazing system designed to withstand the wind pressure as per IS 875 (Part-III). The Suspended System held with Spider Fittings of SS-316 Grade Steel of approved manufacturer with glass panel having 12 mm thick clear toughened glass held together with SS- 316 Grade Stainless steel Spider & bolt assembly with laminated glass fins 21 mm thick. The Glass fins and glass panel assembly shall be connected to Slab/beams by means of SS- 316 Grade stainless steel brackets & Anchor bolts and at the bottom using SS channel of 50x25x2mm using fastener & anchor bolts, non staining weather sealants of approved make, Teflon/ nylon bushes and separators to prevent bi-metallic contacts, all complete to perform as per specification and approved drawings. The complete system to be designed to accommodate thermal expansion & seismic movements etc. The joints between glass panels (6 to 8 mm) and gaps at the perimeter & in U channel of the assembly to be filled with non staining weather sealant, so as to make the entire system fully water proof & dust proof. The rate shall include all design, Engineering and shop drawing including approval from structural designer, labour, T&P, scaffolding, other incidental charges including wastage, enabling temporary services all fitting fixers nut bolts, washer, Buffer plates, fastener, anchors, SS channel laminated glass etc. all complete. For the purpose of payment, actual elevation area of Glazing including thickness of joints and the portion of Glass panel inside the SS channel shall be measured. |
| 111 | FALSE CEILING |
| 112 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board |
| 113 | Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main \\"T\\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross \\"T\\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \\"T\\" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross \\"T\\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \\"T\\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.12.5 mm thick fully Perforated Gypsum Board tile made from plaster board having glass fibre conforming to IS: 2095 Part I, of size 595x595 mm, having perforation of 9.7x9.7 mm at 19.4 mm c/c with centre borders of 48 mm and the side borders of 30 mm, backed with non woven tissue on the back side , having as NRC ( Noise Reduction Co efficient) of 0.79, with 50 mm resin bonded glass wool backing. |
| 114 | CURTAIN WORKS |
| 115 | Supplying and laying polyester, washable and stain free cloth(Bio-Active fabric washable germ free suitable for sterile area) curtain curtain system with maximum curtain curtain cloth height 230 cm(top 30 cm white colour net and 200cm light blue color as per approval) stitching with stifiner tape, pleats, ironing and laying around each bed using PVC runner with hooks & stopper for hanging/sliding etc. as per the direction of engineer in charge including conveyance to site, laying in line and level, sealing all cutting in false ceiling with powder coated MS cup, all leads and lifts including all labour charges etc. complete. (unpleated length of the cloth measurement will be considered for payment also the bottom and top foldings will not be considered in cloth measurement)/ supplying and fixing powder coated 20mm dia. GI round tube hanging support of required length(app. length 1.10m) one end fixing from slab by using 6mm dia expansion bolt at a distance not more than 2m, c/c down end fixed to powder coated aluminium channel frame 45 x 20mm x 1mm thick section by using SS screw as per the direction of engineer in charge including conveyance. |
| 116 | Providing and fixing of Horizontal roller blinds width 100 mm regular quantity made from 100 % polyster/Fibre yarn coated with fade resistant polymer to ensure complete opaquety with zero light transmittance, having suitable coating on exterior, including all fixtures and fittings complete in all respect as per design and instruction of Engineer in-charge and as per site conditions. The colour will be approved by the competent authority. and inclusive of all labour charges. |
| 117 | PAINTING |
| 118 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 119 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm |
| 120 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 121 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerin charge. The product performance shall carry guarantee for 10 years against any leakage.For horizontal surface one coat @1.10 kg per sqm. |
| 122 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerin charge. The product performance shall carry guarantee for 10 years against any leakage.For vertical surface two coats @0.70 kg per sqm |
| 123 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 124 | Finishing walls with water proofing cement paint of required shade:New work (Two or more coats applied @ 3.84 kg/10 sqm) |
| 125 | PLUMBING AND SANITARY FITTINGS |
| 126 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid |
| 127 | Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required:Single half stall urinal with 5 litre PVC. automatic flushing cistern |
| 128 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 129 | Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.Waste coupling 31 mm dia of 79 mm length and 62 mm breadth weighing not less than 45 gms |
| 130 | Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms |
| 131 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality and colour450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm. weighing not less than 170 gms |
| 132 | Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge. |
| 133 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore |
| 134 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:20 mm nominal bore |
| 135 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore |
| 136 | Providing and fixing PTMT grating of approved quality and colour. Circular type100 mm nominal dia |
| 137 | Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2 |
| 138 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10Kgf/cm2 - External work - Exposed on wall |
| 139 | Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall |
| 140 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.15 mm nominal dia pipes |
| 141 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal dia pipes |
| 142 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.32 mm nominal dia pipes |
| 143 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1 .00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 75 mm pipe 6 Kgf/cm2 |
| 144 | Providing and fixing PVC pipes, fittings, including fixing the pipe with clamps at 1.00 m spacing. this includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per the direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 75 mm pipe 4 kgf/cm2 |
| 145 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Vent cowl |
| 146 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank :ISI 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 147 | Providing and fixing PTMT extension nipple for water thank pipe, fittings of approved quality and colour .20 mm nominal bore, weighing not less than 40 gms |
| 148 | Constructing soak pit 1.20x1.20 m filled with brickbats including S.W. drain pipe 100 mm diameter and 1.20 m long complete as per standard design. |
| 149 | Providing and fixing of wall mounted foot operated handwash sink with back splash (S.S 304 grade top 1.5mm thick and covering 1mm). The rate includes material, carriage, shifting up to 5th floor, placing, labour charges, etc. including tap, . the placement as per the direction of engineer in-charge. |
| 150 | Providing and fixing PTMT Bottle Trap for Wash basin and sink.Bottle trap 38 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the center of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 263 gms |
| 151 | Providing and fixing uplasticised PVC connection pipe with brass unions: 45 cm length15 mm nominal bore |
| 152 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steeel bar conforming to IS:1786, having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufactures permanent identification mark to be visible even after fixing including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1cement: 3 coarse sand: 6 graded stone aggregate 20 mm nominal size) Complete as per design |
| 153 | Providing and fixing in position Pre-cast R.C.C. manhole cover and frame of required shape and approved quality. L D - 2.5Rectangular shape 600x450 mm internal dimensions |
| 154 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall25 mm nominal dia pipes |
| 155 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall32 mm nominal dia pipes |
| 156 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Surgeon type wash basin of size 660x460 mm with a pair of 15 mm C.P. brass pillar taps with elbow including operated levers |
| 157 | Flexible (coil shaped) PVC waste pipe for sink and wash basin 40 mm dia with length not less than 700 mm i/c PVC waste fittings. |
| 158 | Providing and fixing PVC pipes includings jointing of pipes with one step pvc solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer in Charge. 150 mm dia 6 Kgf/cm2 |
| 159 | Supplying and placing of 5000 Litre 1mm thick stainless steel water tank of 1750mm dia , 2600mm height, Stainless steel mounted stand around 180kg and grade of ASTM A240 gr.304/ SS316 BA/2B as per the direction of Engineer in-charge. The rate inclusive of all the transportation, Steel stand support, loading and unloading charges, fixing charges, Labour charges, etc. Nothing shall be additionally paid in this item |
| 160 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge Concealed work, including cutting chases and making good the wall etc. 15 mm pipe 10kgf/cm2 |
| 161 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 32 mm pipe 10Kgf/cm2 |
| 162 | Providing and fixing PTMT grating of approved quality and colour. Rectangular type with openable circular lid150 mm nominal size square 100 mm diameter of the inner hinged round grating |
| 163 | Providing and fixing Single tap Scrub sink - SS 304 size L30 x W16 x D15" with including supply of Elbow tap and dispenser complete as per the direction of engineer in charge. |
| 164 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia Elbow |
| 165 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement-110 mm dia Door Elbow |
| 166 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm dia Bend |
| 167 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes including jointing with PVC solvent cement 110x110x110 mm dia Tee |
| 168 | Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x110x110 mm dia Door tee |
| 169 | Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia Vent cowl |
| 170 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm Dia Y |
| 171 | Providing and fixing a Disabled Toilet complete set comprising white wall-mounted Matrix set (WB 46X36 with one pair mounting brackets, EWC and cistern complete with all necessary fittings, seat cover, one number hinged rail 76cm and 4 nos of grab rails 60cm) and accessories. The item shall include providing and fixing all brackets, expansion sleeves, stainless steel/brass bolts, screws, nuts, washers, etc., including cutting and making good the walls wherever required, complete in all respects as per manufacturer specifications and as directed by the Engineer-in-Charge. |
| 172 | Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm Sand Cast Iron P or S trap, 10 litter low level white P.V.C.flushing cistern, including flush pipe, manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever require:Stainless Steel AISI-304 (18/8) orissa pattern W.C. pan of size 585x 480 with flush pipe and integrated type foot rests |
| 173 | Constructing brick masonry chamber for underground C.I. inpection chamber and bends with bricks in cement mortar 1:4 ( 1 cement: 4 coarse sand) C.I.cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23kg and weight of frame 15 kg), R.C.C top slab with 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:5:10 (1 cement: 5 fine sand: 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand) finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design: Inside dimensions 500x700 mm and 45 cm deep for pipe line with one or two inlets:With common burnt clay F.P.S (non modular) bricks of class designation 7.5 |
| 174 | Providing and fixing P-trap for water closet of approved make water seal, including jointing with pipe using necessary rubber gasket / solvent cement, cutting wherever required, complete in all directed by the Engineer-in-Charge. |
| 175 | Providing and fixing in position Pre-cast R.C.C. manhole cover and frame of required shape and approved quality.L D - 2.5Square shape 450 mm internal dimensions |
| 176 | Providing and fixing square-mouth S.W. gully trap class SP -1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: 180x150 mm size P typeWith common burnt clay F.P.S (non modular) bricks of class designation 7.5 |
| 177 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.110 mm diameter |
| 178 | Providing and fixing on wall face unplasticised- PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion Coupler110 mm |
| 179 | SIGNAGES |
| 180 | Design, providing and fixing Digital Printed vinyl signage boards with transparent 3mm acrylic Sheet with 4 nos. SS Studs with lettering of size 15x45 cm. Complete as per the per the direction of Engineer in charge. <br> |
| 181 | NAME BOARD ACP SHEET WITH MULTIWOOD LETTERING : Design, Supplying and fixing Name Board as per the technical specifications given -1 Inch GI pipe frame (16Guage) for Frame (Size proportional), Primer Paint & Black Painted Pipes for Frame.,5mm ACP sheets (Aluminum Composite Panel) for Box area, 18mm thick Multi wood Lettering for Name Board as approved by Engineer in charge. For Measurement purpose, only area of ACP sheet to be measured |
| 182 | BUILDING PERMIT |
| 183 | Preparation of civil drawings, submission of drawings to LSGD/Municipality/Corporation/ concerned authority and obtaining approval for the same, complete excluding the Departmental Fee for the Permission and Ownership etc. Any statutory payment obligation shall be the sole responsibility of the client. |
| 184 | ELECTRICAL WORKS |
| 185 | POINT WIRING |
| 186 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B |
| 187 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C |
| 188 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group B |
| 189 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 190 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 191 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. WALL FAN points. |
| 192 | CIRCUIT WIRING |
| 193 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire |
| 194 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 195 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 196 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit including conduit and all accessories as required for complete installation and instructed by engineer in charge/consultant. 1Cx50sq.mm Copper Flexible Cable |
| 197 | SWITCH , SOCKET AND METAL BOXES |
| 198 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 199 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 200 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 201 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 202 | Supply & fixing Computer points with 3 nos 3 pin 5/6A socket with 2no.5/6A switch with modular front plate and cover on surface/recess, including proving and fixing suitable size GI boxes, its interconnections etc. as required complete. |
| 203 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 204 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) |
| 205 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module |
| 206 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module |
| 207 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 208 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 209 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required. |
| 210 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Bell push |
| 211 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outlet |
| 212 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required |
| 213 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface |
| 214 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module |
| 215 | POWER CIRCUITRY |
| 216 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 217 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 218 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 WAY(4+12), DOUBLE DOOR |
| 219 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 220 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 Way(4+24), Double door |
| 221 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way(4+24), Double door |
| 222 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)6 Way (4+18), Double door |
| 223 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 Way (4+12) Double door |
| 224 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door |
| 225 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door |
| 226 | Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 227 | Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 125 Amp, 36 KA |
| 228 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole |
| 229 | Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps |
| 230 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker with overcurrent protection (RCBO), having a sensitivity current up to 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A-40A, 4P, 30mA. |
| 231 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker with overcurrent protection (RCBO), having a sensitivity current upto 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A-40A, 4P, 100mA |
| 232 | Supplying and fixing 40A / 63A, TP MCB, 415 Volts, \\"C\\" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc as required. |
| 233 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 234 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 235 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 236 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps |
| 237 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 238 | Supply, installation, testing and commissioning of SMC FRP rectangular junction Box (200 x 140 x 95mm) of approved make with MCB rail suitable for providing connection for fixing four pole isolator as per the direction of Engineer in charge. (Make: Sintex) |
| 239 | Supplying and fixing FP CRCA sheet steel enclosure with provision to mount MCB/Isolator/RCCB/RCBO and other modular devices on surface/ recess complete with connections, testing and commissioning etc. as required. |
| 240 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 40amps DP Isolator complete with connections, testing and commissioning etc. as required. |
| 241 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required |
| 242 | Supply, installation, testing and commissioning of following rating Change Over Switch conforming to IEC 60947-3, IS/IEC 60947 -3, with CRCA sheet powder coated enclosure, complete with terminals and all accessories etc as required and as instructed by engineer in charge and making good any damages made during installation. 32/40A, 415V, FP COS |
| 243 | Supplying and fixing Cable End Boxes (IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with testing and commissioning etc. as required. For 10 way, Double door SPN MCBDB |
| 244 | Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 4 way, Double door TPN MCBDB |
| 245 | Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 6 way, Double door TPN MCBDB |
| 246 | Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 8 way, Double door TPN MCBDB |
| 247 | Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for tripple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 248 | PANELS |
| 249 | Main Panel:-Supply, Installation, Testing and Commissioning of 415 V 50Hz LT Switch board OEM Design Verified Assembly Panel complying to IEC 61439 Part 1 & 2.The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type , Ingress Protection rating shall be IP42 & Impact protection shall be IK10 with cable entry facility at top or bottom (as per site condition),cable alley, switchgear compartment, meter chamber, C.T chamber, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum upto 1800mm from the finished floor level. Form of construction of panel shall be 3B or above. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. INCOMER: 1 Nos 630 A 36 kA 4P MCCB EDO MP based with 3O/C 1E/F Releases & S/T O/V relay with CT at neutral earthing conductor, 1 Nos 700A 4P Contactor, 1 Set RYB Indication Lamp with control fuses and switches, 1 No. Multi-function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring V,A,F,KW,KVA,PF,THD. CT and necessary accessories , 1 no. of Under Voltage/Over Voltage Relay. 1 no. Class B & Class C/ Class 1 & Class 2 Surge arrestor device with necessary HRC fuse for protection of same. OUTGOINGS: 1 No 250 A, 36 kA, 4P MCCB, TM based, 1No 320A, 36kA, 4P MCCB, TM based, 4 No 160A, 36kA 4P MCCB, TM based, 2 Nos 125 A 36 kA 4P , MCCB, MP based, 1 Nos 250 A TPN, Isolator ON-OFF-TRIP Lamps with 2A fuse -9 sets Surge Protection Devices for Main Panel: Type 1-2 sets, 630A 415V,50kA best conductivity Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. All Breakers in the incoming side shall be with LSIG protection and all the breakers in the outgoing side shall be with LSI protection. ON/OFF/TRIP indicators shall be provided for all the breakers (incoming & outgoing). Necessary spreader terminals, extended ROH, phase barriers, shrouding etc shall be as per the rules |
| 250 | LIFT PANEL :Fabrication, supply, erection, testing and commissioning of floor or wall mounting dust and vermin proof, cubicle type, front operated MV panel board as per IS 8623 - CPRI Certified made out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalized complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components as shown in the schematic drawing. The panel shall be with Top/bottom entry to receive incoming & outgoing. Providing all connections and interconnections as required and providing all accessories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. Incomer - 100A 16kA TM based MCCB , 125A , 433V, 25kA best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc. complete as required. Multifunction meter having multiline LED display with following parameters -Phase wise instantaneous and Average values?Voltage, Current, Power Factor, Phase wise instantaneous and Average values?Active Power, Reactive Power lead & lag, Apparent Power, Import & Export Cumulative values? Active Energy, Reactive Energy lead & lag, Apparent Energy, PF for 3 phases and average, Instantaneous Frequency, Total Harmonics Distortion ? Phase wise Voltage and Phase wise Current - 1 Set RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoings: 63A 100mA 4P RCBO - 1 nos. , 25A 30mA DP RCBO 1 nos., 6A SP MCB- 3Nos |
| 251 | SMDB-1 (8 WAY) - Supply, installation, Testing and Commissioning of factory fabricated OEM 415 V 50 Hz 4 way complying to IEC 61439 part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wire meter chamber with all meters & indicating lamps, Aluminium bus bar, neutral link, DIN bar with all accessories etc, complete with necessary control wiring and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper. All copper joints shall be tinned. Knock outs of proper diameter shall be provided on gland plates. The height of the operating handle of switch gear shall be minimum 300 mm and maximum upto 1800mm from the finished floor level complete as per the directions of engineer in charge. Incomer -1 no. 160 A 36 kA TP MCCB, Outgoing: 5Nos 63A TP 25 kA MCCB, 3 NOS 25A 25kA TP MCCB |
| 252 | SMDB- UTILITY (4 WAY) - Supply, installation, Testing and Commissioning of factory fabricated OEM 415 V 50 Hz 4 way complying to IEC 61439 part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wire meter chamber with all meters & indicating lamps, Aluminium bus bar, neutral link, DIN bar with all accessories etc, complete with necessary control wiring and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper. All copper joints shall be tinned. Knock outs of proper diameter shall be provided on gland plates. The height of the operating handle of switch gear shall be minimum 300 mm and maximum upto 1800mm from the finished floor level complete as per the directions of engineer in charge. Incomer -1 no. 160 A 36 kA TP MCCB, Outgoing: 1Nos 125A TP 25 kA MCCB, 2Nos 63A 25kA TP MCCB, 1 Nos 40A 25kA TP MCCB. |
| 253 | HVAC SMDB (12 WAY) - Supply, installation, Testing and Commissioning of factory fabricated OEM 415 V 50 Hz 4 way complying to IEC 61439 part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wire meter chamber with all meters & indicating lamps, Aluminium bus bar, neutral link, DIN bar with all accessories etc, complete with necessary control wiring and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper. All copper joints shall be tinned. Knock outs of proper diameter shall be provided on gland plates. The height of the operating handle of switch gear shall be minimum 300 mm and maximum upto 1800mm from the finished floor level complete as per the directions of engineer in charge. Incomer -1 no. 320 A 36 kA TP MCCB, Outgoing: 4 Nos 80A 25kA TP MCCB, 8 Nos 63A TP 25 kA MCCB. |
| 254 | UPS SMDB (4 WAY) - Supply, installation, Testing and Commissioning of factory fabricated OEM 415 V 50 Hz 4 way complying to IEC 61439 part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wire meter chamber with all meters & indicating lamps, Aluminium bus bar, neutral link, DIN bar with all accessories etc, complete with necessary control wiring and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper. All copper joints shall be tinned. Knock outs of proper diameter shall be provided on gland plates. The height of the operating handle of switch gear shall be minimum 300 mm and maximum upto 1800mm from the finished floor level complete as per the directions of engineer in charge. Incomer -1 no. 160 A 36 kA TP MCCB, Outgoing: 3 Nos 50A 25 kA TP MCCB, 1 No 40A kA TP MCCB Details as shown in SLD. |
| 255 | CABLE SUPPLY AND LAYING |
| 256 | Supply of 400 sqmm 3.5 core PVC/XLPE insulated armoured cable with aluminium conductors for working voltages up to and including 1100 volts conforming IS 1584/part I/1988 for PVC IS 7098 part I for XLPE |
| 257 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm |
| 258 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm |
| 259 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 400 sq mm |
| 260 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm |
| 261 | Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 120 sqmm |
| 262 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 120 sq mm |
| 263 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm |
| 264 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm |
| 265 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp |
| 266 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp |
| 267 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp |
| 268 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 269 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 270 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 6 sq mm with factory made clamp |
| 271 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 4 sq mm with factory made clamp |
| 272 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required |
| 273 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp |
| 274 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 4 sq mm with factory made clamp |
| 275 | CABLE TERMINATION |
| 276 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm) |
| 277 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm) |
| 278 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm) |
| 279 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm) |
| 280 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm) |
| 281 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 282 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 283 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm) |
| 284 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 285 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 286 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 6 sq. mm (22mm) |
| 287 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3C X 4 sq. mm (22mm) |
| 288 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm) |
| 289 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 4 sq. mm (19mm) |
| 290 | CABLE TRAY |
| 291 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness |
| 292 | Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.600 mm width X 50 mm depth X 2.0 mm thickness |
| 293 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness |
| 294 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness |
| 295 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 296 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X50 mm depth X 2.0 mm thickness |
| 297 | Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.450 mm width X 50 mm depth X 2.0 mm thickness |
| 298 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness |
| 299 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness |
| 300 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness |
| 301 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 302 | Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness |
| 303 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 304 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 305 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 306 | Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness |
| 307 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 308 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 309 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness |
| 310 | EARTHING PROTECTION |
| 311 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 312 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 313 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 314 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 315 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 316 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG) |
| 317 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 318 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 319 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 320 | LIGHT AND FAN FIXTURES |
| 321 | SITC of 2x 2 LED Recess mounted 36W light fixture, system efficacy greater than 110 lm/W and system lumen output not less than 3600 lm. Luminaire shall have satin finished translucence (HET) diffuser for Uniform illumination and wider light distributionwith CRCA powder coated housing, driver with minimum 4 KV internal surge protection with electronic drive system, power factor greater than or equal to 0.95, THD less than 10%, rated life of 50,000 hours at L70 with a CRI greater than 80, UGR less than 19, SDCM less than 5 and CCT in between 4000K to 5700K.Luminaire shall be flicker free with ripple factor less than 5%, ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. all necessary accessories as required for the light fixture.LM79, LM80, type test certificate & BIS certificate shall be submitted, Luminaire/Drive shall be BIS approved of same make. |
| 322 | SITC of LED recessed downlight fixture Maximum 18 +/-2 W light fixture. System efficacy greater than 110 lm/W and system lumen output not less than 1980 lm. Luminaire shall have satin finished translucence (HET) diffuser for Uniform illumination and wider light distribution with Die Cast Al powder coated housing, driver with minimum 2.50 KV internal surge protection with electronic drive system, power factor greater than or equal to 0.95, THD less than 10%, rated life of 50,000 hours at L70 with a CRI greater than 80, UGR less than 19, SDCM less than 5 and CCT in between 4000K to 5700K. Luminaire shall be flicker free with ripple content is less than 10%, ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mm FRLSPVC insulated, copper conductor, single core cable and earthing etc. all necessary accessories as required for the light fixture. LM79, LM80, type test certificate & BIS certificate shall be submitted, Luminaire/Drive shall be BIS approved of same |
| 323 | SITC of LED recessed downlight fixture Maximum 10W light fixture. Systemefficacy greater than 110 lm/W and system lumen output not less than 1100 lm. Luminaire shall have satin finished translucence (HET) diffuser for uniform illumination and wider light distribution with Die Cast Al powder coated housing, driver with minimum 2.50 KV internal surge protection with electronic drive system, power factor greater than or equal to 0.95, THD less than 10%, rated life of 50,000 hours at L70 with a CRI greater than 80, UGR less than 19, SDCM less than 5 and CCT in between 4000K to 5700K. Luminaire shall be flicker free with ripple content is less than 10%, ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. all necessary accessories as required for the light fixture. LM79, LM80, type test certificate & BIS certificate shall be submitted, Luminaire/Drive shall be BIS approved of same. |
| 324 | SITC of 4 feet surface/suspended mounted LED batten type luminaire with a power consumption not more than 20 W, luminaire lumen output of 2200 lumens, luminaire efficacy greater than 110 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a sleek design with extruded aluminium section, white CRCA housing with optically efficient poly carbonate diffuser to provide uniform illumination and wider light distribution. The luminaire shall have a CCT of 4000K /6500 K, CRI greater than 80, power factor greater than 0.95, SDCM less than 5, THD less than 10%. The luminaire shall be EMI/ EMC compliant and shall have an internal surge protection of 3 kV with 50,000 burning hours as per L70B50 criteria. The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs. The luminaire shall have CRI greater than 80, THD less than 20%. The luminaire shall have an internal surge protection of 4 kV with 25,000 burning hours as per L70B50 criteria. |
| 325 | SITC of 2 feet surface/suspended mounted LED batten type luminaire with a power consumption not more than 10 W, luminaire lumen output of 1100 lumens, luminaire efficacy greater than 110 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a sleek design with extruded aluminum section, white CRCA housing with optically efficient poly carbonate diffuser to provide uniform illumination and wider light distribution. The luminaire shall have a CCT of 4000K /6500 K, CRI greater than 80, power factor greater than 0.95, SDCM less than 5, THD less than 10%. The luminaire shall be EMI/ EMC compliant and shall have an internal surge protection of 3 kV with 50,000 burning hours as per L70B50 criteria. The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs. The luminaire shall have flicker content less than 5% and shall have high and low cut off with auto restart feature, including all accessories necessary as required to complete installation. |
| 326 | SITC of 10W LED BULKHEAD LIGHT fixture, System efficacy greater than or equal to 100 lm/W and system lumen output not less than 1000 lm, driver with minimum 2.50 KV internal surge protection with electronic drive system, power factor greater than 0.95, THD less than 10%, rated life of 50,000 hours at L70 with a CRI greater than 80, SDCM less than 5 and CCT in between 4000K to 5700K. ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc.all necessary accessories as required for the light fixture. LM79, LM80, type testcertificate & BIS certificate shall be submitted, Luminaire/Drive shall be BIS approved of same make. |
| 327 | Supply, installation, testing and commissioning of Integral, SMD LED, IP 65, 80 W LED Surface/Suspend Mounted Round Mid-Bay / High-Bay fixture with System efficacy of more than 135 lm/W (10800 lumens). Luminaire shall be made up of Die Cast Aluminium Housing. Luminaire shall have PC lens with polycarbonate reflecxor for Uniform illumination and wider light distribution. The innovative design with Aeroflo Technology ensures flow of free air through the Housing and keep the heat away from Electrical Components. LM 80-08 compliant LEDs from reputed makes such as Nichia, Japan / Cree, USA / Bridgelux, USA / Lumiled USA / Citizen Japan should be provided. LEDs used in the product shall comply with EN 62471 for Photo biological safety and certificate for the same from manufacturer shall be provided. Luminaire shall use SMD type LED. The LED shall be compliant with LM80-08 standard with Useful L70B50 life of 100000 Hrs tested at maximum current (Complete LM 80 test report for LED should be submitted for 10000 hrs of testing). The LEDs used should be with CCT of 5700 K and CRI of Minimum 70. LED Driver shall be CRCA constructed, Isolated type, multistage Constant Current topology driver with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage ? 240V) with 4 KV internal surge protection, Power factor greater than 0.9 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. Compliance to Indian Standards of IS10322 Part 5 / Sect 1:1967; 16105 : 2012; IS 16106 : 2012; IS 15885 (Part2/Sec13) : 2012; IS 16108 : 2012 |
| 328 | Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 329 | Supplying and fixing of required length 32 mm dia G.I. Pipe (light class) including painting etc. as required |
| 330 | Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no:s blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accesories including safety pin, nut and bolts , washers, temperature rise equal to 75deg celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required: |
| 331 | SITC of 250mm sweep Exhaust Fan, 900rpm light duty exhaust fan shutter type white colour, 9 or 10 inch star rated as per BEE, with its all accessories including mounting as required for complete installation. |
| 332 | SITC of 450mm sweep Wall fan having speed control, oscillation control at bottom as suitable for operation on single phase 230 volt AC supply complete with continuous duty motor and all accessories including mounting as required for complete installation. |
| 333 | CEILING FAN CLAMP |
| 334 | Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar, bent to shape with hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete. |
| 335 | LIGHTNING PROTECTION |
| 336 | Providing and fixing of maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of min 2500mm length (8.20 feet), having a diameter of 20mm with copper bonding thickness of 250 microns as per UL 467. The Rod has to be either continuous arrangement with fault current withstand capability of 20 KA rms value for 1 second and I peak of 50 KA. The rod must be having corrosion test, peel off test for uniform coating, 180 degree bend test with out peeloff of copper bonding.Stainless steel Clamp for Bonding. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 ?m. It should be free from hazardous substances. The mineral compound is required to have minimum 15 Kg of the total composite. The compound should be chemically inert and needs to submit Govt approved Indian labs test certificate. FRP Earth electrode inspection chamber with weight bearing capacity of 60KN. The dimension shall be 290mmx 290mmx 209mm. Govt approved Indian labs test certificate required |
| 337 | Installation of Exothermic Weld Joints for 10mm round copper bonded steel conductor having 100 microns as per IS/IEC 62305. Each under ground joints has to be wrapped with petrolatum- coated chemical fibre fabric having 1.1mm thick and width 50mm. Govt approved Indian labs test certificate required |
| 338 | Providing and laying copper coated steel solid round conductor 10mm diameter from earth electrode directly in ground as required. copper coated steel, high corrosion resistant. Meets the requirement of (IS/IEC 62305) copper coating thickness of 100microns Should be tested and use exclusively for lightning protection earthing system and ring equipotential bonding. After test link needs to be routed inside Heavy duty conduit to avoid touch potential till ground level. Govt approved Indian labs test certificate required |
| 339 | Providing and fixing of Stainless Steel Test Joint suitable with suitable Outdoor Enclosure: For 8mm dia solid round aluminium conductor & 10mm dia copper coated solid steel round conductor having 100 microns of copper bonding . Conforms to the requirements according to (IS/IEC 62305).The enclosure should be outdoor glass-fibre reinforced polycarbonate opaque having minimum inner dimension of 75mm x 75 mm x 50 mm. The test link has to be straight and needs minimum 4 mounting screws for strong joints. Inspection of bimetallic corrosion at site required. Seperation of 8mm Aluminium & 10mm Copper bonded steel is required for future inspection and contractor has to make sure both conductors should not touch eachg other to avoid bimetallic corrosion. Single bolt joints are not permitted. Govt approved Indian labs test certificate required |
| 340 | Providing and fixing of Cross Connector/T Connector/Folding Clamp/Clamping Shoe/ Expansion Piece with Connector: to route vertical down conductor /mesh formation made of Aluminium Ferrule using screw free joints. Folding Clamp/Clamping Shoe for metal panels (up to 20mm thickness of the metal frame): Folding clamp/clamping shoe for metal frame thickness up to 20mm, made of stainless steel SS 304/316 grade , conforms to the requirements according to (IS/IEC 62305). Expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length at every 20 meters horizontally. Using round conductor 8mm aluminium conductor with straight Connector: using Aluminium Ferrule. Quick installation using crimp joints. Conforms to the requirements according to (IS/IEC 62305). Make sure all joints are strong and will be inspected at site. Galvanised Iron joints are not permitted to avoid risk of corrosion. Single bolt joints are not permitted to avoid risk of faulty loose joints and reduce risk of flash over. Govt approved Indian labs test certificate required |
| 341 | Providing & fixing of 8mm solid aluminium round conductor with necessary holders @ required interval as specified below: Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required. Conductor with Terrace Conductor Fibre Reinforce Concrete holder @ every 0.75 meters |
| 342 | Providing & fixing of 8mm solid aluminium round conductor with necessary holders @ required interval as specified below: Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required. Conductor with Down Conductor Holder made of whether resistant plastic holder @ every 0.75 meters |
| 343 | Providing & fixing of 8mm solid aluminium round conductor with necessary holders @ required interval as specified below: Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required. Conductor with Parapet Holder made of whether resistant plastic holder @ every 0.5 meters |
| 344 | Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3. For 1,2,3, 4 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod: For 6, 8 meter 40mm rod tapered to 16mm and then to 10mm Meets the requirement (IS/IEC 62305) Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. Air terminal Joining Clip Stainless Steel SS 304 clamp required to connect horizontal air termination to vertical air termination;Lightning tested for 100 KA 10/350 micro sec waveform. This is required if using 17 KG stone supports. Stainless Steel Wall Clamp or 17 KG stone of 365 mm diameter, high level of stability is required to mount 1,2,3,4 meters. No of concrete stones/wall clamps depending on wind load needs to be considered. For 6 & 8 meter air terminalfor mounting: tripod stand or 3 nos & 4 nos respectively wall clamp will be required to withstand heavy wind load. Govt approved Indian labs test certificate required. 6 meter air terminal with Interception Tip mounted on Concrete Stone & Stainless Steel Tripod Stand |
| 345 | Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3. For 1,2,3, 4 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod: For 6, 8 meter 40mm rod tapered to 16mm and then to 10mm Meets the requirement (IS/IEC 62305) Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. Air terminal Joining Clip Stainless Steel SS 304 clamp required to connect horizontal air termination to vertical air termination;Lightning tested for 100 KA 10/350 micro sec waveform. This is required if using 17 KG stone supports. Stainless Steel Wall Clamp or 17 KG stone of 365 mm diameter, high level of stability is required to mount 1,2,3,4 meters. No of concrete stones/wall clamps depending on wind load needs to be considered. For 6 & 8 meter air terminalfor mounting: tripod stand or 3 nos & 4 nos respectively wall clamp will be required to withstand heavy wind load. Govt approved Indian labs test certificate required. 6 meter air terminal with Interception Tip mounted on Stainless Steel Wall Clamp mounting accessories |
| 346 | Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3. For 1,2,3, 4 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod: For 6, 8 meter 40mm rod tapered to 16mm and then to 10mm Meets the requirement (IS/IEC 62305) Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. Air terminal Joining Clip Stainless Steel SS 304 clamp required to connect horizontal air termination to vertical air termination;Lightning tested for 100 KA 10/350 micro sec waveform. This is required if using 17 KG stone supports. Stainless Steel Wall Clamp or 17 KG stone of 365 mm diameter, high level of stability is required to mount 1,2,3,4 meters. No of concrete stones/wall clamps depending on wind load needs to be considered. For 6 & 8 meter air terminalfor mounting: tripod stand or 3 nos & 4 nos respectively wall clamp will be required to withstand heavy wind load. Govt approved Indian labs test certificate required. 4 meter air terminal with Interception Tip mounted on Stainless Steel Wall Clamp mounting accessories |
| 347 | SAFETY MEASURES |
| 348 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 349 | Supply & fixing Laminated drawings of electrical layout, schematic drawing etc. with teakwood frame work on wall as approved by the directorate of electricity |
| 350 | Supply and fixing of Shock treatment chart duly mounted on a wooden frame with glass on front as required in 2 languages (Hindi & English). |
| 351 | Providing & fixing in position 2M X 1M X 2MM , Elastomeric Insulating Mats as per IS 15652:2006, 2.0mm thick, suitable upto 3.3kv(class A), fire retardant, no effects of acids, alkalis and transformer oils, moisture proof, high tensile strength and tenure finish/ cloth impression(Anti slip marking on top) |
| 352 | PUMP SET |
| 353 | Supply, installation, testing, and commissioning of a Solar-assisted Heat Pump, an insulated pressurized SS storage tank, a hot water expansion vessel, insulated piping between the system, valves, and accessories required to complete the system in position with the following specifications: The system should have a capacity of 1500 Liters, consisting of Solar Hot Water Panels with an aggregate capacity of 750L (50% of the total requirement). The insulated Hot Water Storage Tank should be suitable for 6 bar pressure, made of SS 316 - 1 number, 1500 Liters, and can be either horizontal or vertical as per site requirements, Hotwater output range 55°c to 60°c. System operating temp. range - 15-43°c. The Heat Pump should have a COP of at least 4, with a minimum 12 KW heating capacity and a minimum 300 LPH flow rate. Storage tank shall include a back up electrical heater capacity of minimum 6KW. A circulation system with a pump (1 working + 1 standby) between the heat pump and storage tank, all inclusive of a control panel is required. Plumbing work should use CPVC pipes with suitable fittings, and brass fittings should include NRV, Y Strainer, Air Vent, MTA, FTA, and Flow Switches, with pipeline insulation. The price shall include all electrical work from the pump panel to the Heat Pump, including cabling, PVC conduits, contactors, suitable fittings, and all accessories in complete as required |
| 354 | SITC of 5 HP , 415 V, 3 Phase, 50 Hz centrifugal monoblock pump with CI casing, CI impeller and CS shaft, suitable for delivering a minimum discharge of 11.6 LPS at a total head of 22 m, complete with all accessories, foundation, testing and commissioning as required. |
| 355 | Supply, installation, testing and commissioning of single phase pressure boosting pump, 0.6 KW/0.8 HP, 25 mm SUC, and 25 mm DEL., 6 outlets, 3 stages, CI impeller, SS shaft, Mechanical seal, suitable for 35 mtr to 6 mtr head and 20 lpm and 100 lpm discharge respectively |
| 356 | S & F Motor starters of the following ratingsSingle phase DOL starters for 0.25HP to 3HP motor |
| 357 | S & F Motor starters of the following ratingsThree phase DOL starters for 0.25HP to 7.5 HP motor |
| 358 | Supply, Installation, testing and commission, of Water Transfer submersible Pump,for water from Underground tank to overhead tank, with including solenoid valves, level switches, control wires etc. The price shall inclusive of all connected electrical work. Capacity 350lpm at 20Mtrs. head, Electric motor driven, (HP as per selection of pump) single phase, 230V, AC Supply |
| 359 | Supply, Installation, testing and commission, of 1HP sewage transfer pump submersible pump with including solenoid valves, level switches, control wires etc. The price shall inclusive of all connected electrical work. Electric motor driven, (HP as per selection of pump) three phase, 415V, AC Supply |
| 360 | ELEVATOR |
| 361 | Design, Manufacture, Installation, Testing and Commissioning of gearless electric traction type elevator of the following types and capacities suitable for operation on 415 V, 50 Hz, three phase AC supply with Variable Voltage and Variable Frequency (VVVF) drive for the main drive motor as well as door opening motor which comply with power quality requirements as per the latest version of IEEE 519 with electromagnetic brake system, correction drive to next level,,simple operation/ simplex full selective collective operation with/ without attendant, operating control panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency lamp, intercom suitable for hook-up to EPABX (wiring for the intercom shall be terminated near to the main control panel), infrared ray curtains to the full height of the door, protections for reverse power, loss of phase & overload etc., limit switches, over speed governor, fireman?s switch at the ground floor etc. Car body shall be made of 304 grade SS with hairline finish, flooring with 2.50 mm fluted SS, with centre/ side opening doors, hand rails on 3 sides, mirror on the rear side, digital car position indicators in the car and at all landings with UP/DOWN directions, control panel with braille markings, occupancy sensor operated LED lighting in the car to maintain at least 150 lux and ventilating fan, ARD with battery etc. The landing doors shall be made of the same material as of the car body with fire rating as per current Standards. The installation shall include necessary scaffolding, all required minor civil works, construction of buffer blocks with springs, supply and fixing all supporting steel structures, architraves with 16 mm granite/ large format ceramic tile of approved size and pattern, all required electrical works including wiring inside the shaft and providing necessary light fittings, receptacles etc., supply and fixing necessary control panels and controls as per Standards, all power and control wirings encased in metal/ PVC conduits/ troughs etc. The electrical work shall be done in conformity with NEC 2023 and other relevant Standards. The manufacture and installation of the lifts shall be in compliance with the latest versions of IS 14665, IS 17900, IS 17106 and other relevant Standards. The efficiency of the lift shall be class A according to IS 17515. All certificates/ documents to prove the compliance shall be submitted on completion of work Machine Room Less (MRL) type 20 passenger (1360 kg) bed lift having a speed of 1 m/s in the available lift shaft of size 3100 mm (D) x 2400 mm (W) with a total travel distance of 10 m with 3 stops and 3 openings on the same side, minimum door opening size 1200 mm (W) x 2000 mm (W) with stretcher impact protection on 3 sides. |
| 362 | DOCUMENTATION AND APPROVAL |
| 363 | DOCUMENTATION AND APPROVAL \\"Charges for Preparation of all drawings submitting and getting approval from Electrical Inspectorate, submitting of Completion certificates and arranging inspection, getting sanction and energization certificates from Electrical Inspectorate & KSEB, obtaining power allocation & power connection etc. including feasibility study. for commissioning of the whole installation. All statutory payments will be reimbursed on production of the original receipts. (for modification works) |
| 364 | ELV WORKS |
| 365 | STRUCTURED CABLING AND ACTIVE DEVICES |
| 366 | Supply, installation, testing and commissioning of Cat6A Information Outlet, RJ45 with all accessories required at site to complete the work as per technical specification |
| 367 | Supply, installation, testing, and commissioning of a 16-port smart managed Gigabit network switch featuring sixteen 10/100/1000 Mbps Ethernet ports designed for high speed desktop or wall-mounted deployment; the unit must incorporate advanced layer 2 features including VLAN support for traffic segmentation, Quality of Service (QoS) for prioritized bandwidth traffic, bandwidth control, port trunking, and loop prevention mechanisms; management capabilities must include an intuitive web based graphical user interface, a utility software management tool, and SNMP support for network monitoring and maintenance; design configuration must feature a durable, compact metal chassis with a fanless passive cooling system for silent operation, energy-saving green technology supporting IEEE 802.3az Energy Efficient Ethernet and link-status power down; complete with comprehensive end-to-end testing, switch configuration, port link validation, network integration, and final operational handover. |
| 368 | Supply, installation, testing, and commissioning of a 24-port smart managed Gigabit network switch featuring twenty four 10/100/1000 Mbps Ethernet ports designed for high-speed desktop or wall-mounted deployment; the unit must incorporate advanced layer 2 features including VLAN support for traffic segmentation, Quality of Service (QoS) for prioritized bandwidth traffic, bandwidth control, port trunking, and loop prevention mechanisms; management capabilities must include an intuitive web based graphical user interface, a utility software management tool, and SNMP support for network monitoring and maintenance; design configuration must feature a durable, compact metal chassis with a fanless passive cooling system for silent operation, energy-saving green technology supporting IEEE 802.3az Energy Efficient Ethernet and link-status power down; complete with comprehensive end-to-end testing, switch configuration, port link validation, network integration, and final operational handover. |
| 369 | S I T C Gigabit Multi-WAN Load Balancing Router with Gigabit Ports:1 gigabit SFP and5gigabit RJ45 ports provide high-speed wired connectivity. Up to 4 WAN Ports:1 gigabit SFP WAN port, 1 gigabit RJ45 WAN port, 2 gigabit WAN/LAN ports optimize bandwidth usage |
| 370 | Supply , Installation,Testing and Commissioning of Wireless Accesspoint supportig dual band with 5GHZ and 2,4GHZ concurrent operation 4x4:3 MIMO Wave2 from Day 1 , One.10/100/1000 Base-Tx auto-sensing (RJ45) PoE port .The AP shall be wall mountable as well as celling mountable (provide both options) |
| 371 | Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable |
| 372 | Supply and installation of Cat 6 UTP patch cord, 1m length |
| 373 | SITC Of 4-Port PoE Gigabit Smart Managed Switch with 12 10/100/1000BASE-T PoE ports and 12 10/100/1000BASE-T ports ,100W PoE power budget Supports IEEE 802.3at PoE and Complete web interface for comprehensive switch management CE certified |
| 374 | Supply, installation, testing and commissioning of Cat6 24 port patch panel, fully loaded, with all accessories required at site to complete the work as per technical specification |
| 375 | Supply, Installation, Testing & Commissioning of 15 U Network Rack with 500 mm deep below specifications as minimum and all the necessary accessories: - Lock & Keys - Tray (1 No) - 1 Cooling Fan and Adjustable Shelf - Height - 15U - Dimensions - 13x12x11 cm - Fan Units with 1coolin Fans - PDU 6 point - 1 Nos's - Mounting Hardware Kit (1 lot) - Tray - Front glass doors and back steel door and side panels\\" |
| 376 | \\"Supply, Installation, Testing & Commissioning of 9U Network Rack with below specifications as minimum and all the necessary accessories: - Lock & Keys - Tray (1 No) - 1 Cooling Fan and Adjustable Shelf - Height - 9U - Dimensions - 13x12x11 cm - Fan Units with 1coolin Fans - PDU 6 point - 1 Nos's - Mounting Hardware Kit (1 lot) - Tray - Front glass doors and back steel door and side panels\\" |
| 377 | Supply, installation, testing and commissioning of Cat6 16 port patch panel, fully loaded, with all accessories required at site to complete the work as per technical specification |
| 378 | PVC CONDUITING GI BOX AND CABLE TRAY |
| 379 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 380 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 381 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 382 | Supply and laying of 75mm X50Mmm medium class pvc trunking cap along with all accessories as required. |
| 383 | Supply and clamping of 20mm dia corrugated pvc flexible conduit with necessary locking ring and check nut at termination pointed using suitable size GI/painted MS saddles spacing not exceeding 60 cms on surface including making good the damages, colour washing etc.as;required. |
| 384 | HVAC WORKS |
| 385 | Supply, Installation, Testing and Commissioning of air-cooled VRV (Variable Refrigerant Volume) / VRF (Variable Refrigerant Flow) outdoor units (ODUs) equipped with highly efficient, full DC inverter-driven scroll compressors only, air cooled heat exchangers having internally grooved copper tubes, and low-noise condenser fans. The units shall have auto-addressing, an auto-check function for connection errors, and operate with R-410A or equivalent refrigerant gas. Each unit shall be fitted with a noise filter, high-pressure switch, fan motor overload protector, over-current relay, inverter overload protector, and other necessary protective devices. A power failure of one or more IDUs shall not affect operation of other units/circuits. The units shall deliver the rated capacity in accordance with IS 18728:2024 and CPWD specifications. The efficiency of the ODUs shall meet the latest ASHRAE / ECSBC 2024 standards. Suitable vibration isolators shall be provided with the ODUs. The system shall operate at outdoor conditions up to a maximum ambient dry-bulb temperature of 50°C. Each unit shall be equipped with an oil recovery system to ensure stable operation with long refrigeration piping lengths and an oil-balancing circuit to prevent inadequate lubrication. Compatibility with centralized control systems such as BACnet, LonWorks, and Modbus is required. The ODUs shall be suitable for a 3-phase, 415 V, 50 Hz power supply, with suitable interconnecting control cabling between IDUs, ODUs, and the central controller. All necessary power cabling up to the ODU electrical panel, pressure testing, additional refrigerant charging for commissioning, and all associated accessories required for commissioning shall be included in the scope of work. The VRF outdoor unit circuit schedule shall be as per the tender drawings/specifications.. |
| 386 | Supply, Installation, Testing, and Commissioning of VRV/VRF 1.6TR high-wall type indoor unit complete with a corded/cordless remote (subject to consultant's approval). The machine shall be suitable for operation on 230 V, 50 Hz, single-phase AC supply, including all power cabling to the nearest power socket. The unit shall include a washable synthetic media pre-filter, DC fan section with a low-noise fan/dynamically balanced blower, multi-speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pan, and necessary accessories,etc.. |
| 387 | Supply, Installation, Testing, and Commissioning of VRV/VRF 1.3 TR high-wall type indoor unit complete with a corded/cordless remote (subject to consultant's approval). The machine shall be suitable for operation on 230 V, 50 Hz, single-phase AC supply, including all power cabling to the nearest power socket. The unit shall include a washable synthetic media pre-filter, DC fan section with a low-noise fan/dynamically balanced blower, multi-speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pan, and necessary accessories, etc. |
| 388 | Supply, Installation, Testing, and Commissioning of VRF/VRV 1.6TR ceiling mounted low-static ductable type indoor unit along with a corded remote. The unit shall be equipped with a washable synthetic media pre-filter, a fan section with a low noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dx copper coil, an electronic expansion valve, a corded remote control, an outer cabinet, vibration isolators, a drain pan, and other necessary supports, suitable for operation on a single-phase AC supply of 230 V ± 10%, 50 Hz.. |
| 389 | Supply, Installation, Testing, and Commissioning of VRF/VRV 2.0TR ceiling mounted low-static ductable type indoor unit along with a corded remote. The unit shall be equipped with a washable synthetic media pre-filter, a fan section with a low noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dx copper coil, an electronic expansion valve, a corded remote control, an outer cabinet, vibration isolators, a drain pan, and other necessary supports, suitable for operation on a single-phase AC supply of 230 V ± 10%, 50 Hz.. |
| 390 | Supply, Installation, Testing, and Commissioning of VRF/VRV 4.0TR ceiling mounted, mid/high static ductable type indoor unit along with a corded remote. The unit shall be equipped with a washable synthetic media pre-filter, a fan section with a low-noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dx copper coil, an electronic expansion valve, an outer cabinet, vibration isolators, a drain pan, and other necessary supports, suitable for operation on a single-phase AC supply of 230 V ± 10%, 50 Hz.. |
| 391 | Supply, Installation, Testing, and Commissioning of VRF/VRV 5.5TR ceiling mounted, mid/high static ductable type indoor unit along with a corded remote. The unit shall be equipped with a washable synthetic media pre-filter, a fan section with a low-noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dx copper coil, an electronic expansion valve, an outer cabinet, vibration isolators, a drain pan, and other necessary supports, suitable for operation on a single-phase AC supply of 230 V ± 10%, 50 Hz.. |
| 392 | Supply and installation of indoor Refnet / Y-joint separation tubes for refrigeration pipe joints and headers, in appropriate orientation to enable proper distribution of refrigerant. The distribution joints shall be factory insulated with pre-formed sections of expanded polystyrene or equivalent.. |
| 393 | Supply and installation of outdoor Refnet / Y-joint separation tubes for refrigeration pipe joints and headers, in appropriate orientation to enable proper distribution of refrigerant. The distribution joints shall be factory insulated with pre-formed sections of expanded polystyrene or equivalent. |
| 394 | Supply, Installation, Testing, and Commissioning of centralized type remote controller, color touchscreen type with UPS battery backup, all-inclusive of necessary installation supports and wiring. The controller shall function as an advanced air conditioning management system, providing complete control of VRV/VRF air conditioning equipment (including connected air handling units (AHUs)). It shall offer user-friendly operation through its touchscreen, icon display, and color LCD display. The controller shall be compatible with BACnet, LonWorks, or Modbus interface. The controller shall control up to 64 groups of indoor units with the following functions: 1. Start/stop of air conditioners as a zone, group, or individual unit 2. Temperature setting for each indoor unit or zone 3. Switching between temperature control modes, fan speed adjustment, and airflow direction control, including enable/disable of individual remote controller operation 4. Monitoring of operation status, including operation mode, temperature settings of individual indoor units, maintenance information, and troubleshooting details 5. Scheduling indoor unit operating time 6. Displaying air conditioner operation history.. |
| 395 | Supply, Installation, Testing, and Commissioning of the Soft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:1/4 inch (6.35 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps,for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 396 | Supply, Installation, Testing, and Commissioning of theSoft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:3/8 inch (9.52 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 397 | Supply, Installation, Testing, and Commissioning of the Soft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:1/2 inch (12.7 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 398 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:5/8 inch (15.88 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 399 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:3/4 inch (19.05 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 400 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:7/8 inch (22.2 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 401 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1.0 inch (25.4 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 402 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-1/8 inch (28.6 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 403 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-1/4 inch (31.8 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 404 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-3/8 inch (34.9 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 405 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-1/2 inch (38.1 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 406 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 17/18 Gauge with 25mm thick Insulation:1-5/8 inch (41.3 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 407 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 16/17 Guage with 25mm thick Insulation:1-3/4 inch (44.45 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 408 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 16/17 Guage with 25mm thick Insulation:1-7/8 inch (47.62mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 409 | Supply, installation, and testing of shielded copper flexible communication cabling between VRF indoor and outdoor units. The communication cable shall be routed through PVC conduits. The cable size shall be 2-core x 1.5 SQMM (or) as per VRF OEMs technical specifications.. |
| 410 | Supply, installation, testing, and commissioning of 25mm dia rigid UPVC condensate drain piping duly insulated with 9 mm thick closed-cell nitrile finished with 7 mils factory-laminated glass cloth, along with necessary U-trap, clamps, fittings such as bends, tees, and other necessary fittings, adequately supported as per site requirements, conforming to tender specifications.. |
| 411 | Supply, installation, testing, and commissioning of 32mm dia rigid UPVC condensate drain piping duly insulated with 9 mm thick closed-cell nitrile finished with 7 mils factory-laminated glass cloth, along with necessary U-trap, clamps, fittings such as bends, tees, and other necessary fittings, adequately supported as per site requirements, conforming to tender specifications.. |
| 412 | Supply, installation, testing, and commissioning of 40mm dia rigid UPVC condensate drain piping duly insulated with 9 mm thick closed-cell nitrile finished with 7 mils factory-laminated glass cloth, along with necessary U-trap, clamps, fittings such as bends, tees, and other necessary fittings, adequately supported as per site requirements, conforming to tender specifications.. |
| 413 | Supply, installation, testing, and commissioning of 3.0TR - 1200 CFM, 25mm E.S.P, VRF-compatible DX type recirculating factory-built AHUs with 2-stage filtration, 6 row DX cooling coil, double-skin AHU made of 50 mm thick panels consisting of 0.8 mm thick pre-coated GSS on outside, 0.8 mm thick Aluminum sheet inside with factory-injected PUF with a minimum density of 40 kg/m³. The AHU shall be ceiling or floor-mounted type, single- or double-deck (as per site conditions) along with thermal-break aluminum extruded profile at corners and joints, complete with plug fan compatible with VFD as specified in the starter panel, suitable IE3 class (per IS 12615) TEFC drive motor with IP55 protection suited for 415 ± 10% volts, 50 Hz, 3 phase AC supply, minimum two-bend GSS/PVC eliminators, cooling coil section with aluminum-finned copper tubes, filter section with 50 mm thick metal viscous/washable synthetic-type air pre- and fine filters (MERV 8 and MERV 14), mixing box, aluminum VCDs on fresh air, return air, and supply air openings, drain connection, 18 G stainless steel 304 with 19 mm NBR-insulated drain pan, necessary vibration isolation arrangement, expansion valve, drier, VRF/DX AHU kit, corded remote controller, limit switches for access doors, inspection lamp. UV-C emitters equipped with reflectors to be mounted on the coil surface using removable extruded aluminum frames. The UV-C emitters to be UL certified and capable of producing minimum 254 nm wavelength radiation, 7.5 W/sqft of coil surface area for equal distribution. Heaters (capacity to be proposed by OEM) to be slip-in type tubular heater with step controller to be fitted inside AHU with suitable humidistat, thermostat, air stat/airflow switch, and safety thermostat. Heaters to be arranged in two independently operating banks. One bank shall be operated through humidistat and one bank through thermostat. All the necessary incoming power and control cabling, earthing between AHU/strip heaters and control panel, all supporting GI hangers, MS angles, channels, nuts, bolts, washers, and other necessary items for unit installation shall be included in the scope of supply. Fans shall be Eurovent/AMCA certified. AHUs shall be Eurovent/AHRI-certified.. |
| 414 | Supply, installation, testing, and commissioning of 5.5TR - 2200 CFM, 40mm E.S.P, VRF-compatible DX type recirculating factory-built AHUs with 2-stage filtration, 6 row DX cooling coil, double-skin AHU made of 50 mm thick panels consisting of 0.8 mm thick pre-coated GSS on outside, 0.8 mm thick Aluminum sheet inside with factory-injected PUF with a minimum density of 40 kg/m³. The AHU shall be ceiling or floor-mounted type, single- or double-deck (as per site conditions) along with thermal-break aluminum extruded profile at corners and joints, complete with plug fan compatible with VFD as specified in the starter panel, suitable IE3 class (per IS 12615) TEFC drive motor with IP55 protection suited for 415 ± 10% volts, 50 Hz, 3 phase AC supply, minimum two-bend GSS/PVC eliminators, cooling coil section with aluminum-finned copper tubes, filter section with 50 mm thick metal viscous/washable synthetic-type air pre- and fine filters (MERV 8 and MERV 14), mixing box, aluminum VCDs on fresh air, return air, and supply air openings, drain connection, 18 G stainless steel 304 with 19 mm NBR-insulated drain pan, necessary vibration isolation arrangement, expansion valve, drier, VRF/DX AHU kit, corded remote controller, limit switches for access doors, inspection lamp. UV-C emitters equipped with reflectors to be mounted on the coil surface using removable extruded aluminum frames. The UV-C emitters to be UL certified and capable of producing minimum 254 nm wavelength radiation, 7.5 W/sqft of coil surface area for equal distribution. Heaters (capacity to be proposed by OEM) to be slip-in type tubular heater with step controller to be fitted inside AHU with suitable humidistat, thermostat, air stat/airflow switch, and safety thermostat. Heaters to be arranged in two independently operating banks. One bank shall be operated through humidistat and one bank through thermostat. All the necessary incoming power and control cabling, earthing between AHU/strip heaters and control panel, all supporting GI hangers, MS angles, channels, nuts, bolts, washers, and other necessary items for unit installation shall be included in the scope of supply. Fans shall be Eurovent/AMCA certified. AHUs shall be Eurovent/AHRI-certified.. |
| 415 | Supply, installation, testing, and commissioning of 8.5TR - 3400 CFM, 50mm E.S.P, VRF-compatible DX type recirculating factory-built AHUs with 2-stage filtration, 6 row DX cooling coil, double-skin AHU made of 50 mm thick panels consisting of 0.8 mm thick pre-coated GSS on outside, 0.8 mm thick Aluminum sheet inside with factory-injected PUF with a minimum density of 40 kg/m³. The AHU shall be ceiling or floor-mounted type, single- or double-deck (as per site conditions) along with thermal-break aluminum extruded profile at corners and joints, complete with plug fan compatible with VFD as specified in the starter panel, suitable IE3 class (per IS 12615) TEFC drive motor with IP55 protection suited for 415 ± 10% volts, 50 Hz, 3 phase AC supply, minimum two-bend GSS/PVC eliminators, cooling coil section with aluminum-finned copper tubes, filter section with 50 mm thick metal viscous/washable synthetic-type air pre- and fine filters (MERV 8 and MERV 14),mixing box, aluminum VCDs on fresh air, return air, and supply air openings, drain connection, 18 G stainless steel 304 with 19 mm NBR-insulated drain pan, necessary vibration isolation arrangement, expansion valve, drier, VRF/DX AHU kit, corded remote controller, limit switches for access doors, inspection lamp. UV-C emitters equipped with reflectors to be mounted on the coil surface using removable extrudedaluminum frames. The UV-C emitters to be UL certified and capable of producing minimum 254 nm wavelength radiation, 7.5 W/sqft of coil surface area for equal distribution. Heaters (capacity to be proposed by OEM) to be slip-in type tubular heater with step controller to be fitted inside AHU with suitable humidistat, thermostat, air stat/airflow switch, and safety thermostat. Heaters to be arranged in two independently operating banks. One bank shall be operated through humidistat and one bank through thermostat. All the necessary incoming power and control cabling, earthing between AHU/strip heaters and control panel, all supporting GI hangers, MS angles, channels, nuts, bolts, washers, and other necessary items for unit installation shall be included in the scope of supply. Fans shall be Eurovent/AMCA certified. AHUs shall be Eurovent/AHRI-certified. |
| 416 | Supply and installation of a suitable, CPRI-approved (IEC 61439) AHU VFD starter panel, factory-fabricated, wall-mounted type, including all necessary control and power cable wiring between the AHU and the panel. The motor control shall be facilitated by a variable frequency drive (VFD) complying with the latest IEEE 519 standards. The panel shall incorporate controls such as contactors, overload relays (OLR), single-phase preventer (SPP), control switches, and MCBs for AC units. The panel shall have a 24V AC power supply for fire interlock. The panel shall have an auto/manual selection switch, on/off push buttons, and on, off, and trip indication lamps, etc. The panel shall have control element features, including a humidistat, thermostat, air stat/airflow switch, and safety thermostat, along with control wiring. The panel shall feature ON/OFF switches with indicators and a bypass DOL/star-delta starter (selected based on motor size) for the VFD, along with a manual changeover switch for transitioning between VFD and bypass operations The fan/blower motor shall be interlocked with heaters (where provided) such that the power supply to the heaters will be switched on only after the blower has been started and run to full designed speed. The panel shall have contactors and breakers for the heater banks, with the required power and control wiring to maintain temperature/RH % as per indoor design conditions.. |
| 417 | Supply, installation, testing, and commissioning of inline exhaust fan 600CFM @ minimum 15mm static pressure. The fan shall be AMCA-certified for both air performance and sound performance. The fan casing shall be constructed from galvanized sheet steel. The installation cost shall be inclusive of an electronic speed regulator, power and control wiring between the power supply and the fan and speed regulator, suitable enclosure, plug for socket connection, mounting brackets, and all other necessary accessories, as per site conditions.. |
| 418 | Supply, installation, testing, and commissioning of cabinet fan (EXHAUST AIR) 600CFM @ minimum 40mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a HEPA filter having a minimum efficiency of 99.97% at 0.3 ?m. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions. |
| 419 | Supply, installation, testing, and commissioning of cabinet fan (EXHAUST AIR) 1000CFM @ minimum 40mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a HEPA filter having a minimum efficiency of 99.97% at 0.3 ?m. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions.. |
| 420 | Supply, installation, testing, and commissioning of cabinet fan (EXHAUST AIR) 1500CFM @ minimum 60mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a HEPA filter having a minimum efficiency of 99.97% at 0.3 ?m. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions.. |
| 421 | Supply, installation, testing, and commissioning of cabinet fan (EXHAUST AIR)2000CFM @ minimum 60mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a HEPA filter having a minimum efficiency of 99.97% at 0.3 ?m. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions. |
| 422 | Supply, installation, testing, and commissioning of cabinet fan (EXHAUST AIR) 2500CFM @ minimum 60mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a HEPA filter having a minimum efficiency of 99.97% at 0.3 ?m. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions.. |
| 423 | Supply, installation, testing, and commissioning of cabinet fan (EXHAUST AIR) 3500CFM @ minimum 60mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a HEPA filter having a minimum efficiency of 99.97% at 0.3 ?m. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions.. |
| 424 | Supply, installation, testing, and commissioning of cabinet fan (FRESH AIR) 800CFM @ minimum 40mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible three-phase motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a MERV 8 pre-filter. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions.. |
| 425 | Supply, installation, testing, and commissioning of cabinet fan (FRESH AIR) 1500CFM @ minimum 40mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible three-phase motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a MERV 8 pre-filter. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions.. |
| 426 | Supply, installation, testing, and commissioning of cabinet fan (FRESH AIR) 2000CFM @ minimum 60mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible three-phase motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a MERV 8 pre-filter. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions.. |
| 427 | Supply, installation, testing, and commissioning of cabinet fan (FRESH AIR) 3000CFM @ minimum 60mm static pressure. The casing shall be double-skin, acoustically lined internally, and constructed from galvanized steel. Fans with three phase motors shall be equipped with VFD-compatible three-phase motors. The fan shall be AMCA-certified for both air performance and sound performance. The fan shall be equipped with a MERV 8 pre-filter. The installation cost shall be inclusive of an electronic speed regulator for single-phase fans. For three-phase fans, the installation cost shall include a VFD starter panel, along with necessary power and control wiring for connecting the power supply, fan, and VFD panel, as well as suitable enclosures, mounting brackets, and all other necessary accessories, as per site conditions. |
| 428 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows,splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.63 mm sheet |
| 429 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.80 mm sheet |
| 430 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular dueling as per IS 655-2006 Thickness 1.00 mm sheet |
| 431 | Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.63 mm thick |
| 432 | Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.8. mm thick |
| 433 | Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 1.00 mm thick |
| 434 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class \\"\\"O\\"\\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.Nitrille rubber insulation - 25 mm |
| 435 | Supply, storage, installation, testing, and commissioning of 10 mm thick acoustic insulation for ducts using nitrile rubber open-cell foam, fibre-free material with a minimum density of 140 kg/m³. The insulation shall have antimicrobial protection in accordance with ASTM G-21 and ASTM E-2180 and shall conform to Class 1 rating for flame spread as per BS 476 Part 7. The work shall be carried out in line with the specification and designed to meet the required noise criteria. The insulation shall be applied up to a distance of 4 metres from the fan outlet (or) as instructed by the Engineer-in-Charge. The insulation system shall be complete in all respects for commissioning.. |
| 436 | Supply and application of two coats of a vapor barrier coating (Foster painting) on exposed ducts / copper refrigerant pipelines, as per the Engineer-in-Charge’s directions. The work includes surface preparation, application of the vapor barrier coating, and related works to ensure complete coverage and protection |
| 437 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. Gl volume control duct damper |
| 438 | Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/ main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.Fire damper |
| 439 | Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/ main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.Actuator |
| 440 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. |
| 441 | Supplying & fixing of powder coated extruded aluminum Return Air Grills with louvers but without volume control dampers complete as required. |
| 442 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminum with aluminum volume control dampers with anti smudge ring and removable core. |
| 443 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminum without volume control dampers with anti smudge ring and removable core. |
| 444 | Supply and installation of fresh air/exhaust air louver constructed from powder coated aluminium with bird screen as per the specifications and drawings.. |
| 445 | Supply, installation, fixing, and hanging of factory-fabricated fire-retardant flexible canvas connection of minimum 150 mm width at the outlet of each ducted indoor unit with a zipper to facilitate temperature measurement. The fabric shall be made of polyester cloth with black PVC coating on both sides and a galvanized steel seam.. |
| 446 | FIREFIGHTING WORKS |
| 447 | PUMPS |
| 448 | a)Supplying,installation,testing and commissioning of Electric driven Main Fire Pump suitable for Automatic operation and consisting of following, complete in all respect , as required : b) Horizontal type, Multi stage ,centrifugal, split casing Pump of Cast Iron body and bronze impeller with stainless steel shaft ,mechanical seal conforming to IS 1520. C) Suitable HP Squirrel Cage Induction Motor, TEFC, Synchronous speed 1500rpm suitable for operation on 415 V 3 phase 50 HZ AC supply with IP55 Protection for enclosure ,horizontal foot mounted type with class F insulation, conforming to IS 325. d) M.S Fabricated common base plate coupling, coupling guard ,foundation bolts etc as required. e) Suitable cement concrete foundation duly plastered with Anti vibration pads 2280 lpm at 70 m head |
| 449 | a)Supplying,installation,testing and commissioning of Diesel Engine driven Main Fire Pump suitable for Automatic operation and consisting of following, complete in all respect , as required :(Diesel Driven Pump) b) Horizontal type, Multi stage ,centrifugal, split Pump of Cast Iron body and bronze impeller with stainless steel shaft ,mechanical seal conforming to IS 1520. C) Suitable HP ,1500rpm,water cooled with radiator,diesel engine conforming to relevant IS standard complete with auto starting mechanism 12/24 V Electric starting equipment,diesel tank, exhaust pipe extended upto 10m outside pump house duly insulated with 50 mm thick glass wool with 1 mm thick Al sheet cladding residential silencer, instruments and protection as per standard specifications, stop solenoid for Auto stop in the event of fault with audio indications, painted with post office red colour etc as required. d) M.S Fabricated common base plate coupling, coupling guard ,foundation bolts etc as required. e) Suitable cement concrete foundation duly plastered with Anti vibration pads2280 lpm at 70 m head |
| 450 | a)Supplying, installation, testing and commissioning of Electric driven Pressurisation Pump suitable for Automatic operation and consisting of following, complete in all respect , as required :(Jockey Pump) b) Horizontal type, Multi stage ,centrifugal, split casing Pump of Cast Iron body and bronze impeller with stainless steel shaft ,mechanical seal conforming to IS 1520. C) Suitable HP Squirrel Cage Induction Motor, TEFC type suitable for operation on 415 V 3 phase 50 HZ AC supply with IP55 Protection for enclosure ,horizontal foot mounted type with class F insulation, conforming to IS 325. d)M.S Fabricated common base plate coupling, coupling guard ,foundation bolts etc as required. e) Suitable cement concrete foundation duly plastered with Anti vibration pads180 lpm at 70m Head |
| 451 | PUMP PANEL |
| 452 | Fabrication, supply, installation, testing and commissioning of Electrical Control Panel of cubicle construction Floor mounted type fabricated out of 2 mm thick CRCA sheet compartmentalised with hinged lockable doors, dust vermin proof, powder coated of approved shade after 7 tank treatment process cable alleying interconnection with suitable size copper conductor cable or solid copper strip having switchgearsand accessories, mopuntigs and internal wiring, earth terminals, numbering etc., complete in all respects suitable for main fire pump , pressurisation pump and diesel pump set complete as per CPWD specification with following incoming and outgoings suitable for operation of 415 V, 3 phase, 50 Hz, AC supply with enclosure protection class IP 42 as required: INCOMING : 250A, 50kA 4P MCCB ,Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Digital Ammeter 0-250A with selector switch and CTs etc. LED Type RYB phase indicating Lamps ,ON/OFF, Trip indicating lamps set of Cu Bus Bar 300A . OUT GOING :(Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) MAIN FIRE PUMP: 125 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. JOCKEY PUMP : 63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. DIESEL ENGINE CONTROL: Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller tocontrol operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 453 | PIPES,VALVES AND ACCESSORIES |
| 454 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:25 mm dia |
| 455 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:32 mm dia |
| 456 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:40 mm dia |
| 457 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:50 mm dia |
| 458 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:65mm dia |
| 459 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:80mm dia |
| 460 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:100mm dia |
| 461 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:150mm dia |
| 462 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:200mm dia(Wall thickness 6.3mm) |
| 463 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 1239/3589 i/c fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., in ground including welding ,excavation and providing cement concrete blocks as supports, Anti corrosive treatment with coal tar ,Asphalt type as per IS 10221, refiiling the trench etc., of following sizes150 mm dia |
| 464 | Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:80 mm dia |
| 465 | Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:100 mm dia |
| 466 | Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:150 mm dia |
| 467 | Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:200 mm dia |
| 468 | Providing,installation,testing and commissioning of non-return valve of following sizes conforming to IS :5312 complete with rubber gasket, GI bolts , nuts, washers etc as required.80mm dia |
| 469 | Providing,installation,testing and commissioning of non-return valve of following sizes conforming to IS :5312 complete with rubber gasket, GI bolts , nuts, washers etc as required.100 mm dia |
| 470 | Providing,installation,testing and commissioning of non-return valve of following sizes conforming to IS :5312 complete with rubber gasket, GI bolts , nuts, washers etc as required.150mm Dia |
| 471 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates,pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipeof required size, flanges, orifice plate, gasket etc of follwing sizes as required: 150 mm dia |
| 472 | Supplying and fixing single headed external yard hydrant valve with one no: 63 mm dia instantaneous FM Gun metal or stainless steel coupling and cast iron wheel, ISI marked ISI marked conforming to IS 5290(Type A) with blank Gun metal or Stainless steel cap and chain as required:Single headed stainless steel |
| 473 | Supplying and fixing single headed internal hydrant valve with instantaneous Gun metal or stainless steel coupling of 63mm dia with cast iron wheel ISI marked conforming to IS 5290(Type A) with blank Gun metal or Stainless steel cap and chain as required:Single headed stainless steel |
| 474 | Providing, installation ,testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel , Grade 304,sheet with3 mm dia holes with stainless steel flange.200 mm dia |
| 475 | supplying and fixing air vessel made of 250 mm dia 8 mm thick MS sheet , 1200 mm in height with Air release valve on top and flanged connection to riser , drain arrangement with 25 mm dia Gun metal wheel valve with required accessories , pressure guage and painting with synthetic enamel paint of approved shade as required. |
| 476 | Providing and fixing of pressure switch in MS pipeline including connection etc as required: |
| 477 | Providing and fixing of flow switch in MS pipe including connection etc as required:100 mm dia |
| 478 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 479 | Supplying and fixing 63 m dia,15m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required: Stainless steel (Grade 304) |
| 480 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. a) 20 mm nominal Internal dia water hose thermoplastic(Textile reinforced) type-2 as per IS:12585 b) 20 mm nominal internal dia gun metal globe valve &nozzle c) Drum and brackets for fixing the equipments on wall. d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.30 m |
| 481 | Supply, installation, testing and commissioning of hose boxes wall/pedestal type of size 600 x 250 x 400 mm made out of 18 gauge MS sheet steel with front side glass, locking arrangement and painted with approved colour, With all necessary fixing accessories and installation as required as per specifications. |
| 482 | Supplying and fixing 63 mm dia gun etal short metal branch pipe ith 20 mm nominal interanal diameter size nozzle conforming to IS 903 suitable for Instantaneous connection to Interconnect hose pipe coupling as required:Stainless steel (Grade 304) |
| 483 | Supply, installation, testing and commissioning of weather proof hose boxes wall/pedestal type of size 600 x 250 x 400 mm made out of 18 gauge MS sheet steel with front side glass, locking arrangement and painted with approved colour completed as required and as per specifications. |
| 484 | AIR RELEASE VALVE; Supply, installation, testing and commissioning of gunmetal air release valve 25 mm with necessary fittings etc. complete. |
| 485 | Supply, installation, testing and commissioning of lever operated 25mm dia Gate/ball valve conforming to IS 9890:1981 with forged body, brass/stainless steel ball and shall be internally threaded to receive pipe connections 25mm dia |
| 486 | Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters FIRE in black and gold. Cost shall be inclusive of providing MS stand for 2 nos of fire buckets, duly painted over a coat of primer. |
| 487 | SPRINKLERS |
| 488 | Providing,fixing, testing and commissioning of 15 mm dia quatzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Pendent Sprinkler |
| 489 | Providing,fixing, testing and commissioning of 15 mm dia quatzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Upright sprinkler |
| 490 | Supplying, installation, testing & commissioning of sprinkler flexiblepipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 700 mm |
| 491 | Supplying, installation, testing & commissioning of sprinkler flexiblepipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1000 mm |
| 492 | Providing, installation, testing and commissioning of adjustable rosette plate for 15 mm dia in white finish UL listed or FM approved complete as required: |
| 493 | FIRE BRIGADE |
| 494 | Supply, installation, testing, and commissioning of a fire brigade draw-off outlet, cast iron body, fitted with 3 Nos. gunmetal 63 mm female instantaneous inlets conforming to IS: 903, complete with non-return valves, 25 mm drain valve, flanged outlet, 3 Nos. rubber blank caps with G.I. chains, and all necessary accessories for complete installation. |
| 495 | Supplying and fixing fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia M.S. Pipe connection conforming to IS 904 as required:3 way-150 mm dia M.S.Pipe |
| 496 | FIRE EXTINGUISHERS |
| 497 | Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity.Co2 type Fire Extinguisher, made from brand new seamless Steel cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Wheel type valve with initial Charge and mounted on Rubber Wheels / wall mounted brackets as per IS: 16018 specification, bearing ISI Mark. 4.5 Kgs |
| 498 | Supply and installation of ABC Stored pressure type Fire Extinguisher 6 Kgs Capacity Mono Ammonium Phosphate based Dry Chemical Powder as per IS 14609 with ISI Mark for Fighting ABC Class of Fire, stored Pressure type of Mild steel body pressurized by Nitrogen Gas. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket. The Extinguisher should be manufactured strictly as per IS: 15683:2006 with ISI mark |
| 499 | Clean Agent Modular Type Ceiling mounted Fire Extinguisher 5 Kgs Capacity made of Mild Steel Body of 1.6 mm thickness with pressure gauge, refillable device and safety release device CE Certified Brass valve suitable for A, B and C Classes of Fire complete with Charge of Clean agent (Gas) is also known as HFC Blend A, It is a blend of Hydro Fluoro carbon and organic detossificant essence P26. The sprinkler body will comprise of temperature sensitive quartsoid bulb of temperature rating of 680. The cylinder will be supplied with a proper mounting arrangement to mount it on the ceiling. The Extinguisher shall be externally epoxy powder coated as per IS: 5 Color Shade No. 538: 5 Kgs |
| 500 | SIGNAGES |
| 501 | SITC of self glowing \\"FIRE EXTINGUISHER\\" sign boards of size (150 X 150 mm) in triangular shape fixed on the wall and shall be as per IS code 9457:2005, IS 12349, IS 12407 |
| 502 | Supply, installation, testing and commissioning of Fire Exit Light, Laser type, with High Glow LED, size:300x 178 x 32 mm. or 390 x190 x 60mm, Ceiling Mounting type with hanging clamps, on/off switch, Red /Green Colour option with minimum of 25 Mtr. viewing distance, power consumption: 5.0 Watt per face (maximum) Double Side Display and shall be as per IS code 9457:2005, IS 12349, IS 12407. |
| 503 | Supply, installation, testing and commissioning of Fire Exit Light, Laser type, with High Glow LED, size:300x 178 x 32 mm. or 390 x190 x 60mm, Ceiling Mounting type with hanging clamps, on/off switch, Red /Green Colour option with minimum of 25 Mtr. viewing distance, power consumption: 5.0 Watt per face (maximum), with Single Side Display and shall be as per IS code 9457:2005, IS 12349, IS 12407. |
| 504 | Providing and fixing in position the signage \\" FIRE ORDER\\" on 3mm thick \\"Opaque\\" PVC foam board of computerized cut, PVC non reflective self adhesive vinyl painted foam board of 2' x 3' and shall be as per IS code 9457:2005, IS 12349, IS 12407 |
| 505 | Providing and fixing of Floor Identification Signage (MAIN STAIRCASE, FIRE STAIRCASE, FIRE ASSEMBLY POINT, PUMP ROOM, FIRE CONTROL ROOM, ELECTRICAL ROOM, FIRE LIFT, PASSENGER LIFT Etc.) on every floor, lettering size shall be 5 Cm. with contrasting colour from background. Size shall be 15cm x 30cm and shall be as per IS code 9457:2005, IS 12349, IS 1240 |
| 506 | Providing and fixing of Floor identification signage (e.g., GROUND FLOOR, FIRST FLOOR, etc.) will be placed at each stair enclosure on every floor, displaying the floor number in words. The letter size will be 5 cm, with a contrasting color to the background. The dimensions of the signage will be 15 cm x 30 cm, and it will comply IS Code 9457:2005, IS 12349, and IS 12407. |
| 507 | Providing and fixing of signage : \\"IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE\\" with red letters, each 1.25 cm in height, on a white background. The board dimensions will be 25 cm x 30 cm and will be mounted at a height of 2 meters from the finished floor, positioned near manual call points. The signage will comply with IS Code 9457:2005, IS 12349, and IS 1240 standards. |
| 508 | AUTHORITY APPROVAL |
| 509 | AUTHORITY APPROVALS AND COORDINATION: Preparation of all drawings, submitting and getting approval from fire department, submitting of completion certificates and arranging inspection, getting sanction, etc. for commissioning of the whole installation in the premises.(All statutory payments will be reimbursed with original receipts.) |
| 510 | FIRE ALARM SYSTEM |
| 511 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of response indicator on surface/ recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 512 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 513 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 514 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of addressable phone control module complete as required. |
| 515 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 516 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of fire fighter telephone handset complete as required |
| 517 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of fire fighter phone jack complete as required. |
| 518 | Supply, Installation, Testing and Commissioning of Automatic Analogue Addressable Smoke detector with auto floating sensitivity (to avoid resetting manually) complete with mounting base, LED indication, addressing rotary / dip switch / soft programing, junction box, cable termination using gland & locknut, connections etc including all accessories as required .Detector shall be UL Listed / FM Approved OR EN 54 Certified as applicable. |
| 519 | CABLING & WIRINGSupplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 520 | Supply, installation, testing and commissioning of public address and talk back system consisting of 2 zone public address cum 2 way talk back console with mike and selector, multiple channel talk back facility, power supply, battery charger, battery housing, multiple channel selector with all call and mic on. The console shall be provided with suitable capacity amplifier, and suitable capacity battery (min 12V), etc. complete as required for meeting the technical specifications The system shall operate on 230V AC mains with automatic changeover to battery backup during power failure. The battery backup shall provide minimum 30 minutes operation under full load condition. |
| 521 | Supply, Installation, Testing and Commissioning of Wall-Mounted Fire Fighter Talk Back Unit for two-way voice communication between fire fighters and the control room, complete with handset / speaker-microphone assembly, call indication LED, call push button, flush / surface mounting enclosure, termination accessories, and all necessary hardware required for proper installation and operation, in accordance with approved technical specifications |
| 522 | INTELLIGENT FIRE ALARM SYSTEMTwo Loop Panel Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 05, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 22, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysSep 23, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 15 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender