Defence Statutory Bodies & Commissions/Committees Closing in 6 days TDR #57375908

Tender For Repair/ Replacement & Maintenance Of Lt Switch Gear, Panel, Apfc Panel, Capacitor Bank And Connected Item At Certain Location Of Training Bn Of 1 Eme Center, Hq Tasa Under Age Em I Of Ge(U) Secunderabad

Issued by Statutory Bodies & Commissions/Committees · Hyderabad, Telangana
Tender Value
47 Lakhs
Estimated cost
Bid Submission
29 Sep 2026
6 days left
EMD
94000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Hyderabad → Telangana
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/ Replacement & Maintenance Of Lt Switch Gear, Panel, Apfc Panel, Capacitor Bank And Connected Item At Certain Location Of Training Bn Of 1 Eme Center, Hq Tasa Under Age Em I Of Ge(U) Secunderabad

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 18-Sep-2026 BOQ Corrigendum BOQ 29-Sep-2026
2 18-Sep-2026 Date Corrigendum Date 29-Sep-2026

BOQ

Name of Work:- REPAIR/ REPLACEMENT & MAINTENANCE OF LT SWITCH GEAR, PANEL, APFC PANEL, CAPACITOR BANK AND CONNECTED ITEM AT CERTAIN LOCATION OF TRAINING BN OF 1 EME CENTER, HQ TASA UNDER AGE EM I OF GE(U) SECUNDERABAD
Sl. No. Item Description
1Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600 Amps rating for phase and neutral 4 strips with colour
2coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
3MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415lt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
4MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing)
5MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
6Digital Ammeter 0 to 500 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
7Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
8Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
9Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour
10coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
11MCCB 4pole, 320 Amps, with adjustable thermal and magnetic settings, 36 KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
12MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 36 KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
13MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 25 KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
14MCCB 4pole, 63Amps, with adjustable thermal and magnetic settings, 18KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Outgoing)
15Digital Ammeter 0 to 300 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
16Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
17Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
18Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3 mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 300 Amps rating for phase and neutral 4 strips with colour
19coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
20MCCB 4pole, 200 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
21MCCB 3pole, 40 Amps, with adjustable thermal and magnetic settings, 27KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing)
22Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
23Digital Voltmeter 0-500 Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
24Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
25Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour
26coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
27MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415lt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
28MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 08 No (Outgoing)
29Digital Ammeter 0 to 500 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
30Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
31Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
32Digital Voltmeter 0-500 Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
33Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
34Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3 mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour
35coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
36MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
37MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 0 2No (Outgoing)
38MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 0 2No (Outgoing)
39MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 0 1No (Outgoing)
40Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
41Digital Voltmeter 0-500 Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
42Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
43Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour
44coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
45MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
46MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing)
47MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
48Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
49Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
50Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
51Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600 Amps rating for phase and neutral 4 strips with colour
52coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
53MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
54MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Outgoing)
55MCCB 4pole, 200 Amps, with adjustable thermal and magnetic settings, 35KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
56MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 04 No (Outgoing)
57Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
58Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
59Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
60Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600 Amps rating for phase and neutral 4 strips with colour
61coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
62MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
63MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
64MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing)
65Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
66Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
67Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
68Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour
69coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
70MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
71MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
72MCCB 4pole, 40 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 05 No (Outgoing)
73Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
74Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
75Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
76Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour
77coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
78MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
79MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
80MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
81MCCB 4pole, 40 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 05 No (Outgoing)
82Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set
83Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set
84Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
85S&F in repairs Weather proof outdoor bus bar chamber made out of 3mm thick MS sheet comprising of 125 Amps MCCB 16KA breaking capacity as incomer and 4 Nos aluminium strips each of 200Amps as outgoing busbar, 90cm long duly insulated mounted on insulators with 4 No’s mounting legs made out of 25mm x 25mm x 6mm angle iron grouted in PCC block of size 30cm x 30cm x 90cm (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), and connections with suitable size of aluminium thimbles, nuts, bolts & washers, cable glands at entry and outlet points and excavation, earth work, returning filling in and removal of surplus soils including taking out old unserviceable bus bar chamber complete all as specified and directed.
86Supply, installation connecting electrically commissioning and testing complete outdoor type, as recommended by manufacturer, Automatic Power Factor Correction(APFC) system 8 stage type intel VAr APFC Panel with heavy duty MPPH capacitors and MCCBs as incomer factory made single unit 440 volts, 50 Hz, 3 phase 100 KVAR (2No X 5 KVAR+ 3No X 10 KVAR+ 3 x 20 KVAR) including taking down old existing one and comprising with following provisions :- (a) Metallised polypropylene MPP-H capacitor bank heavy duty of rating 100 KVAR 2NoX5 KVAR+3No X 10 KVAR+ 3X20 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931 Make :- L&T/ EPCOS/ MEHER.(b) Capacitor duty contactor of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947, Make :- L&T/ C&S/BCH.(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors suitable to disconnect capacitor bank on No voltage. Visual alarm if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achieved (leading of lagging). Make :- L&T/ MEHER/ HAVELLS.(d) Digital volt meter and ammeter of range as required and recommended by manufacturer with in-built selector switch and CTs of appropriate ratio.(e) MCCB 63 Amps 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make:- L&T/Hager/ Legrand/ ABB/ Havells.(f) MCCB 200 Amps 4 pole 415 volts of appropriate current rating with rupturing capacity 35 KA as incomer confirming to IS 13947 part 2, IEC 947 2. Make:- L&T/Hager/ Legrand/ ABB/ Havells.
87Supply, installation connecting electrically commissioning and testing complete outdoor type, as recommended by manufacturer, Automatic Power Factor Correction(APFC) system 7 stage type intel VAr APFC Panel with heavy duty MPPH capacitors and MCCBs as incomer factory made single unit 440 volts, 50 Hz, 3 phase 70 KVAR (2 No X 5 KVAR+ 3 No X 10 KVAR + 2 No X 15 KVAR) including taking down old existing one and comprising with following provisions :- (a) Metallised polypropylene MPP-H capacitor bank heavy duty of rating 70 KVAR (2 No X 5 KVAR+ 3 No X 10 KVAR + 2 No X 15 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931, Make :- L&T/ EPCOS/ MEHER.(b) Capacitor duty contactor of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947, Make :- L&T/ C&S/BCH.(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors suitable to disconnect capacitor bank on No voltage. Visual alarm if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achieved (leading of lagging). Make :- L&T/ MEHER/ HAVELLS.(d) Digital volt meter and ammeter of range as required and recommended by manufacturer with in-built selector switch and CTs of appropriate ratio.(e) MCCB 63 Amps 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make:- L&T/Hager/ Legrand/ ABB/ Havells.(f) MCCB 160 Amps 4 pole 415 volts of appropriate current rating with rupturing capacity 35 KA as incomer confirming to IS 13947 part 2, IEC 947 2. Make:- L&T/Hager/ Legrand/ ABB/ Havells.
88Supply, installation connecting electrically commissioning and testing complete outdoor type, as recommended by manufacturer, Automatic Power Factor Correction(APFC) system 7 stage type intel VAr APFC Panel with heavy duty MPPH capacitors and MCCBs as incomer factory made single unit 440 volts, 50 Hz, 3 phase 50 KVAR (4 No X 5 KVAR+ 3 No X 10 KVAR)including taking down old existing one and comprising with following provisions :- (a) Metallised polypropylene MPP-H capacitor bank heavy duty of rating 50 KVAR (4 No X 5 KVAR+ 3 No X 10 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931 Make :- L&T/ EPCOS/ MEHER.(b) Capacitor duty contactor of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947, Make :- L&T/ C&S/BCH.(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors suitable to disconnect capacitor bank on No voltage. Visual alarm if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achieved (leading of lagging). Make :- L&T/ MEHER/ HAVELLS.(d) Digital volt meter and ammeter of range as required and recommended by manufacturer with in-built selector switch and CTs of appropriate ratio.(e) MCCB 63 Amps 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make:- L&T/HPL/ Legrand/ ABB/ HAVELLS.(f) MCCB 125 Amps 4 pole 415 volts of appropriate current rating with rupturing capacity 35 KA as incomer confirming to IS 13947 part 2, IEC 947 2. Make:- L&T/HPL/ Legrand/ ABB/ HAVELLS.
89Repair and maintenance of LT Panel of any capacity complete, including site inspection, shutdown, dismantling of damaged components, cleaning of panel, replacement/repair/Refixing of breakers, contactors, relays, meters, bus bars, insulators, control wiring, cable terminations and earthing connections as required, rust removal, painting, construction/repair of RCC foundation with excavation, PCC, grouting and fixing of foundation channels, reinstallation and alignment of panel as required, testing of insulation resistance, continuity, protection and control circuits, commissioning, trial operation under load, and all labour, materials, tools, tackles, transportation and incidental works required for satisfactory completion of the work as directed by the Engineer-in-Charge.
90Repair / maintenance, excluding major spares but including regular maintenance of the Automatic Power factor correction control panel capacity 50 to 125 KVAR and 3 to 8 stages installed at various locations at AGE E/M No I including carrying out complete maintenance / repairs as required of all the sub systems viz, based control panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT, MCBs / MCCBs for isolation (with all the accessories) any breakdown maintenance and replacement of unserviceable parts / new parts if any, project completion and trouble shooting responsibility also lies with the contractor including following provisions complete all as specified and directed.Notes :-(i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, replacement of defective control wiring, small parts such as Push buttons, lugs, any auxiliary contacts, auto selector switch etc and necessary servicing repair by expert technician and register will be maintained for the same.(ii) The scope of work includes the labour charges required for removing, repairing , refixing, carrying out electrical termination capacitor bank etc complete(iii) Major Spare parts will be measured as supply only under respective item.
91Supply only power factor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old existing capacitor complete all as specified and directed.
92All as per item No 17.00 above but 10 KVAR Capacitor.
93All as per item No 17.00 here-in-before but 15 KVAR Capacitor.
94All as per item No 17.00 here-in-before but 20 KVAR Capacitor.
95All as per item No 17.00 here-in-before but 25 KVAR Capacitor.Make for item No 19.00 to 19.04- L&T or equivalent make in Schneider/HPL
96Supply only APFC relay with auto-set function 6 stage, including taking down old existing relay complete all as specified and directed.Make:- L&T/schneider/siemens
97Supply only APFC relay with auto-set function 6 stage, including taking down old existing relay complete all as specified and directed.Make:- L&T/schneider/siemens
98S&F in repairs, 3pole 63Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
99S&F in repairs, 3pole 125Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
100S&F in repairs, 4pole 160Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
101S&F in repairs, 3pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
102S&F in repairs, 4pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
103S&F in repairs, 3pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
104S&F in repairs, 4pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
105S&F in repairs, 4pole 400Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
106S&F in repairs, 4pole 630Amp MCCB, 50KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
107M&L in repairs, Earthing complete with galvanized steel earth plate electrode of size 600 x 600 x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5m below normal ground level connected to GI strip 25x4mm as earth lead by means of bolts, nuts, washers and check nuts made out of galvanized iron or steel all as shown on Electrical Plate No. 3 of SSR Part-I including testing on completion complete all as specified and directed by Engr-in-charge.Note 1: The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, 50mm thick RCC 1:2:4 type B-1 using 20mm graded stone aggregate cover slab reinforced with 6 Nos of 8mm dia TMT bars both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe medium grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub-heading earthing, specified on Sl Page No. 422 of SSR Part-II. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57375908
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 47 Lakhs
LAST DATE 29-09-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/ Replacement & Maintenance Of Lt Switch Gear, Panel, Apfc Panel, Capacitor Bank And Connected Item At Certain Location Of Training Bn Of 1 Eme Center, Hq Tasa Under Age Em I Of Ge(U) Secunderabad
Basic Detail
Tender No GE (U)/SEC/TOKEN/M54 OF 2026-27
Bidding Type Tender
Location
City Hyderabad
State Telangana
Key Dates
Publish Date 18 Sep 2026
Submission Date 29 Sep 2026
Open Date 01 Jan 0001
Finance
Tender Value 47 Lakhs
Tender Fee 500
EMD 94000
Exemption Available
Document List
BOQ_883255.xls
ff12094c-b57a-43fb-9d9e-7d629c1f4181.html
M54_8660_Tender.pdf
Tendernotice_1 (9).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 18, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 29, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 6 days
Sep 29, 2026
18:00 IST

Corrigendum-2 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 6 days
Sep 29, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 6 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_883255.xls

html

ff12094c-b57a-43fb-9d9e-7d629c1f4181.html

pdf

M54_8660_Tender.pdf

pdf

Tendernotice_1 (9).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender