Tender For Repair/ Replacement & Maintenance Of Lt Switch Gear, Panel, Apfc Panel, Capacitor Bank And Connected Item At Certain Location Of Training Bn Of 1 Eme Center, Hq Tasa Under Age Em I Of Ge(U) Secunderabad
Tender Overview
Project Description
Tender for Repair/ Replacement & Maintenance Of Lt Switch Gear, Panel, Apfc Panel, Capacitor Bank And Connected Item At Certain Location Of Training Bn Of 1 Eme Center, Hq Tasa Under Age Em I Of Ge(U) Secunderabad
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 18-Sep-2026 | BOQ Corrigendum | BOQ | 29-Sep-2026 |
| 2 | 18-Sep-2026 | Date Corrigendum | Date | 29-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600 Amps rating for phase and neutral 4 strips with colour |
| 2 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 3 | MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415lt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 4 | MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing) |
| 5 | MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 6 | Digital Ammeter 0 to 500 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 7 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 8 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 9 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour |
| 10 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 11 | MCCB 4pole, 320 Amps, with adjustable thermal and magnetic settings, 36 KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 12 | MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 36 KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 13 | MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 25 KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 14 | MCCB 4pole, 63Amps, with adjustable thermal and magnetic settings, 18KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Outgoing) |
| 15 | Digital Ammeter 0 to 300 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 16 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 17 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 18 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3 mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 300 Amps rating for phase and neutral 4 strips with colour |
| 19 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 20 | MCCB 4pole, 200 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 21 | MCCB 3pole, 40 Amps, with adjustable thermal and magnetic settings, 27KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing) |
| 22 | Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 23 | Digital Voltmeter 0-500 Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 24 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 25 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour |
| 26 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 27 | MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415lt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 28 | MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 08 No (Outgoing) |
| 29 | Digital Ammeter 0 to 500 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 30 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 31 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 32 | Digital Voltmeter 0-500 Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 33 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 34 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3 mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour |
| 35 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 36 | MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 37 | MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 0 2No (Outgoing) |
| 38 | MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 0 2No (Outgoing) |
| 39 | MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 0 1No (Outgoing) |
| 40 | Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 41 | Digital Voltmeter 0-500 Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 42 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 43 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour |
| 44 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 45 | MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 46 | MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing) |
| 47 | MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 48 | Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 49 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 50 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 51 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600 Amps rating for phase and neutral 4 strips with colour |
| 52 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 53 | MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 54 | MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Outgoing) |
| 55 | MCCB 4pole, 200 Amps, with adjustable thermal and magnetic settings, 35KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 56 | MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 04 No (Outgoing) |
| 57 | Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 58 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 59 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 60 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600 Amps rating for phase and neutral 4 strips with colour |
| 61 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 62 | MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 63 | MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 64 | MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing) |
| 65 | Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 66 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 67 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 68 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour |
| 69 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 70 | MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 71 | MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 72 | MCCB 4pole, 40 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 05 No (Outgoing) |
| 73 | Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 74 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 75 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 76 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour |
| 77 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- |
| 78 | MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) |
| 79 | MCCB 4pole, 160 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 80 | MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) |
| 81 | MCCB 4pole, 40 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 05 No (Outgoing) |
| 82 | Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
| 83 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
| 84 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
| 85 | S&F in repairs Weather proof outdoor bus bar chamber made out of 3mm thick MS sheet comprising of 125 Amps MCCB 16KA breaking capacity as incomer and 4 Nos aluminium strips each of 200Amps as outgoing busbar, 90cm long duly insulated mounted on insulators with 4 No’s mounting legs made out of 25mm x 25mm x 6mm angle iron grouted in PCC block of size 30cm x 30cm x 90cm (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), and connections with suitable size of aluminium thimbles, nuts, bolts & washers, cable glands at entry and outlet points and excavation, earth work, returning filling in and removal of surplus soils including taking out old unserviceable bus bar chamber complete all as specified and directed. |
| 86 | Supply, installation connecting electrically commissioning and testing complete outdoor type, as recommended by manufacturer, Automatic Power Factor Correction(APFC) system 8 stage type intel VAr APFC Panel with heavy duty MPPH capacitors and MCCBs as incomer factory made single unit 440 volts, 50 Hz, 3 phase 100 KVAR (2No X 5 KVAR+ 3No X 10 KVAR+ 3 x 20 KVAR) including taking down old existing one and comprising with following provisions :- (a) Metallised polypropylene MPP-H capacitor bank heavy duty of rating 100 KVAR 2NoX5 KVAR+3No X 10 KVAR+ 3X20 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931 Make :- L&T/ EPCOS/ MEHER.(b) Capacitor duty contactor of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947, Make :- L&T/ C&S/BCH.(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors suitable to disconnect capacitor bank on No voltage. Visual alarm if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achieved (leading of lagging). Make :- L&T/ MEHER/ HAVELLS.(d) Digital volt meter and ammeter of range as required and recommended by manufacturer with in-built selector switch and CTs of appropriate ratio.(e) MCCB 63 Amps 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make:- L&T/Hager/ Legrand/ ABB/ Havells.(f) MCCB 200 Amps 4 pole 415 volts of appropriate current rating with rupturing capacity 35 KA as incomer confirming to IS 13947 part 2, IEC 947 2. Make:- L&T/Hager/ Legrand/ ABB/ Havells. |
| 87 | Supply, installation connecting electrically commissioning and testing complete outdoor type, as recommended by manufacturer, Automatic Power Factor Correction(APFC) system 7 stage type intel VAr APFC Panel with heavy duty MPPH capacitors and MCCBs as incomer factory made single unit 440 volts, 50 Hz, 3 phase 70 KVAR (2 No X 5 KVAR+ 3 No X 10 KVAR + 2 No X 15 KVAR) including taking down old existing one and comprising with following provisions :- (a) Metallised polypropylene MPP-H capacitor bank heavy duty of rating 70 KVAR (2 No X 5 KVAR+ 3 No X 10 KVAR + 2 No X 15 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931, Make :- L&T/ EPCOS/ MEHER.(b) Capacitor duty contactor of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947, Make :- L&T/ C&S/BCH.(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors suitable to disconnect capacitor bank on No voltage. Visual alarm if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achieved (leading of lagging). Make :- L&T/ MEHER/ HAVELLS.(d) Digital volt meter and ammeter of range as required and recommended by manufacturer with in-built selector switch and CTs of appropriate ratio.(e) MCCB 63 Amps 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make:- L&T/Hager/ Legrand/ ABB/ Havells.(f) MCCB 160 Amps 4 pole 415 volts of appropriate current rating with rupturing capacity 35 KA as incomer confirming to IS 13947 part 2, IEC 947 2. Make:- L&T/Hager/ Legrand/ ABB/ Havells. |
| 88 | Supply, installation connecting electrically commissioning and testing complete outdoor type, as recommended by manufacturer, Automatic Power Factor Correction(APFC) system 7 stage type intel VAr APFC Panel with heavy duty MPPH capacitors and MCCBs as incomer factory made single unit 440 volts, 50 Hz, 3 phase 50 KVAR (4 No X 5 KVAR+ 3 No X 10 KVAR)including taking down old existing one and comprising with following provisions :- (a) Metallised polypropylene MPP-H capacitor bank heavy duty of rating 50 KVAR (4 No X 5 KVAR+ 3 No X 10 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931 Make :- L&T/ EPCOS/ MEHER.(b) Capacitor duty contactor of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947, Make :- L&T/ C&S/BCH.(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors suitable to disconnect capacitor bank on No voltage. Visual alarm if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achieved (leading of lagging). Make :- L&T/ MEHER/ HAVELLS.(d) Digital volt meter and ammeter of range as required and recommended by manufacturer with in-built selector switch and CTs of appropriate ratio.(e) MCCB 63 Amps 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make:- L&T/HPL/ Legrand/ ABB/ HAVELLS.(f) MCCB 125 Amps 4 pole 415 volts of appropriate current rating with rupturing capacity 35 KA as incomer confirming to IS 13947 part 2, IEC 947 2. Make:- L&T/HPL/ Legrand/ ABB/ HAVELLS. |
| 89 | Repair and maintenance of LT Panel of any capacity complete, including site inspection, shutdown, dismantling of damaged components, cleaning of panel, replacement/repair/Refixing of breakers, contactors, relays, meters, bus bars, insulators, control wiring, cable terminations and earthing connections as required, rust removal, painting, construction/repair of RCC foundation with excavation, PCC, grouting and fixing of foundation channels, reinstallation and alignment of panel as required, testing of insulation resistance, continuity, protection and control circuits, commissioning, trial operation under load, and all labour, materials, tools, tackles, transportation and incidental works required for satisfactory completion of the work as directed by the Engineer-in-Charge. |
| 90 | Repair / maintenance, excluding major spares but including regular maintenance of the Automatic Power factor correction control panel capacity 50 to 125 KVAR and 3 to 8 stages installed at various locations at AGE E/M No I including carrying out complete maintenance / repairs as required of all the sub systems viz, based control panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT, MCBs / MCCBs for isolation (with all the accessories) any breakdown maintenance and replacement of unserviceable parts / new parts if any, project completion and trouble shooting responsibility also lies with the contractor including following provisions complete all as specified and directed.Notes :-(i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, replacement of defective control wiring, small parts such as Push buttons, lugs, any auxiliary contacts, auto selector switch etc and necessary servicing repair by expert technician and register will be maintained for the same.(ii) The scope of work includes the labour charges required for removing, repairing , refixing, carrying out electrical termination capacitor bank etc complete(iii) Major Spare parts will be measured as supply only under respective item. |
| 91 | Supply only power factor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old existing capacitor complete all as specified and directed. |
| 92 | All as per item No 17.00 above but 10 KVAR Capacitor. |
| 93 | All as per item No 17.00 here-in-before but 15 KVAR Capacitor. |
| 94 | All as per item No 17.00 here-in-before but 20 KVAR Capacitor. |
| 95 | All as per item No 17.00 here-in-before but 25 KVAR Capacitor.Make for item No 19.00 to 19.04- L&T or equivalent make in Schneider/HPL |
| 96 | Supply only APFC relay with auto-set function 6 stage, including taking down old existing relay complete all as specified and directed.Make:- L&T/schneider/siemens |
| 97 | Supply only APFC relay with auto-set function 6 stage, including taking down old existing relay complete all as specified and directed.Make:- L&T/schneider/siemens |
| 98 | S&F in repairs, 3pole 63Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 99 | S&F in repairs, 3pole 125Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 100 | S&F in repairs, 4pole 160Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 101 | S&F in repairs, 3pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 102 | S&F in repairs, 4pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 103 | S&F in repairs, 3pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 104 | S&F in repairs, 4pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 105 | S&F in repairs, 4pole 400Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 106 | S&F in repairs, 4pole 630Amp MCCB, 50KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified. |
| 107 | M&L in repairs, Earthing complete with galvanized steel earth plate electrode of size 600 x 600 x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5m below normal ground level connected to GI strip 25x4mm as earth lead by means of bolts, nuts, washers and check nuts made out of galvanized iron or steel all as shown on Electrical Plate No. 3 of SSR Part-I including testing on completion complete all as specified and directed by Engr-in-charge.Note 1: The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, 50mm thick RCC 1:2:4 type B-1 using 20mm graded stone aggregate cover slab reinforced with 6 Nos of 8mm dia TMT bars both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe medium grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub-heading earthing, specified on Sl Page No. 422 of SSR Part-II. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 6 daysCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 6 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender