Tender For Provn Of Fire Alarm System At Various Locations At Afs Yelahanka.
Tender Value
43.20 Lakhs
Estimated cost
Bid Submission
25 Sep 2026
18 days left
EMD
86406
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bengaluru Urban → Karnataka
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Fire Alarm System At Various Locations At Afs Yelahanka.
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil complete all as specified and directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in not exceeding 25 cm thick complete all as specified and directed. |
| 3 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 4 | M & L for Boring of holes under roof, pavement, hardstanding by trenchless technology using ultrasound technique and necessary machine including HDPE pipe of 50mm dia suitable for 0.4mpa working pressure complete all as specified and directed. |
| 5 | Supply, Installation, testing and commissioning & Programming of Microprocessor based addressable four loop capacity, Networkable type fire alarm control panel with log history. The panel should be equipped with sufficient numbers of 1 loop with up to 10 to 15% spare capacity with each loop shall have a capacity of minimum 99 detectors and 99 analog addressable devices in one loop with features four access levels, capable of taking flash scan devices, 240 Volts AC power supply automatic battery charger, 24 AH, 2x12 Volts sealed lead acid batteries sufficient for 48 hours during an emergency conditions as required. The panel shall be as per tech specification EN54/ UL listed RS 232 communication port and RS 422 Network card complete including relay modular on front, confront module, asson module etc in all respect all as specified and directed.MAKE : HONEYWELL /GST/ASES |
| 6 | Supply, installation, testing and commissioning Microprocessor based Intelligent Addressable multi sensor type Heat & Smoke detectors (Combination of Photo electric & thermal sensor) with bases including fixed on metal junction of size 75x75x50 mm with metal glands and gasket. The detector shall sense fire / smoke and generate alarm if any Fire / smoke occurred in the building. The detectors shall have Two built in LEDs for 360 degree viewing complete all as specified and directed.MAKE : HONEYWELL/GST/ASES |
| 7 | Supply and fix addressable manual call point resettable type complete all specified and directed.MAKE : HONEYWELL/GST/ASES |
| 8 | Supply and fix addressable electronic sounder cum strobe complete all specified and directed.MAKE : HONEYWELL/GST/ASES |
| 9 | Supply and laying of 6 fibre single mode, armoured, ISO/IEC-11801, EN50173, ANSI/TIA-586-C3, fibre optic cable complete all specified and directed.MAKE : HONEYWELL/GST/ASES |
| 10 | Supply & laying of 4 Core, 1.5 Sqmm armoured FRLS insulated & sheathed copper cable complete all specified and directed. |
| 11 | Supply and laying HDPE Pipe 40mm dia for OFC cables complete all specified and directed. |
| 12 | Supply and fix cable route indicator made out of 3 mm thick MS sheet of size 20 cm x 15 cm duly painted with two coats black paint over a coat of red oxide primer and writing cable direction, type of cable with white paint, mounted on angle iron 40x40x3 mm, angle height 45 cm, (30cm below ground level) with PCC 20cmx20cmx15cm complete all as specified and as directed. |
| 13 | Supply, installation, testing and commissioning Intelligent addressable Short Circuit Isolator (Fault Isolation Module) shall be suitable for DIN rail mounting and mounted external device shall display status of Tri colour with Open, short circuit LED status indication for normal, The Device shall be suitable for Loop connectivity. (The FIM shall be considered for every 20/22 devices as the site condition) complete all as specified and directed.MAKE : HONEYWELL/GST/ASES |
| 14 | Supply, installation, testing and commissioning Addressable control module complete all as specified and directed. MAKE : HONEYWELL/GST/ASES |
| 15 | Supply and fix Duct detector Photoelectric, integrated low-flow technology having Air velocity rating from1.5m/s to 20.3m/sec, Versatile mounting options, square or rectangular configuration, Broad ranges for operating temperature −20°C to 70°C and humidity, 0% to 95% Complete all as specified and directed. MAKE : HONEYWELL/GST/ASES |
| 16 | Supply and fix Active repeater panel of DIMENSIONS [MM] (H X W X D) 165 x 254 x 50,OPERATING TEMPERATURE +5°C to +45°C,RELATIVE HUMIDITY 5% - 95% non-condensing, Compatible with all intelligent multiprotocol fire alarm control panels • Connects to RS485 peripheral bus• Active or Passive options• Backlit adjustable alphanumeric display• General status LEDs• Controls for system reset, accept, mute, silencealarms, and self-test (active repeater only)• “Access Enable” key-switch on active repeater complete all as specified and directed. MAKE : HONEYWELL/GST/ASES |
| 17 | Supply, installation testing and commissioning of gas based automatic gas suppression system consisting of following equipments :- (a) 67.8 Ltrs cylinder with valve -01 Nos (b) Sinor (NOVEC-1230 -55 Kgs © Master cylinder comprising below items (i) Pressure gauge + Low pr supervisory switch (ii) electromagnetic actuator (iii) Pneumatic actuator (iv) Flexible discharge hose (v) flexible actuation hose (vi) manual & Pneumatic actuator (vii) Union 7/16 JIC 1/8 (d) Nozzles -02 Nos (e) Pressure switch -01 Nos (f) Manifold check valve -01 nos (g) Discharge pressure switch -01 nos (h) gas release panel -01 Nos (j) Container Strap -01 Nos (k) release switch -01 Nos (l) abort switch -01 Nos (m) Signage -01 Nos (n) Hooter -01 Nos (o) Seamless piping -01 Lot (as per OEM Recommendation and user requirement) complete all as specified and directed.MAKE : HONEYWELL/GST/ASES |
| 18 | M&L for fixing and installation of motorised siren \\"Dual Tone\\" of range 2 KM with driving unit installed at technical bldg complete all as specified and directed.MAKE : HONEYWELL/GST/ASES |
| 19 | Supply and laying GI tubing light grade 50mm dia in trenches/fixing on pole /wall/crossing in drain etc. for protection of UG cable complete all as specified and directed. |
| 20 | Supply and fixing voltage stabilizer for automatic operation of capacity 1 KVA single phase naturally air-cooled indoor type and designed for input variation between 170 KVA to 250 KVA with output voltage stabilized at 230 V with accuracy of + 5% of capacity complete all as specified and directed.MAKE : V GUARD /VOLTAS /SERVOKON |
| 21 | M&L for sub main wiring in PVC casing and caping of required size 4sqmm PVC insulated multistrand copper conductor FRLS with 01x4 Sqmm PVC insulated multistrand copper conductor as earth continuity wire all as specified and directed. Note: - For the purpose of payment two runs of 4sqmm conductors and one run of 4 Sqmm conductor with casing caping will be measured as one length. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 04, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 25, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysOct 03, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 26 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender