Tender For Repair / Replacement Of Old Unsv Rusted Pipe Line,Pump/Motor.Cleaning Of Over Head Tank And Connected Works Of External Water Supply ; Repairs/Maint Lt Panels & Earthing ;Repair/Maint To Lt External Electrification Atsigar Mil Stn Under Ge
Tender Overview
Project Description
Tender for Repair / Replacement Of Old Unsv Rusted Pipe Line,Pump/Motor.Cleaning Of Over Head Tank And Connected Works Of External Water Supply ; Repairs/Maint Lt Panels & Earthing ;Repair/Maint To Lt External Electrification Atsigar Mil Stn Under Ge 872 Ews
BOQ
| Sl. No. | Item Description |
| 1 | M&L for dismantling / demolition unserviceable Prestressed Cement Concrete (if required on ground) / LT Steel Tubular Pole of any description and any size after taking proper electric shut down from the concerened JE(E/M) / Engr-in-Charge. On demolition / taking out of old electric pole will be kept aside in safe custody to issue under schedule of credit. The job includs made good to the disturbed ground surface area, complete all as specified and as directed.NOTE : Unserviceable pole will be dismantled at ground level and disturbed ground will made good as directed for which earthwork, demolition Cement Concrete, etc. will not be measured and paid separately. |
| 2 | Material & Labour for steel tubular swaged pole 410 SP-31 (9.0 metre long) seamless type, including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of bituminious paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed. Note- Earthwork shall be measured and paid seperately. Volume occupied by steel pole shall be deducted to derive the quantity of PCC. |
| 3 | Supply and fixing new MS Cross arms, bracings, supports, clamp and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any type, shape or as indicated and directed inclusive of one coat of red oxide and one coat of aluminium paint and Incl taking down existing rusted/worn out MS cross arm, angle, clamps, nuts, bolts and washers complete all as specified and directed. . |
| 4 | M&L for taking down unserviceable/rusted GI Earth Wire, Cradles Guards of any size and shape at any Position from LT Electric Poles of any size and capacity, complete all as specified and as directed. |
| 5 | S&F Insulator Pin type, 100mm height, 65mm dia for 1100 Volt grade, Porcelain, Vitreous, white, brown or green including One Galvanised Mild Steel Spindle Two Galvanised Iron Washer and One Galvanised Iron Nut including Taking down unserviceable Insulator, complete all as specified and as directed. |
| 6 | S&F Insulator Shackle type, Porcelain, Vitreious, white brown or green of size 75mm High & 90mm dia including Galvanised Mild Steel Straps of Section 31x3.0mm, 12mm dia Insulator Bolts, Nuts, Washer, etc. for Working Pressure 1100 Volt grade including Taking down unserviceable Insulator, complete all as specified and as directed. |
| 7 | M&L for dismantling LT stay assembly complete of any description, complete all as specified and as directed.NOTE : Unserviceable Stay Assembly will be dismantled at Ground Level and disturbed Ground will Made Good as directed for which. Earth Works, demolition of Cement Concrete etc. will not be Measured & Paid separately. |
| 8 | Material & Labour for Stay assembly Diameter of stay rod in 20 mm incl stay insulator or egg insulator complete with all accessories as shown in electrical plate No. 1 and Incl dismantling existing stay assembly complete all as specified and directed. |
| 9 | Material & Labour for Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size and incl taking down unsv Danger notice plate of any size complete all as specified and directed. |
| 10 | M&L Galvanised Iron Wire 4.0mm dia (8 SWG) as Continuous Earth Wire, Guards and Cradles (hexagonal/rectangular), etc. and binding with and including GI Binding Wire 1.6mm dia, complete all as specified and as directed. |
| 11 | Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 Sqmm 3.5 core, fixing along the poles or passing through pipes or laid under floor of through walls etc jointing and testing complete all as specified and directed. (Note: Excavation and earth work will be measured and paid seperately) |
| 12 | Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 Sqmm 4.0 core, fixing along the poles or passing through pipes or laid under floor of through walls etc jointing and testing complete all as specified and directed. (Note: Excavation and earth work will be measured and paid seperately) |
| 13 | Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 Sqmm 2.0 core, fixing along the poles or passing through pipes or laid under floor of through walls etc jointing and testing complete all as specified and directed. (Note: Excavation and earth work will be measured and paid seperately) |
| 14 | Excavation in trenches, not exceeding 1.5 M wide and not exceeding 1.5 M depth for foundation, trenches for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10sq m on plan and n exc 1.5m in depth and getting out in Soft/disintigrated rock complete all as specified and directed. |
| 15 | Description all as per Srl item No. 14 here in before but exceeding 1.5 m width and not exceeding 3.00 m in depth. |
| 16 | Material & Labour for Sand cushioning to under ground cable in trenches/existing cable trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified by Engr-in-Charge. |
| 17 | Supply and laying locally available best quality, well burnt sub class B bricks (old size i.e. 230x115x75mm), laid dry in trenches for protection of UG cables complete all as specified and directed. |
| 18 | Returning, Filling in including Spreading, Levelling, Watering, Well Ramming in Layers not exc. 25 Cm, Providing Heaps along the Route of the pipe Line with Surplus Soil in Soft/disintigrated rock complete all as specified and as directed. |
| 19 | Removing Soft/disintigrated rock excavated material not exc. 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and directed. |
| 20 | Supply & laying (in replacement) galvanized steel tubing \\"light grade\\" with GI fittings in trenches/ under roads/ along pole/ wall for cable protection of size 50mm bore dia all as specified & directed. |
| 21 | Supply & laying (in replacement) galvanized steel tubing \\"light grade\\" with GI fittings in trenches/ under roads/ along pole/ wall for cable protection of size 40mm bore dia all as specified & directed. |
| 22 | Material and labour for providing cement concrete 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) as in foundation filling complete all as specified and directed . |
| 23 | Material and labour for providing cement concrete 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) for copping of poles including necessary form work and finished the surface complete all as specified and directed. |
| 24 | M & L for plain cement concrete (1:2:4), type B1 (using 20mm graded stone aggregate) as in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating, including necessary formwork complete all as specified and as directed. |
| 25 | M & L for preparing and painting and painting on steel tubular swaged pole 410 SP-22/31 (8.5/9.00 metre long) including cross arms, GI brackets with two coats of aluminium paint over a coat of aluminium red oxide primer on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed. |
| 26 | Supplying and laying synthetic rubber insulated mats 2 mm thick for voltage upto 1100Volts for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified or directed. |
| 27 | Re-straining and tightening of existing serviceable ACSR conductor of any size without taking down including all arangement and including binding wire 2 mm dia and colour sleeve Jumpers complete all as specified and directed. |
| 28 | Material & Labour for Trimming of tree branches Clearing of LT line 4 mtr all around by cutting tree branches at ground level of any numbers and any girth on any numbers of conductors/earth wire complete all as specified and directed. |
| 29 | S&F MCCB 63 Amp, 3 Pole, 415 Volt, 16 kA with Thermal Magnetic Trip Unit including Outgoing and Incoming Cable Connection and fixing to existing Panel Board and connecting up including Taking down/out unserviceable MCCB, complete all as specified and as directed. |
| 30 | S & F in repair PVC/fibre separator for LT over head line 1100 volts conductor 3/4 wire system for horizontal minimum 04xNos in each span complete with nuts, bolts including taking down old separator complete all as specified and as directed . |
| 31 | S & F in repair LED ammeter, 0-50 Amps of dial size 96x96mm flush mounting with accuracy class 1.0, single phase complete all as specified and directed. |
| 32 | S & F in repair LED Voltmeter, 0-500 Volt of dial size 96x96mm flush mounting with accuracy class 1.0, single phase complete all as specified and directed. |
| 33 | Material & Labour for Earthing with Galvanised Earth Plate Electrode 600x600x6.0mm thick, buried directly in Ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below normal Ground Level, connected to Galvanised Earth Lead Wire 4.0mm dia by means of Bolts, Nuts, Check, Nuts and Washers of Galvanised Iron or Steel and Earth Wire protected with and including GI Pipe 15mm bore (dia) Light grade, connected to Test Point upto 7.50 Metre away from Earth Electrode situated, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc.150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, PGI Funnel with GI Watering Pipe 20mm bore (dia) Medium grade including necessary Excavation in Soft/ Loose Soil, Returning, Filling in and Removal of surplus Spoil upto a distance of 50.00 Metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including Taking down/out Unserviceable Earthing of any description, complete all as per specified and as directed. |
| 34 | Material & Labour for Earthing with Galvanised Earth Plate Electrode 600x600x6.0mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with and including Galvanised Earth Strip of size 32x6.0mm by means of Bolts, Nuts, Check nuts and Washers of GI or Steel and connected Earthing Testing Point/Bus-bar with GI 40mm bore (dia) Light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc. 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, PGI Funnel with GI Watering Pipe 20mm bore (dia) Medium grade including necessary Excavation in Soft/Loose Soil, Returning, Filling in and Removal of surplus Spoil upto a distance of 50.00 Metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including Taking down/out Unserviceable Earthing of any description, complete all as per specified and as directed. |
| 35 | S & F in repairs 35 Watt LED Street light fittings, New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having Bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK08 including lamp and connections complete all as specified and as directed. Make : Havell's/CG/Bajaj/HPL etc or other equivelant make as per list of manufacturer. |
| 36 | S & F in repairs 60 Watt LED Street light fittings, New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and Toughened glass having Bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK07 including lamp and connections complete all as specified and as directed.. |
| 37 | S&F LED Flood light 70 watt 230 V, AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp including Taking down Unserviceable Flood Light Fitting of any description from any Height, complete all as specified and directed |
| 38 | S&F LED Flood light 100 watt 230 V, AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp including Taking down Unserviceable Flood Light Fitting of any description from any Height, complete all as specified and directed |
| 39 | S&F LED Flood light 120 watt 230 V, AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp including Taking down Unserviceable Flood Light Fitting of any description from any Height, complete all as specified and directed |
| 40 | S&F Shock Proof, Rust Proof, Fire Retradrant, Non-transparent Kiosks Pole Box of size 270x170x120mm made of Engineering Plastic on Piece moulding for Outdoor type, Heavy duty with 4 No. insulated Alunminium Bus-bar of 60 Amp capacity, mounted on Unbreakable Insulators MCB SP, 10 Amp, complete with Aluminium Lugs of suitable size upto 50 Sqmm including 2 No. Flat Iron 40x3mm Clamps with suitable size Mild Steel Bolts, Nuts & Washers, etc. and duly Painted on Both Sides with Two Coats of Synthetic Enemel Paint over a Coat of Red Oxide Zinc Chrome Primer including Taking down Unserviceable Pole Box of any description from any Height, complete all as specified and as directed. |
| 41 | Supply and fixing 1.5sqmm 3 core single phase copper conductor multistranded cable PVC insulated screened, PVC bedded, un-armoured, electric power cables (heavy duty) 1100 volts grade with stranded copper conductor for street light/bldg security light fittings through existing pipe/pole on wall/pole from junction box/LT over head line to fittings all as per site conditions or as directed. |
| 42 | S&F in replacement MCCB, 4 pole, 100 Amps, 415 Volts, breaking capacity 25 KA, adjustable thermal and fixed magnetic setting fixed-in-repairs, including taking out old unserviceable MCCB of any description complete all as specified and as directed.. |
| 43 | S&F in replacement MCCB, 4 pole, 125 Amps, 415 Volts, breaking capacity 25 KA, adjustable thermal and adjustable magnetic setting fixed-in-repairs, including taking out old unserviceable MCCB of any description complete all as specified and as directed. |
| 44 | S & F in repair PVC/fibre separator for LT over head line 1100 volts conductor 3/4 wire system for horizontal minimum 04xNos in each span complete with nuts, bolts including taking down old separator complete all as specified and as directed . |
| 45 | S & F in repair LED ammeter, 0-50 Amps of dial size 96x96mm flush mounting with accuracy class 1.0, single phase complete all as specified and directed. |
| 46 | S & F in repair LED Voltmeter, 0-500 Volt of dial size 96x96mm flush mounting with accuracy class 1.0, single phase complete all as specified and directed. |
| 47 | Taking up or down Steel Tubing 20mm bore (dia) and Connections, segregating the Serviceable Pipes and Connections, stacking properly at Site(s) and keep in Safe Custody for re-use/credit, complete all as specified and as directed. |
| 48 | Taking up or down Steel Tubing/PPR 25mm/32 bore (dia) and Connections, segregating the Serviceable Pipes and Connections, stacking properly at Site(s) and keep in Safe Custody for re-use/credit, complete all as specified and as directed. |
| 49 | Taking up or down Steel Tubing 40mm bore (dia) and Connections, segregating the Serviceable Pipes and Connections, stacking properly at Site(s) and keep in Safe Custody for re-use/credit, complete all as specified and as directed. |
| 50 | Taking up or down Steel Tubing 50mm bore (dia) and Connections, segregating the Serviceable Pipes and Connections, stacking properly at Site(s) and keep in Safe Custody for re-use/credit, complete all as specified and as directed. |
| 51 | Taking up or down Steel Tubing/PPR 80mm/90 mm bore (dia) and Connections, segregating the Serviceable Pipes and Connections, stacking properly at Site(s) and keep in Safe Custody for re-use/credit, complete all as specified and as directed. |
| 52 | Supply & fix 3- layer PP-R Polypropylene random copolymer pipes having 90mm outer diameter with SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain polypropylene random fittings as per site requirement i.e. tees, bends, elbow, reducer, enlarger, union, socket etc laid in trenches complete in all respect as specified or directed.Note : (i) Taking out old rusted or unserviceable water pipe of any type or specifications will be measured and paid separately.(ii) Necessary earth work for laying in trench/underground will be measured and paid separately.(iii) Cost of T&P and any type of PP-R fittings required at site for branch connections/fixing of water pipe line deemed to be included in the unit rate quoted by the contractor. |
| 53 | Supply & fix 3- layer PP-R Polypropylene random copolymer pipes having 50mm outer diameter with SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain polypropylene random fittings as per site requirement i.e. tees, bends, elbow, reducer, enlarger, union, socket etc laid in trenches complete in all respect as specified or directed.Note : (i) Taking out old rusted or unserviceable water pipe of any type or specifications will be measured and paid separately.(ii) Necessary earth work for laying in trench/underground will be measured and paid separately.(iii) Cost of T&P and any type of PP-R fittings required at site for branch connections/fixing of water pipe line deemed to be included in the unit rate quoted by the contractor. |
| 54 | Supply & fix 3- layer PP-R Polypropylene random copolymer pipes having 32mm outer diameter with SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain polypropylene random fittings as per site requirement i.e. tees, bends, elbow, reducer, enlarger, union, socket etc laid in trenches complete in all respect as specified or directed by the Engr-in-Charge.Note : (i) Taking out old rusted or unserviceable water pipe of any type or specifications will be measured and paid separately.(ii) Necessary earth work for laying in trench/underground will be measured and paid separately.(iii) Cost of T&P and any type of PP-R fittings required at site for branch connections/fixing of water pipe line deemed to be included in the unit rate quoted by the contractor. |
| 55 | Supply & fix 3- layer PP-R Polypropylene random copolymer pipes having 25mm outer diameter with SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain polypropylene random fittings as per site requirement i.e. tees, bends, elbow, reducer, enlarger, union, socket etc laid in trenches complete in all respect as specified or directed.Note : (i) Taking out old rusted or unserviceable water pipe of any type or specifications will be measured and paid separately.(ii) Necessary earth work for laying in trench/underground will be measured and paid separately.(iii) Cost of T&P and any type of PP-R fittings required at site for branch connections/fixing of water pipe line deemed to be included in the unit rate quoted by the contractor. |
| 56 | Supply, laying, connection and testing 80mm bore, Steel water tubing, galvanised, medium grade with all fittings, laid in trenches, etc complete all as specified and directed. (Note: Excavation and earth work work shall be measured and paid seperately) |
| 57 | Supply, laying, connection and testing 50mm bore, Steel water tubing, galvanised, medium grade with all fittings, laid in trenches, etc complete all as specified and directed. (Note: Excavation and earth work work shall be measured and paid seperately) |
| 58 | Supply, laying, connection and testing 40mm bore, Steel water tubing, galvanised, medium grade with all fittings, laid in trenches, etc complete all as specified and directed. (Note: Excavation and earth work work shall be measured and paid seperately) |
| 59 | Supply, laying, connection and testing 25mm bore, Steel water tubing, galvanised, medium grade with all fittings, laid in trenches, etc complete all as specified and directed. (Note: Excavation and earth work work shall be measured and paid seperately) |
| 60 | Supply, laying, connection and testing 20mm bore, Steel water tubing, galvanised, medium grade with all fittings, laid in trenches, etc complete all as specified and directed. (Note: Excavation and earth work work shall be measured and paid seperately) Please Enable Macros to View BoQ information |
| 61 | Supply, laying, connection and testing 20mm bore, Steel water tubing, galvanised, medium grade with all fittings, laid in trenches, etc complete all as specified and directed. (Note: Excavation and earth work work shall be measured and paid seperately) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender