Tender For Replacement Of Two Nos Of Old 500Kva Dg Set With Two Nos Of New Dg 500Kva Set With Allied Fire And Fabrication Works In Worli Hub
Tender Value
Ref. Documents
Estimated cost
Bid Submission
18 Sep 2026
3 days left
EMD
1.98 Lakhs
Bank guarantee accepted
Document Fee
23559
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mumbai → Maharashtra
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Replacement Of Two Nos Of Old 500Kva Dg Set With Two Nos Of New Dg 500Kva Set With Allied Fire And Fabrication Works In Worli Hub
BOQ
| Sl. No. | Item Description |
| 1 | Work of replacing power backup systems at Worli Hub |
| 2 | SITC of D.G.SET WITH PANEL -500KVA (R3-ME-6-17-qq) |
| 3 | 1st category Al armoured cables FRLS outer sheathed- 3.5C x 300 Sq.mm(R3-ME-2-1-ac) |
| 4 | Cable End Termination For Aluminium Cables – 3.5C x 300 Sq.mm (R3-ME-2-12-ac) |
| 5 | 1st category Al armoured cables FRLS outer sheathed- 2C x 2.5 Sq.mm (R3-ME-2-3-e) |
| 6 | Cable End Termination For Al Cables – 2C x 1.5 / 2.5 Sq.mm (R3-ME-2-12-a) |
| 7 | 600 X 600 X 3.15 mm Copper Plate, 3000mm dip with suitable size cu strip earth pit as per IS 3043. The earth pit shall be provided with watering pipe (Class B) with wire messed funnel, 25X3 cu strip / 2X8SWG Cu.wire up to chamber, disconnecting links with 600 x 600 mm (clear) RCC chamber & 3mm thick heavy duty CI chequered plate cover with hinge. Bentonite shall be provided for earth pits. Excavation, back filling, removal of excess soil is included in the scope. (R3-ME-7-1-d) |
| 8 | Earthing Continuity Conductors -25 x 3mm Tinned copper. (R3-ME-7-4-a) |
| 9 | Earthing Continuity Conductors -50 x 6mm GI (R3-ME-7-4-g) |
| 10 | Supplying and erecting Fire resistant Mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30- 2011 suitable to seal the openings with all kinds of cables, pipes and cable support system in steel and aluminium and plasticprofiles (Except hollow core conductors). The residual openings shall be closed with filler, as per specification(R3-ME-15-27-a) |
| 11 | Supplying standard first aid box with necessary antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Bandaid) adhesive tape for medicinal use, scissors, anti-septic solution etc. (All above contents shall be of standard makes)(R3-ME-15-31-d) |
| 12 | Removal of cable from 1.5 sq.mm to 3-1/2 core x 35 sq.mm.(R3-ME-8-1-h) |
| 13 | Removal of cable above 3-1/2 core x 120 Sq.mm upto 3-1/2 core x 400 sq. mm.(R3-ME-8-1-k) |
| 14 | Removal of DG set(R3-ME-8-1-V) |
| 15 | The scope includes design,provide,laying& installtn of 9 kg DPP Standalone,AFD system with C02 gas fire suppression systm designed to provide a uniform concentration within the electrical panels.The systm shall have Cert. of Compliance from UL,standard(s) for safety2127/NFPA 12.Storage cylinders with steel bracket, extinguishing agent,detectn tube, cylinder valve and associated accessories including adaptors, pressure switch, fire detectn tube fittings will be provided with the complete operatn of systm.Safety requirements such as warning signs,discharge alarm shall be part of the systm. The detectn tube(Sensitivity temp 95°C+15°C) shall be fixed withcylinder valve at top of cylinder. The tube shall be pressurized with dry nitrogen. In case of fire and on reaching of pre-determined temp., the tube shall rupture and gas shall be released instantly from the tube.The pressure switch shall be provided for indication fordischarge of gas. Cylinder& detetction tube shall be UL approved.(FAIR-DPPAFD9) |
| 16 | Fire Extinguiosher should be for all type of Fire A-B-C. It should have a delivery mechanism of multidirectional nozzle with conicaldeflector and SS 316 cap with black colour powder coating. It Should have thickness of 1.22mm. It shoild have high metal strength whichprovides durability.(FAIR-CLN-AGENT-1) |
| 17 | Fire bucket , stand,hook and First Aid Box-Providing Round bottom FIRE Bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I.sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook.(R3-ME-15-31-A) |
| 18 | Fire bucket , stand,hook and First Aid Box-Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver Paint.(R3-ME-15-31-B) |
| 19 | Removing & refixing of MS shed by increasing height and length as per proper site requirment for new DG. (15feet hight x 12feet width x 45feet length approximate). |
| 20 | Removing & refixing of of MS plateform by increasing width and length as per proper site requirment for new DG. (4feet hight x 12feet width x 45feet length approximate). |
| 21 | Scrapping and fire retardant painting with including 2 coat of primer and coats of animal paint at MS shutter panel room , DG Shed MS shed and DG MS plateform as per site requirment |
| 22 | SITC of 500Kva D.G Set Synchronising panel, The panel shall be a floor-mounted, free-standing, DG Synchronizing cum Load Sharing Panel designed for parallel operation of 500 kVA (or multiple DG sets totaling up to 1000 kVA capacity) with automatic synchronization, load sharing, auto load shedding/restoration, and bypass bus coupler facility. The panel shall be suitable for 415 V, 3-phase, 4-wire, 50 Hz system and compliant with IS 8623, IEC 61439, and relevant fire safety norms , Fabrication material: 2 mm thick CRCA sheet steel ., Degree of protection: IP-54 (dust & splash proof) – suitable for indoor installation in fire station/control room.,Powder coating: RAL 7032 Smoke Grey (textured finish)., Gland plate: 3 mm thick at bottom with removable gland plate. ,Busbar chamber, instrument chamber & cable alley separated by sheet metal barriers.,Door: Hinged with 3-point locking arrangement & neoprene gasket.,Lifting arrangement: Eye bolts / lifting lugs.,Earth bus: Full-length GI earth busbar at bottom with 2 Nos. earthing terminals.BUSBAR Material: High conductivity Aluminium (E91E grade or equivalent).,Current rating: Suitable for 1000 kVA load (minimum 1000–1250 A rating with derating factor).,Insulation: Heat shrinkable PVC sleeves (color coded – RYB + Black for neutral).,Support: SMC / DMC insulators at suitable intervals.,Neutral busbar: Separate & fully rated (100% of phase busbar). Provision for connection from 500kva DG AMF Panel- 1 and 500kva DG AMF Panel-2 In Synchroninsing panel Bus Coupler: ACB 1000 A, 4-pole, 50 kA, with bypass provision (manual/auto changeover with interlock) for maintenance of any incomer without load interruption., Bypass Bus Coupler arrangement : Manual / motorized changeover with mechanical & electrical interlocks to allow individual breaker isolation while maintaining power continuity. Microprocessor-based Auto Synchronizing Relay (e.g., Woodward Easygen / DEIF / ComAp / equivalent) with Auto synchronization, Isochronous / droop load sharing, Reverse power protection, Synchro-check relay, Auto start/stop sequencing, Load-dependent start/stop, Master-slave configuration. Auto Mains Failure logic integration (if grid incomer is present), Auto Load Shedding / Restoration facility (priority-based for fire pump, emergency loads).Multifunction Meter (Class 0.5 accuracy) with RS-485 MODBUS port Suitable for IOT., indication lamps (LED type): RYB phase, DG ON, Breaker ON/OFF/TRIP, Synch ON, Fault, etc, Annunciation window: 8–16 windows with audible hooter for faults (over/under voltage, over/under frequency, low lube oil, high water temp, etc.).,Push buttons: Auto/Manual/Test, Emergency Stop, Accept/Reset. IoT / Remote Monitoring Features, IoT Gateway / Module integrated with RS-485 MODBUS communication, Protection & Safety Over-current, Short-circuit, Earth-fault protection on all breakers., Reverse power, Under/over frequency, Under/over voltage.,Phase sequence & phase failure protection.,Interlocks: Mechanical & electrical (to prevent paralleling out-of-sync). Emergency stop mushroom push button (external).Space heater with thermostat (anti-condensation). Factory acceptance test as per IEC 61439. Panel testing: Insulation resistance, HV test, functional test, synchronization test, load sharing test, IoT connectivity test.Training to fire department personnel on operation & monitoring. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 04, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 18, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysSep 21, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓