Tender For Supply Installation Testing And Commissioning Of 3X150tr Water Cooled Screw Chiller With Associated Ancillaries In The Basement Area Of 500 Bedded Hospital At Dr. Rpgmc Kangra At Tanda.

Issued by Government Departments · Kangra, Himachal Pradesh
Tender Value
3.96 Crore
Estimated cost
Bid Submission
18 Sep 2026
2 days left
EMD
7.93 Lakhs
Bank guarantee accepted
Document Fee
7000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Kangra → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Supply Installation Testing And Commissioning Of 3X150tr Water Cooled Screw Chiller With Associated Ancillaries In The Basement Area Of 500 Bedded Hospital At Dr. Rpgmc Kangra At Tanda.

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 10-Sep-2026 Date changed corrigendum Date 14-Sep-2026
2 14-Sep-2026 Date extended Date 18-Sep-2026
3 14-Sep-2026 Date extended Date 18-Sep-2026

BOQ

Name of Work:-
Sl. No. Item Description
1Supply,installation,testing and commissioning of water cooled Screw type Chilling unit with VFD of 150 TR Acutal capacity as per below given condition data & complete with semi-hermetic twin/mono screw Horizontal compressors,motor,factory insulated cooler.water cooled condenser,vibration isolators,integral refrigerant piping and wiring,flow switches and chiller and condenser outlet,first charge of refrigerant,lubricant,microprocessor based control panel,accessories as required.Motor shall be be suitable for 415 + 10% V,50HZ,3ph AC supply as per specification complete in all respects. Less Credit of Useful Dismental Material of three No. Chillers, 6 No. Pumps, 2 No. Cooling Towers is Amounting To Rs. 620000/-(Six Lacs Twenty Thousand only.). The amount will be deducted from over all quoted Tender Rates.
2Necessary arrangement for stepless capacity control capable of reducing compressor capacity down to 25 % of full load. Compressor shall start in unloaded conditions. Manufacture to submit selection sheet at constant condenser & evaporator temperature at part load .Matching shell and tube water cooled condenser of MS Shell and copper tubes ASME Stamped.Matching shell and tube water cooled Evaporator MS Shell and copper tubes ASME Stamped.Chiller shall have water inlet & outlet connection with Victaulic couplings to avoid vibrations transmission.Refrigerant line accessories comprising of safety valve,angle valve,liquid line indication,liquid level control etc. suction line and chiller insulation with minimum 19mm thick polyvinyle nitrile rubber insulation complete as required.Initial /first charge of refrigerant gas& compressor oil as required complete in all respects.
3Screw type chilling machine described above as per specifications and complete in all respects for the operating parameters as given under.
4Evaporator-:
5Leaving water temperature: 44 degree F
6Entering water temperature: 54 degree F
7Fouling factor:0.0005000 sq ft Hr degree f/BTU
8Maximum pressure drop : 3 meter
9Condenser:
10Leaving water temperature: 97.5degree F
11Entering water temperature: 90 degree F
12Fouling factor:0.00100sq ft Hr degree f/BTU
13Maximum pressure drop : 5 meter
14Unit performance shall comply with AHRI standard 550/590 and 551/591.
15Minimum COP shall be 5.9 at AHRI Conditions
16IKW/TR at Design Conitions :-- Not More than 0.69
17IPLV :-not more than 0.38
18NPLV:- Not more than 0.39
19Control/safety Features
20Precise Temp .control,Anti -Freeze & No flow Protection
21Anti-Freeze &No flow Protection
22Automatic run time balance
23SinglePhase / Phase loss Protection
24Over load Protection
25Over Current Protection
26HP/LP Protection
27Compressor Run Hours
28Password Protection
29BMS Compatibility
30Alarm Output
31Stored Past History and Alarm
32DLT Protection
33Oil LevelProtection
34Schedulng to facilitate auto operation
35Graphic Display.
36Civil foundations will be made by the tenderer
37The OEM shall perform and submit the radiographic (X‑ray) examination of long seam welding for evaporator and condenser and test reoprt of the same shall be verified during
38The evaporator and condender shall have ASME Stamping with Even pass system only
39OEM & compressor shall be of same make,chiller compressor sourced from third patry manufacturer under labling program is not acceptable.
40Chiller 150 TR(Actual Capacity)
41Chilled Water Pumps:-
42Supply,Installation, Testing and Commissioinig of CENTRIFUGAL END- SUCTION PUMPS, factory mounted on a base frame with electric motor. All pumps shall be aligned properly as required. The pump motor shall be suitable for 415/3/50 power supply. The motor selected shall be as per IE3 efficiency level and non-overloading type. Pumps with performance characteristics as required complete in all respects.given below :
43Flow = 435 gpm
44Head = 35 m
45CENTRIFUGAL END- SUCTION PUMPS (Flow = 435 gpm)
46Condenser Water Pumps
47Supply,Installation, Testing and Commissioinig of CENTRIFUGAL END- SUCTION PUMPS, factory mounted on a base frame with electric motor. All pumps shall be aligned properly as required. The pump motor shall be suitable for 415/3/50 power supply. The motor selected shall be as per IE3 efficiency level and non-overloading type. Pumps with performance characteristics as required complete in all respects.
48Flow = 545 gpm
49Head = 22 m
50CENTRIFUGAL END- SUCTION PUMPS (Flow = 545 gpm)
51COOLING TOWER
52Supply, Installation, testing and commissioning of fiberglass Reinforced Plastic (FRP) cooling tower suitable for following flow rate as required complete in all respects.
53Water Flow rate 545 USGPM
54Water entering Temperature - 97 °F
55Water entering Temperature - 90 °F
56FRP type Cooling Towers
57PIPING & VALVES
58Supplying and fixing MS class ‘C’ pipes cut to required lengths and complete with welded joints as per site conditions. Quoted price shall include providing and fixing in position fittings, elbows, tees, reducers, expanders, mating flanges & sockets as required. The pipes shall be of following sizes as required complete in all respects.
59150 mm dia
60125 mm dia
61Supplying, installing and fixing in position Butterfly Valves of PN 16 rating and suitable for following pipe sizes as required complete in all respects.
62150 mm Dia
63125 mm Dia
6450 mm Dia
65Supplying, installing and commissioning of Balancing Valves of PN 16 Ratingand suitable for following pipe sizes as required complete in all respects.
66150 mm dia
67Supplying, installing , Testing and commissioning of Y strainers of PN 16 ratingand suitable for for following pipe sizes as required complete in all respects.
68150 mm dia
69Y strainers of PN 16 rating
70Supplying, installing , Testing and commissioning of Dual plate check valves as required complete in all respects.
71150 mm Dia
72Dual plate check valves
73Supply, installing and fixing in position Flexible Coupling installed at chiller inlet& outlet and pump outlets as required complete in all respects.
74150 mm Dia
75Flexible Coupling installed at chiller inlet& outlet
76Supply and installation of Pressure Gauge with siphon & valve as required complete in all respects.
77Pressure Gauge with siphon & valve
78Supply and installation of Mercury in glass Thermometer as required complete in all respects.
79Mercury in glass Thermometer
80Supply and Installation of Water flow switches as required complete in all respects.
81`Water flow switches
82Supply and installation of Ball Valve as required complete in all respects.
8325 mm Dia
8420mm Dia
85Supply and installation of Auto Air vent as required complete in all respects.
8620 mm Dia
87Auto Air vent
88INSULATION
89Supplying and fixing of 32 mm thick Nitril Rubber insulation on chilled water piping/fittings including valves, flanges, union, etc to match the existing specifications as required complete in all respects.
90Pipe of 150 mm dia
91STRUCTURE
92Supply and fabrication of structural steel consisting of MS C Channels , MS Angles & MS Pipes for making supports for chilled water header and cooling tower base frames as required complete in all respects.
93DISMANTALLING
94Shifting of old chiller to the scrap yard as required complete in all respects.
95Shifting of Old chilled water / condenser water pumps as required complete in all respects.
96Shifting of Old Cooling Towers as required complete in all respects.
97ELECTRICAL
98Supply , Installation , Testing and Commissioning of Electrical Panel for the chiller which include ACB 1600 Amp -2 Nos, Bus Coupler ACB 1000 Amp - 1 No. , ACB 800 Amp. - 2 No. MCCB 630 Amp-2 No. , MCCB 250 Amp-6 No., MCCB 125 Amp-3 No., MCCB 63 Amp - 6, Complete Star Delta and DOL (Direct Online Starter) - 13 No. ( Chiller pumps - 4 No., Condenser Pump-4 No, Cooling Towers - 3 No. Hot water Generator - 2 No. ans replacement of AHU (Air Handling Unit) starter panel. All are installed in the existing panels along with necessary modification required for installation and copper cables of different capacity to complete the installation are also include in the cost as required complete in all respects.
99Relaying, & Retermination of 3CoreX 300 Sq mm Aluminum Armoured cable of different capacity as required complete in all respects.
100Relaying and Retermination of power cables of different capacity for pumps as required complete in all respects.
101Supply, laying , termination , Testing & Commissioning of 3 Core X 10 Sq mm Aluminum Armoured cable for CT (Cooling Tower) Fans as per pump Fan ratings as required complete in all respects.
102ELECTRICAL HOT WATER GENERATORS
103Supply, Installation, testing and Commissioining of Electrical Hot WaterGenerators suitable for centralized heating complete with inbuilt auto stepcontroller, High Temperature cut off , Low level Cut off , Phase visualindication, Fault visual and Audio anunciation etc .
104200 KW
105HOT WATER CIRCULATION PUMPS
106Supply,Installation, Testing and Commissioinig of CENTRIFUGAL END-SUCTION PUMPS, factory mounted on a base frame with electric motor. Allpumps shall be aligned properly as required. The pump motor shall be suitablefor 415/3/50 power supply. The motor selected shall be as per IE3 efficiencylevel and non-overloading type. Pumps with performance characteristics as given below :
107250 GPM @35 Mtrs Head
108ELECTRICAL PANEL for Hot Water Generator
109Supply, Installation, Testing and Commissioing of Electrical Panel with oneincomer, 2 out goings for the hot water generators and 3 Nos starters for hotwater circulation pumps
110In Comer 800 Amps TPN - 1 No
111Outgoing 400 Amps TPN - 2 Nos
112Outgoing : DOL or Star Delta Starters for Hot Water Circulation Pumps - 3 Nos
113Panel as described above
114Supply, Laying , termination , Testing & Commissioning of 3.5 C X 300 Sq mmAluminum Armoured cable for Hot Water Generators.
115Supply, Laying , termination , Testing & Commissioning of 4 C X 10 Sq mmAluminum Armoured cable for Hot Water Circulation Pumps.
116Supplying and installation following size of perforated pre-painted M.S. cable trays with perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required complete in all respects.
117300mm (wide) x 50mm(depth) x 1.6mm (thick)
118150mm (wide) x 50mm(depth) x 1.6mm (thick)
119Supply and Laying of GI Earth Strip 25mmx5 mm on surface or in recess for connections etc. as rqeuired.
120Supply and Laying of GI Earth Wire 6 SWG dia on surface or in recess for loop earthing as required.
121PIPING & VALVES
122Supplying and fixing MS class ‘C’ pipes cut to required lengths and complete with welded joints as per site conditions. Quoted price shall include providing and fixing in position fittings, elbows, tees, reducers, expanders, mating flanges & sockets as required. The pipes shall be of following sizes as required complete in all respects.
123200 mm dia
124150 mm dia
125125 mm dia
126Supplying, installing and fixing in position Butterfly Valves of PN 16 rating and suitable for following pipe sizes as required complete in all respects.
127200 mm Dia
128150 mm Dia
129Supplying, installing , Testing and commissioning of Y strainers of PN 16 ratingand suitable for for following pipe sizes as required complete in all respects.
130125 mm dia
131Y strainers of PN 16 rating
132Supplying, installing , Testing and commissioning of Dual plate check valves as required complete in all respects.
133125 mm Dia
134Supply, installing and fixing in position Flexible Coupling installed at chiller inlet& outlet and pump outlets as required complete in all respects.
135125 mm Dia
136Flexible Coupling installed at inlet& outlet
137Supply and installation of Pressure Gauge with siphon & valve as required complete in all respects.
138Pressure Gauge with siphon & valve
139Supply and installation of Mercury in glass Thermometer as required complete in all respects.
140Mercury in glass Thermometer
141Supply and installation of Ball Valve as required complete in all respects.
14225 mm Dia
14320 mm Dia
144INSULATION
145Supplying and fixing of 32 mm thick Nitril Rubber insulation on chilled water piping/fittings including valves, flanges, union, etc to match the existing specifications as required complete in all respects.
146Pipe of 200 mm dia
147Pipe of 150 mm dia
148Pipe of 125 mm dia
14910 years AMC Period for complete system:
150(i) Repair Maintenance and regular examination of HVAC system with equipment maintenance, servicing of AHU's of different capacity, 3 no. chillers 150 T.R. capacity, 1 no. 54 Kw hot water generators, humidifiers, all water pumps, cooling towers, descaling of condensers etc. and interlocking with control valves, dechoking of water pipes etc. and, power control , fuses, contactors relay, timers, Drier Core,Liquid Line stainer, Compressor oil, Refilling of Gas, Loading and Unloading Coils, flow switches, oil rings, rubber coupling, main coupling, mechanical switch, bearings, all types of motor rewinding etc. and maintenance of console panel, AC main supply panel, selector switches, Ampere Meter, Voltmeter including its wiring, minor spare parts and AHU's Belt replacement with alignment of motors etc. as required complete in all respects so as to keep the system functional round the clock with 04 Nos. comprehensive quarterly services in one year and also emergency break down call attending services to the best satisfaction of Engineer-in-charge for 10 years.
151(ii) The firm will provide emergency minor adjustment all back services 24 hours in all working days as well as holidays/ Sundays.The firm will maintain the HVAC System in reliable and efficient operating conditions.The firm in addition will provide necessary technical staff during all VVIP visits at 500 bedded Hospital Dr.RPGMC Tanda.
152(iii) Being hospital OT and ICU area the minimum time for clearing minor faults shall be restricted to 24 Hrs. and in case of major fault the same has to be cleared with in 7 days. In case the company/ firm fails to clear the defects with in prescribed period of time this office shall be free to initiate penal action as per terms and conditions of the contract or as decided by JE incharge at site.
153First year under warranty(Rs. 0/-)
1542nd year under warranty(Rs.0/-)
1553rd year under warranty(Rs.0/-)
156Fourty year(Rs.1375000/-)
157Fifth year(Rs.1445000/-)
158sixth year(Rs.1520000/-)
159seventy year(Rs.1620000/-)
160Eight year(Rs.1730000/-)
161Nineth year(Rs.1800000/-)
162Tentth year(Rs. 1900000/-)
163GST@18%(Rs.2050200/-)
164G. TOTAL:Rs. 13440200/- Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57333252
AUTHORITY Government Departments
TENDER VALUE 3.96 Crore
LAST DATE 18-09-2026
Authority
Authority Name Public Works Department
Work Description Tender for Supply Installation Testing And Commissioning Of 3X150tr Water Cooled Screw Chiller With Associated Ancillaries In The Basement Area Of 500 Bedded Hospital At Dr. Rpgmc Kangra At Tanda.
Basic Detail
Tender No Electrical Division HPPWD Palampur letter No. 3390-94 dated 26-08-2026
Bidding Type Tender
Location
City Kangra
State Himachal Pradesh
Key Dates
Publish Date 14 Sep 2026
Submission Date 18 Sep 2026
Open Date 18 Sep 2026
Finance
Tender Value 3.96 Crore
Tender Fee 7000
EMD 7.93 Lakhs
Exemption Not Available
Document List
1065e9ff-b4d0-4513-89df-096ea602c9ad.html
3X.pdf
BOQ_211945.xls
DECLARATION.pdf
Tendernotice_1 (14).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 14, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 14, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Sep 18, 2026
18:00 IST

Corrigendum-2 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 2 days
Sep 18, 2026
18:00 IST

Corrigendum-3 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 2 days
Sep 18, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 2 days
Sep 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 2 days